• Title/Summary/Keyword: Duval Triangle Method

Search Result 3, Processing Time 0.017 seconds

A Study on the Reliability of Failure Diagnosis Methods of Oil Filled Transformer using Actual Dissolved Gas Concentration (유중가스농도를 이용한 유입식 변압기 고장진단 기법의 신뢰성에 관한 연구)

  • Park, Jin-Yeub;Chin, Soo-Hwan;Park, In-Kyoo
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.3
    • /
    • pp.114-119
    • /
    • 2011
  • Large Power transformer is a complex and critical component of power plant and consists of cellulosic paper, insulation oil, core, coil etc. Insulation materials of transformer and related equipment break down to liberate dissolved gas due to corona, partial discharge, pyrolysis or thermal decomposition. The dissolved gas kinds can be related to the type of electrical faults, and the rate of gas generation can indicate the severity of the fault. The identities of gases being generated are using very useful to decide the condition of transformation status. Therefore dissolved gas analysis is one of the best condition monitoring methods for power transformer. Also, on-line multi-gas analyzer has been developed and installed to monitor the condition of critical transformers. Rogers method, IEC method, key gas method and Duval Triangle method are used to failure diagnosis typically, and those methods are using the ratio or kinds of dissolved gas to evaluate the condition of transformer. This paper analyzes the reliability of transformer diagnostic methods considering actual dissolved gas concentration. Fault diagnosis is performed based on the dissolved gas of five transformers which experienced various fault respectively in the field, and the diagnosis result is compared with the actual off-line fault analysis. In this comparison result, Diagnostic methods using dissolved gas ratio like Rogers method, IEC method are sometimes fall outside the ratio code and no diagnosis but Duval triangle method and Key gas method is correct comparatively.

Fault Analysis of Transformer using Tunable Infrared Gas Sensors (가변 파장형 적외선 센서를 이용한 변압기 결함 진단)

  • Gun-Ho Lee;Seung-Hwan Yi
    • Journal of Sensor Science and Technology
    • /
    • v.32 no.1
    • /
    • pp.55-61
    • /
    • 2023
  • The objective of this study is to determine the concentrations of mixed gases by establishing a diagnosis method of a transformer using tunable-wavelength optical infrared sensors. Absorption of infrared light by methane, acetylene, and ethylene gases injected is measured from the outputs of the infrared sensors. Regression analysis equations of the gas concentrations are acquired from their respective measured absorption. The obtained concentrations are as follows: -3-9 % errors above 600 ppm(methane), 3 % errors above 1200 ppm(acetylene), and 10 % errors above 500 ppm(ethylene). The concentration inference equations obtained using the individual gases are applicable when the absorption wavelength bands do not overlap. The results of the fault analysis of a transformer using the Duval triangle method and the tunable infrared gas sensors are as follows: temperature faults with -1-1% errors and energy faults with -7-7 % errors.

DGA Interpretation of Oil Filled Transformer Condition Diagnosis

  • Alghamdi, Ali Saeed;Muhamad, Nor Asiah;Suleiman, Abubakar A.
    • Transactions on Electrical and Electronic Materials
    • /
    • v.13 no.5
    • /
    • pp.229-232
    • /
    • 2012
  • DGA is one of the most recent techniques developed to diagnose the fault condition on oil filled insulation transformers. There are more than 6 known different methods of DGA fault interpretation technique and so there is the likelihood that they may vary in their interpretations. A series of combined interpretation methods that can determine the power transformer condition faults in one assessment is therefore needed. This paper presents a computer program- based system developed to combine four DGA assessment techniques; Rogers Ratio Method, IEC Basic Ratio Method, Duval Triangle method and Key Gas Method. An easy to use Graphic User Interface was designed to give a visual display of the four techniques. The result shows that this assessment method can increase the accuracy of DGA methods by up to 20% and the no prediction result had been reduced down to 0%.