Dynamic Link Library 기법을 이용한 과전류 계전기 모델링 (The Modeling of OverCurrent Relay using Dynamic Link Library)

  • 성노규;서훈철;여상민;김철환
    • 전기학회논문지
    • /
    • 제58권6호
    • /
    • pp.1065-1070
    • /
    • 2009
  • This paper presents the new technique of modeling using Dynamic Link Library(DLL) in ElectroMagnetic Transients Program - Restructured Version(EMTP-RV) in which we have simplified the procedures of OverCurrent Relay(OCR) modeling. The DLL function is designed to allow EMTP-RV users to develop advanced program model modules and interface them directly and intimately with the EMTP-RV engine. The modeled OCR is verified by simulating the various fault cases in the distribution system. Also, the performance for the modeling of OCR using DLL is compared with that of the method using the control components of EMTP-RV and using EMTP/MODELS. The results show the validity of modeled OCR and the effectiveness of the method using DLL function.

EMTP 선로모델이 과전압 해석결과에 미치는 영향에 관한 연구 (A Study on the Effects of Line Constants Models for the Overvoltage Analysis in EMTP)

  • 김경탁;곽주식;권동진;구교선;우정욱
    • 조명전기설비학회논문지
    • /
    • 제24권10호
    • /
    • pp.33-41
    • /
    • 2010
  • There are several overvoltages by abnormal conditions in power system. We need to calculate these ovevoltages for the insulation design and the fault analysis. For these calculations, we used EMTP(Electro-magnetic Transients Program). During EMTP calculations, the accurate modelling of the equipments is very important for analysis results. In this paper, we considered the effects of the modelling condition's changes for transmission line within EMTP modelling cases of overvoltage analysis. Specially, we considered CB closing cases of 765[kV] system. So, we had changed the calculation frequencies of Line Constants, which is used for CB closing cases. In addition, we compared the calculation result and the measured result.

EMTP를 이용한 개폐서지 분석 및 선로 모델의 영향 (Analysis of Switching Surge and Effect of Line Models using EMTP)

  • 임수빈;여상민;김철환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1940-1941
    • /
    • 2007
  • 양질의 전력을 요구하는 경향으로 인해 과도현상이 높은 관심의 대상이 되고 있다. 스위치를 개방 후 반 사이클 후에는 스위치 양극간 전압은 발전기 전압 첨두치의 2배가 된다. 본 논문에서는 EMTP에서 제공하는 선로모델 중 비연가 선로와 연가선로를 이용하여 개폐서지와 선로모델과의 관계를 모델링 하였다. 송전단 측에서는 스위치 개폐 후 두 선로모델 사이의 전압 파형에는 큰 차이가 없었으나 수전단 측에서는 두 선로모델 간에 현저한 차이를 보여주었다.

  • PDF

EMTP MODELS를 이용한 부족주파수 계전기 동작 구현 (The Implementation of Operation for Underfrequency Relay using EMTP MODELS)

  • 안상필;허정용;김철환;박남옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.575-577
    • /
    • 2004
  • This paper propose methods to implement operation of underfrequency relay using EMTP MODELS. Simulation results shows the operation of the frequency relay as well as the status of generator and power systems. The simulation method described in this paper can thus be employed as a very useful tool in the testing of frequency relay algorithms and/or in the development of any new ones.

  • PDF

3상 일괄형 Pipe Type HTS 케이블의 정상 및 과도상태 해석 (Steady and Transient State Analysis on Three Phase-in One Enclosure Type HTS Cable)

  • 장주영;이종범;김용갑
    • 전기학회논문지
    • /
    • 제59권10호
    • /
    • pp.1748-1753
    • /
    • 2010
  • This paper suggests an improved technique to establish the modeling regarding steady and transient state on three phase-in one cryostat type HTS(High Temperature Superconducting) cable. The proposed modeling is established using EMTP/ATPDraw and TACS and MODELS provided by that. It has higher accuracy than the conventional method, as the actual HTS cable is modelled. Steady and transient state analysis performed by EMTP/ATPDraw calculate the current of conductor, shield and former, respectively. In case of the transient state modeled quench state occurred by a single line-to-ground fault, current of conductor shield and former are also calculated, respectively. Especially, various fault resistances and angles are considered to improve the reliability during transient state analysis. Analysis results reveal that the proposed technique improves the accuracy of modeling.

EMTP MODELS를 이용한 2차 아크 모델링 기법에 관한 연구 (A Study on the Technique for the Secondary Arc Modeling Using EMTP MODELS)

  • 안상필;김철환;채영무
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 C
    • /
    • pp.1217-1219
    • /
    • 1998
  • For the improvement of an adaptive SPAR(Single-Phase Auto-Reclosure) and novel protection schemes, it is important to simulate arc faults. But, it is difficult to reproduce the real arc behaviour, i.e. the extinction phenomenon exactly by computer simulations due to extremely random behavior of secondary arc. This paper proposes a new computer modeling techniques for the primary and the secondary arc separately, which can be implemented with EMTP MODELS routine, and the performance of the proposed model is simulated on a typical 154 [kV] korean transmission line system.

