• Title/Summary/Keyword: Electrical Facilities of Private Use

Search Result 14, Processing Time 0.027 seconds

A Study on the Actual Condition Investigation of the Disconnecting Switchgear of 170kV GIS (170kV GIS용 단로기의 현장 사용 실태 조사)

  • Lee, Eun-Suk;Kim, Jong-Seo;Cheon, Jong-Cheol
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1180-1183
    • /
    • 2003
  • 170kV GIS(Gas Insulated Switchgear) is widely used in large industrial factory-electrical facilities of private use because has many benefits. But Other equipments's failures are occurred by GIS failures and give rise economic problems to user. Therefore we will examine the actual condition of the 170kV GIS-electrical facilities of private use and are able to confirm the distribution characteristic analysis of disconnecting switchgear. In this paper, we presents the actual condition investigation of the disconnecting switchgear of 170kV GIS-electrical facilities of private use by post - failure pattern, inspection method, test equipments and so forth.

  • PDF

A Study on the Actual Condition of Domestic 170kV GIS- Electrical Facilities of Private Use (국내 자가용 170kV GIS 사용 실태조사)

  • Cheon, Jong-Cheol;Lee, Eun-Suk;Kim, Jong-Seo
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1741-1743
    • /
    • 2003
  • In this paper, We presents the actual condition of domestic 170kv GIS(Gas Insulated Swichgear)- Electrical Facilities of Private Use be examined by post. We are able to confirm the distribution characteristic analysis of GIS failure- type of industry, occurrence frequency, part and counter plan research for failure preventing.

  • PDF

A study based on question on consciousness of electrical safety in electrical facilities for private use (자가용 전기설비 수용가의 전기안전의식에 대한 설문조사)

  • Kim, Sun-Gu;Bae, Seck-Myung;Haung, Gaung-Su;Yi, Geon-Ho
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.394-397
    • /
    • 2005
  • In korea, the power consumption is increasing every year because of economic growth, requiring of convenience and delightfulness condition. As increasing power consumption, Private Use is steadily increasing and the rate of electrical accident is increasing. Therefore we research the electrical safety culture of our people by the survey of electrical safety. The subject to investigation is possessor, occupier of Private Use and electrical safety manager. This paper will be used to base data for the protection of electrical accident and facility accident at Private Use

  • PDF

Preventing Method against the Occurrence of a Corona between a Dead End clamp and a Porcelain Insulator Used in 154kV Substation

  • Han, Woon-Ki;Choi, Jong-Soo;Lee, Jun;Kim, Jae-Chul
    • International Journal of Safety
    • /
    • v.6 no.2
    • /
    • pp.22-26
    • /
    • 2007
  • An episode of corona is a heterogeneity-caused electric discharge that occurs when electric fields are formed layer on layer and concentrated on an electrode. Electric wires built at the tip of 154kV private facilities use dead end clamp spawns corona from homogeneity caused by field concentration. Corona induces power loss, noise, insulator failure and more. In this research, we've studied the characteristics of coronas that take place in porcelain insulators and terminal electric wires of supporting hard wares (dead end clamp) that are set up as spares in the 154kV private facilities use hydroelectricity installations to support electric wires. Corona, which cannot be identified by regular methods, was measured utilizing UV image camera. As the result of measuring corona via UV image camera, we've confirmed that the depletion of insulators was accelerated following the wire end treatment method and validated the stress intensity of insulators at various lengths of bare wires caused by electric fields via FEMLAB. We have also proposed a new model for relieving homogeneity-caused field concentration, and after analyzing the proposed model via FEMLAB, we've confirmed that the concentration of field distribution was indeed reduced. Such results are exploited in installation of private facilities use equipments, maintenance of insulators and hard wares as well as safety enhancement, and are anticipated to be effectively utilized in corona prevention measures.

The Study of Cable Fault Case and the Fault Management System of Electrical Facilities for private use (수용가 전기설비 사고처리 시스템 및 케이블 사고사례 연구)

  • Kim, Young-Seok;Shong, Kil-Mok;Kim, Sun-Gu
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.59-62
    • /
    • 2009
  • When happen the electrical facilities accident the one's diagnosis system of fault cause was constructed by FMEA method Cable accident cause is given by accident cause that can happen in each one's diagnosis and accident probability value. From the verification of system, the one's diagnosis system agreed well with result that analyzed actual state. Thus, the system is judged to be used effectively examine for accident cause of electrical facilities.

