Analysis of the Switch Installation Criteria by Increasing Operating Capacity in Distribution Line (배전선로 운전용량 상향에 따른 개폐기 설치 기준 분석)

  • Jo, Nam-Hun;Ha, Bok-Nam;Lee, Heung-Ho
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.6
    • /
    • pp.290-295
    • /
    • 2002
  • The present assignment in installing the number of switches for distribution line was made on the basis of a normal feeder capacity 7,000kVA in KEPCO(Korea Electric Power Corporation), Korea. But the normal capacity is revised to 10000kVA in 1998. Even increasing limit of the operating capacity of the distribution lines enables us to give some benefit for the operation flexibility and investment cost of the distribution system. It is disadvantageous in the viewpoint of supply reliability. In distribution systems, switches are equipped to improve the reliability of distribution systems by minimizing the outage section due to fault and maintenance. Utility generally improves the reliability by minimizing the length of outage section, which is caused by fault and maintenance, through switch equipment on distribution system. In order to cope with the changes such as operation capacity, it is necessary to study whether the present criteria is reasonable or not, also to confirm whether the present criteria of installing switches in line is improved or not. In this study, we proposes the number of switch per feeder on the basis of present operation capacity in distribution system.

Time Resolved Measurement of Electric Field Distribution in a Liquid Dielectric

  • Arii, Kiyomitsu;Ihori, Haruo;Fujii, Masaharu
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.2C no.6
    • /
    • pp.287-291
    • /
    • 2002
  • Measurement technique of three dimensional electric field distribution in liquid dielectrics have been studied. Kerr effect and computed tomography(CT) method have been used. Measuring time has been shortened by the use of multi-optical systems to less than several milliseconds. Near future, electric field distribution in front of a streamer tip of breakdown would be measured.

The Development of the Optical Network for the Automation Systems in Electric Power Companies (전력자동화서비스를 위한 광네트워크 설계 및 모뎀개발)

  • Kim, Myong-Soo;Hyun, Duck-Hwa;Cho, Seon-Ku
    • Proceedings of the KIEE Conference
    • /
    • 2002.07d
    • /
    • pp.2543-2545
    • /
    • 2002
  • There are many applicable services such as remote metering, load control, distribution line automation, Pole transformer Monitoring having their own networks in the electric power company. The application of the optical network technology as the back-born network to the Automation Systems in KEPCO is potentially beneficial in reliability, speed, and expandability. The 1-core and 2-core optical modems were developed and used by the Distribution Automation System. But, They had some disadvantages and advantages. So, We designed the new optical modems applied each advantages. This paper presents some of design efforts and test results for the multi-channel optical modem at KRPRI.

  • PDF

A Comparative Study on the Electric Power Efficiency of IDCs with AC and DC Distribution Systems (교류배전시스템과 직류배전시스템이 적용된 IDC 전력효율 비교연구)

  • Son, Sung-Yong;Mok, Hyung-Soo;Park, Kyung-Seok;Hong, Jun-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.8
    • /
    • pp.38-44
    • /
    • 2008
  • Internet Data Centers (IDCs), which are resulted by the rapid progress of Information Technology industry, consist of high-density digital loads with internet server systems. Introduction of DC distribution system may simplify the conventional electric power conversion system, and may result in the improvement of electric power efficiency. However, this conjecture has never been tested under Korean IDC environment. In this study, electric power efficiency of DC distribution system from KT Namsuwon IDC is contrasted with that of conventional AC distribution system from KT Bundang IDC. DC 48[V] based distribution system showed 13.2[%] higher efficiency than the conventional AC based distribution system. The further analysis with the assumption of DC 380[V] suggests efficiency improvement over 25[%] can be achieved.

Applications of an Adaptive Reclosing in Power Distribution Systems (배전시스템에서 적응재폐로방식의 적용에 관한 연구)

  • Rim, Seong-Jeong;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.955-957
    • /
    • 1998
  • This paper presents an adaptive reclosing scheme to improve the reliability in power distribution systems. For an originated faults, this scheme can determine the number of reclosing attempts, so that minimizes the affect of electric facility and customers' load. To verify the effectiveness of the proposed scheme. numerical simulation which calculates a various indices to consider the reliability and the effect of electric facility, is carried out with actual field data. Results show that the proposed scheme can be applicable to field operation.