  • PDF

EMTP를 이용한 전압 불안정 현상의 동적 시뮬레이션 (A Dynamic Simulation at Voltage Instability using EMTP)

  • 허정용;권오상;김철환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.131-133
    • /
    • 2003
  • Voltage instability has been studied for some decade now. But, there is not generally accepted definition of voltage instability because of the complex phenomenon and the variety of ways in which it can manifest itself. Both IEEE and CIGRE have the respective definitions. The areas of voltage instability research arc the analysis, simulation and countermeasure of voltage instability. In this paper, we perform a dynamic simulation of voltage instability and voltage collapse using EMTP MODELS. The exponential load model is designed with MODELS and this load model is connected with test power system. The result shows the process of voltage change in time domain when the voltage instability or voltage collapse occurs.

  • PDF

마이크로터빈과 연료전지의 EMTP-RV 모델링을 통한 마이크로그리드 내 동특성 분석 (Dynamic analysis of Microturbine and FuelCell in MicroGrid using EMTP-RV)

  • 서규석;주재현
    • 조명전기설비학회논문지
    • /
    • 제24권10호
    • /
    • pp.42-48
    • /
    • 2010
  • The Microsource has to supply high quality Power that has high reliability and high energy efficiency to Load according to operating type of Microgrid. The energy sources of microsource type have various dynamic characteristic and transient response corresponding to classes and application skill. This paper shows dynamic characteristic of Microgrid according to Energy Source of microsource type. This research has been carried out by detailed modelling of Microturbine system and Fuelcell system. All models are realized by EMTP/RV and simulated change of operating type and load increase within Microgrid of DC constant voltage inverter model and Microturbine, Fuelcell based Microsource.

EMTP를 이용한 철도차량용 주변압기 고압권선의 공진특성 분석 (Analysis of Resonant Characteristics in High Voltage Windings of Main Transformer for Railway Vehicle using EMTP)

  • 정기석;장동욱;정종덕
    • 한국철도학회논문집
    • /
    • 제19권4호
    • /
    • pp.436-444
    • /
    • 2016
  • 철도차량용 주변압기 고압권선은 고압인통선에 유기되는 이상전압과 내부공진을 발생 시킬 수 있는 다양한 주파수 대역의 고유주파수를 가진다. 공장시험은 다양한 파형과 지속시간을 지닌 이상전압의 여자가능성을 판단하는데 한계가 있다. 본 연구는 전자계과도해석프로그램(이하 EMTP)을 이용하여 고압권선 모델을 설계하고 초기 전압분포와 전압-주파수 관계 측면에서 내부공진특성을 모의분석한다. 턴 단위의 집중매개변수는 변압기 형상정보부터 계산되며, 각 레이어 단위로 합산된 서브모델은 네트워크 모델로 결합되어 EMTP의 라이브러리를 통해 구현한다. 사례연구는 주파수 변동에 따른 레이어 단위의 전압-주파수 관계 특성과 시계열 영역에서 전압 확대 및 분포 양상을 보여준다.

계통 연계 3상 인버터를 위한 LCL 필터 설계 및 EMTP-RV 시뮬레이션 연구 (A Study on LCL Filter Design and EMTP-RV Simulation for Grid-connected Three Phase Inverter)

  • 고윤석
    • 한국전자통신학회논문지
    • /
    • 제16권2호
    • /
    • pp.261-270
    • /
    • 2021
  • 본 연구에서는 계통 연계 3상 인버터를 위한 LCL 필터를 설계 방법론을 연구하였다. 먼저, 대표적인 필터 구조들에 대해서 3상 인버터의 계통 연계를 위한 필터로서의 적용 시 장단점을 분석하였다. 다음, 3상 인버터의 계통 연계를 위한 필터 설계 방법론들을 분석하여 그리드 연계 시 고조파 요구 조건을 만족할 수 있는 효과적인 필터 설계 방법론을 결정하였다. 그리고 설계 방법론의 유효성을 확인하기 위해서 EMTP-RV를 이용하여 3상 인버터, LCL 필터 그리고 필터의 성능을 평가하기 위한 성능 평가 시스템을 모델링 하였다. 끝으로, 하나의 3상 인버터에 대한 LCL 필터를 설계하였으며, EMTP-RV 시뮬레이션 작업을 통해 3상 인버터의 출력 전류 리플의 크기가 제한됨을 확인함으로서 설계 방법론의 유효성을 검증할 수 있었다.