• Title/Summary/Keyword: Electrical grounding

Search Result 615, Processing Time 0.027 seconds

Analysis of Deterioration Characteristics for Connection Factor used in Grounding System (접지시스템에 사용되는 접속요소의 열화특성 분석)

  • Gil, Hyoung-Jun;Shong, Kil-Mok;Kim, Young-Seok;Kim, Chong-Min
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.2
    • /
    • pp.9-13
    • /
    • 2015
  • This paper describes the analysis of deterioration characteristics for connection factor used in grounding system. The connection method of grounding system is specified in IEC standard. In order to analyze the deterioration characteristics for connection factor, deterioration test was carried out when the connection factor was buried in salt water and underground. The test connection factors were C-type sleeve, clamp, and exothermic welding. As a consequence, most of the connection factor was corroded, and the electrical resistance decreased after deterioration. The analytical results can be used to establish the safety of grounding system.

The transient grounding impedance measurment of large grid grounding electrodes (대규모 그리드 접지전극의 과도접지임피던스의 측정)

  • Jeon, Byung-Wook;Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jung, Dong-Cheol;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.69-72
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of large grid grounding system associated with the injection point of impulse current The measurement methods consider two possible errors in the grounding-system impedances: (1) ground mutual resistance due to current flow through ground from the ground electrode to be measured to the current auxiliary, (2) ac mutual coupling between the current test lead and the potential test lead The test circuit was set to reduce the error factors. The transient grounding impedance depends on the rise time and injection point of impulse current It is effective that grounding conductor is connected to the center of the large grid grounding system.

  • PDF

A Study on the Optimal Divergence Spacing of the Connecting Grounding Rod to the Dangerous Voltage in the Global Earthing Network of Urban Rail Transit (도시철도 통합접지망에서의 위험전압에 따른 연접접지봉의 최적 분기간격에 관한 연구)

  • Jung, Ho-Sung;Park, Young;Kim, Hyeng-Chul;Kim, Jin-Hee;Kim, Jae-Moon;Cho, Dae-Hoon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.9
    • /
    • pp.1374-1379
    • /
    • 2012
  • Urban rail transit tends to global grounding system in order to control ground potential rise and potential differences between electric equipments. In addition, global grounding system can discharge the large capacity surge current to the ground safely. Since some railway electric equipments are installed all section of line, the global grounding system connected with the connecting grounding wire is more effectively. However, if the fault occurred in the connecting grounding wire area, some dangerous voltage is generated. So, the installation of additional grounding rod will be required. In this study, the global grounding system is simulated using CDEGS program to analyze the divergence spacing of additional ground rod depending on dangerous electric potential characteristics. Grounding net of the each station is modelled in depending on the size of the platform, and the spacing of the connecting grounding rod are compared 50m, 100m, 250m and 400m. Simulation results considering of earth resistivity and underground condition of the connecting grounding wire, spacing of the connecting grounding rod is that less than 250m to spacing of the ground rod was appropriately confirmed.

Study on Measurement Error Reduction Technique when Measuring Touch and Step Voltage of Grounding System (접지시스템의 접촉전압 및 보폭전압 측정오차 감소 기법에 관한 연구)

  • Kim, Dong-Woo;Lim, Young-Bea;Lee, Sang-Ick;Choi, Myeong-Il;Moon, Hyun-Wook
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.1
    • /
    • pp.188-195
    • /
    • 2015
  • This paper presents measurement error reduction technique of touch and step voltage of grounding system based on numerical analysis. When measuring touch and step voltage of grounding system, auxiliary current probes should be located at suitable places. However, the auxiliary probes can not be located at suitable places in such cases as there are buildings and pavements. Therefore, in this paper, we provided measurement error reduction technique of touch and step voltage of grounding system according to the positions of auxiliary probes and angle between auxiliary probes. Also, measurement error analyses of touch and step voltage of grounding system have been conducted using more than one current probe. Based on these analyses, recommended positions of auxiliary probes within allowable measurement errors were presented.