  • PDF

A Study on Standardization of the Electric Facilities for distribution & Translations - Focused on the Electric Facilities in Subway Stations - (수변전설비의 표준화에 관한 연구 - 지하철 역사전기설비를 중심으로 -)

  • Cho, Sung-Pil;Kang, Cha-Nyeong;Kim, Hak-Lyun
    • Proceedings of the KSR Conference
    • /
    • 2006.11b
    • /
    • pp.838-843
    • /
    • 2006
  • In our modern society, such electric facilities as lighting, elevators, water supplies, drainages, waste water treatments and landscape lighting are being more enlarged, diversified and technology-intensive owing to outstanding technological development, while they require reliable and safe electricity. On the other hand, as more electric energy is consumed with more complicated systems operated, any accident from a personal electric system is likely to have wider spreading effects. In particular, the electric receivers and transformers installed for such public facilities as subway stations require highest safety, reliability and economy, but such requirements tend to be less considered than such financial requirements as budget conditions, much less their safety and reliability. In such a circumstance, this study was aimed at suggesting some standards for safe, reliable and economic subway electric systems in terms of their scale, location and uses. Specifically, this study put forwards the ways to optimize and standardize the electric systems including receivers and transformers for subway stations in order to make them safer, more reliable and economic.

  • PDF

Investigations on the Thermal Phenomena in High Current Electric Switchboard (대전류 통전시 배전반내의 열적 현상에 관한 연구)

  • Lee, B.W.;Kang, J.S.;Sohn, J.M.;Choi, W.J.;Seo, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 1999.11d
    • /
    • pp.1051-1053
    • /
    • 1999
  • In this work, thermal phenomena and temperature rise due to thermal source in electric switchboard were investigated using analytical measures. Electric switchboards are assemblies of panels on which are mounted switches, circuit breakers, high current busbars, meter, fuses and terminals essential to the operation of electric equipment. It is very difficult to predict the temperature rise in switchboard due to the existence of several heat sources. To overcome this situations, we focused on the eddy current distribution on the panel of switchboard caused by high current busbars as a fundamental basis. And thermal sources including busbar and switchgear have been considered. Furthermore, thermal transfer phenomena in switchboard was considered theoretically. Finally, three-dimensional thermal model for eddy current analysis has been adopted and FEM analysis was conducted. As a result, three-dimensional numerical analysis found to be applicable to the analysis of thermal phenomena in switchboard.

  • PDF

A Study on the Reliability of Electric Power Distribution System (배전시스템의 신뢰도에 관한 연구)

  • 김경철;최홍규;원진희
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.3
    • /
    • pp.61-66
    • /
    • 2002
  • Electric power distribution networks are prime examples of systems where a very high degree of reliability is expected. Reliability is the probability of a device or system performing its function adequately for the period of time intended and intented operating conditions intented. This paper shows that a better meshed distribution configuration over the case study of radial configuration distribution system was selected by comparing the indices obtained from EDSA\`s reliability worth assessment of distribution systems program.

A Study on the Optimal Operation of Fuel Cell in Power Systems (전력계통에 있어서 신에너지전원(연료전지)의 최적 운용방안에 관한 연구)

  • 노대석;홍승만;이은미
    • Proceedings of the KAIS Fall Conference
    • /
    • 2002.11a
    • /
    • pp.141-144
    • /
    • 2002
  • Recently, the operation of power distribution systems has become more difficult because the peak demand load is increasing continuously and the daily load factor is getting worse and worse. Also, the consideration of deregulation and global environment in electric power industry is required. In order to overcome these problems, a study on the planning and operation in distribution systems of dispersed generating sources such as fuel cell systems, photovoltaic systems and wind power systems has been performed energetically. This study presents a method for determining an optimal operation strategy of dispersed co-generating sources, especially fuel cell systems, in the case of both only electric power supply and thermal supply as well as electric power supply. In other words, the optimal operation of these sources can be determined easily by the principle of equal incremental fuel cost and the thermal merits is evaluated quantitatively through Kuhn-Tucker's optimal conditions. In order to select the optimal locations of those sources, an priority method using the comparison of total cost at the peak load time interval is also presented. The validity of the proposed algorithms is demonstrated using a model system.