  • PDF

The Study on the Actual Condition about Facility Accident Case and PL Recognition of the Safety Manager in Electric Installation for Private Use (수용가 전기설비 관리자의 PL인식 및 설비사고사례에 관한 실태연구)

  • Kim, Young-Seok;Shong, Kil-Mok;Jung, Jong-Wook;Jung, Jin-Su;Kim, Sun-Gu;Lee, Jun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.309-312
    • /
    • 2008
  • In this paper, we investigated electric safety manager's PL recognition and accident occurrence of electric power facilities(power cable, transformer, circuit breaker) in electric installation for private use. The target of questionnaire survey is 450 electric installations for private use, 154 responded the questionnaire among these and it occupied 35.8%. Most of receiving voltage were 22.900kV. The questionnaire survey says that 58% of electric safety manager knew well about PL contents and 42% of them did not recognize about PL contents, About the PL application of electrical facility accidents, 82.4% of them must applied PL law, 5.8% of them did not need the PL law. Reason of PL application occupied 64% for stability of electrical facility and product, 19% for prevention of same accident. The accident of transformer occupied most and the power cable accident were much next. The questionnaire survey results, electric safety managers are interested in PL content. thev expected necessity of PL application about electrical accident strongly.

  • PDF

The Study on Facility Accident Case and PL Recognition of the Safety Manager in Electric Installation for Private Use (자가용 전기설비 안전관리자의 PL인식 조사 및 사고사례 연구)

  • Kim, Young-Seok;Shong, Kil-Mok;Kim, Sun-Gu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.9
    • /
    • pp.40-46
    • /
    • 2008
  • In this paper, we investigated electric safety manager's PL recognition and accident occurrence of electric power facilities in electric installation for private use. The target of questionnaire survey is 450 electric installations for private use, 154 responded the questionnaire among these and it occupied 35.8[%]. The questionnaire survey says that 58[%] of electric safety manager knew well about PL contents and 42[%] of them did not recognize its. 82.4[%] of them must applied PL law in electric installation, 5.8[%] of them did not need the PL law. Reason of PL application occupied 64[%] for stability of electrical facility and product, 19[%] for prevention of same accident. The accident of transformer occupied most and the power cable accident were much next. The questionnaire survey results, electric safety managers are interested in PL contents, they expected necessity of PL application about electrical accident strongly.

A Survey on the Actual Conditions of False-Tripping of MCCB ard ELB (배선용 및 누전차단기 오동작 실태조사)

  • Yoo, Jae-Geun;Lee, Sang-Ick;Jeon, Jeong-Chay;Jeong, Jong-Wook;Lim, Yong-Bae
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.223-227
    • /
    • 2004
  • False-tripping of MCCB(Molded Case Circuit Breaker) and ELB(Earth Leakage Circuit Breaker), using to protect overload and ground-fault accidents in power system raise direct and indirect losses like as information loss, facilities damage, slipup of goods production in industry place. Cause of false-tipping of MCCB and ELB is various and cause analysis of false-tripping is mostly made up by inference because trip is not reappeared. This paper investigated and analyzed causes and influences of false-tripping of MCCB and ELB by making up a question to safety managers of two hundred and eighteen electrical facilities for private use. Also, the necessity of experimental study on the effect of harmonics on false-tipping of MCCB and ELB was presented.

  • PDF

A Study on the Development of Value-Added Service Based on Remote Electrical Safety Inspection of Electrical Facilities for Private User (일반용 전기설비의 원격 전기안전점검 모델을 활용한 전기안전 부가서비스 제공 방안에 관한 연구)

  • Choi, Myeong-Il;Yoo, Jae-Geun;Jeon, Jeong-Chay;Jung, Yong-Uk
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.365-368
    • /
    • 2008
  • This paper introduce the model of remote monitoring system that combine information technology in electrical safety checks that has been done by professional staff. And for general use, electrical safety Value-Added Service using remote check data were presented. In the near future, If demand and interests of Value-Added Service will be increased, this will be a electrical safety Value-Added Service as an important role in the blind spot of country electricity disaster.