presumption of Earth Resistance by Water Tank Model (수조모델 실험에 의한 접지저항 추정)

  • 고희석;최종규;김주찬;이충식
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.125-131
    • /
    • 2002
  • It is very important to assume potential distribution to be generated in electrode environs and grounding resistance by current beforehand, when incoming at grounding electrode to plan efficient grounding facilities In this paper, we analyzed grounding resistance through a simulation experiment by a water tank scaled model electrode of the rectangular earth plate, a theoretical Calculation result of the rectangular earth plate and measurement of grounding resistance buried rectangular earth plate analysing earth surface potential.

  • PDF

Calculation of Electric Potential Rise of Horizontal Grounding Electrode Caused by Lightning Stroke Currents (뇌격전류에 의한 수평접지극의 전위상승 계산)

  • Lee, Bok-Hee;Cho, Sung-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.12
    • /
    • pp.81-86
    • /
    • 2013
  • An electric potential rise of the grounding electrode developed by the lightning stroke currents should be calculated for the purpose of effective protection of electrical and electronic equipment. In this paper, the electromagnetic model was applied to calculate the harmonic impedance of grounding electrode. Also the empirical equation related to the permittivity and resistivity of soil was used. The lightning current waveforms, which are expressed by the Heidler's equation, were used in order to calculate accurately transient electric potential rises. The transient voltage was obtained by using the simulated harmonic impedance and the lightning current in frequency domain. Finally, the transient voltages of horizontal grounding electrode(10m) under lightning stroke currents were calculated by IFFT(Inverse Fast Fourier Transform).

Characteristics of Transient Grounding Impedances of Rod Electrodes (봉상접지극의 임펼스 전류에 대한 과도접지임피던스 특성)

  • Lee, B.H.;Park, J.S.;Yang, J.J.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1645-1647
    • /
    • 1997
  • Electronic circuits are becoming more vulnerable owing to the development of integrated circuit. Computer and info-communication facilities are very sensitive to surges caused by lightning, and they can suffer a malfunction and damage. Recent concern about damage and upset caused by transient overvoltages has focused on surge protection. The most important parameter in surge protection is the transient grounding impedance. In this paper, the transient grounding impedances of a rod electrode have been measured under impulse current waves. Z-t, Z-i and V-i characteristics of the grounding electrode in according to the length of the grounding lead wire were obtained and analyzed.

  • PDF

Surge Impedance of Grounding System (접지계의 써어지 임피던스)

  • Kim Wang
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.6 no.5
    • /
    • pp.45-49
    • /
    • 1992
  • The transient characteristics of grounding systems are very important in the insulation design of electrical installations and depend on the shape and size of electrodes, soil resistivity and the magnitude and wave of the injection current. This paper establishes an algorithm to compute the surge impedance of two or more grounding systems using the Laplace Transformation technique and deals with the analysis of the transient characteristics on grounding systems.

  • PDF

Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program (MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Lee, Kyu-Jin;Shim, Keun-Bo;Choi, Jong-Kee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.40-46
    • /
    • 2009
  • Although a ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100[kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the MATLAB software program.

Assessment of Potential Interference between Grounding Electrodes Using ETM Method (ETM 기법을 이용한 접지전극의 전위간섭 평가)

  • Gil, Hyoung-Jun;Kim, Dong-Ook;Kim, Dong-Woo;Lee, Ki-Yeon;Choi, Chung-Seog
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.333-336
    • /
    • 2007
  • This paper deals with assessment of potential interference between grounding electrodes using ETM(Electrolytic Tank Modeling) method. When a test current flowed through grounding electrode, potential rise was measured and analyzed using an electrolytic tank in real time. In order to analyze the potential interference between grounding electrodes, ETM method was studies. Potential interference between isolated grounding electrodes was evaluated as functions of the separation distance between grounding electrodes and the configuration of grounding electrode to be induced. It was found that the separation distance between grounding electrodes in reducing the potential interference was a major factor.

  • PDF