• 제목/요약/키워드: Dual Exchanger

검색결과 24건 처리시간 0.03초

이중 열원 히트펌프 시스템의 난방 성능과 운전 특성 (Heating Performance of Heat Pump System Using Dual Heat Source and Its Operation Characteristics)

  • 임효재;손병후
    • 한국지열·수열에너지학회논문집
    • /
    • 제17권2호
    • /
    • pp.30-41
    • /
    • 2021
  • This paper presents the heating performance analysis results of a heat pump system using a dual heat source. In this paper, a dual heat source refers to the ground-coupled heat exchanger using both a surface water heat exchanger (SWHE) and a vertical ground heat exchanger (VGHE). In order to evaluate the system performance, we installed a monitoring system to measure the temperature and power consumption of a heat pump and then collected operation data with 4 different load burdened ratios of the dual heat source heat exchanger. During the whole measurement period, the average heating capacity of a water-to-water heat pump unit was 37.3 kW. In addition, the compressor of the heat pump consumed 9.4 kW of power, while the circulating pump of the dual heat source heat exchanger used 6.7 kW of power. Therefore the average heating coefficient of performance (COP) for the heat pump unit was 4.0, while the entire system including the circulating pump was 2.7. Finally, the parallel use of SWHE and VGHE was beneficial to the system performance; however, further researches are needed to optimize the design data for various load ratios of the dual heat source heat exchanger.

이중탐침법을 이용한 수평형 지중열교환기 뒤채움재의 열확산계수 측정 (Thermal Diffusivity Measurement of Backfilling Materials for Horizontal Ground Heat Exchanger Using Dual-Probe Method)

  • 손병후;최항석
    • 한국지열·수열에너지학회논문집
    • /
    • 제7권2호
    • /
    • pp.51-59
    • /
    • 2011
  • Storage and transfer heat in soils are governed by the soil thermal properties and these properties are therefore needed in many engineering applications, including horizontal ground heat exchanger for ground-coupled heat pumps. This paper presents the measured results of the thermal diffusivity of soils(silica, quartzite, limestone, sandstone, and masonry soils) used for the trench backfilling materials of the horizontal ground heat exchanger. To assess this thermal property, we (i) measure the soil thermal conductivities and volumetric heat capacities using dual-probe method and (ii) compare the estimates from the de Vries method of summing the heat capacities of the soil constituents. The results show that the thermal diffusivity tends to increase as dry soil begins to wet, but it approaches a constant value or even decreases as the soil continues to wet. Measurements made by using the dual-probe method agreed well with independent estimates obtained using the single-probe method.

GHP 배열회수용 이중 쉘-튜브형 배기가스 열교환기의 설계 최적화 (Design Optimization of Dual-Shell and Tube Heat Exchanger for Exhaust Waste Heat Recovery of Gas Heat Pump)

  • 이진우;신광호;최송;정백영;김병순
    • 대한기계학회논문집 C: 기술과 교육
    • /
    • 제3권1호
    • /
    • pp.23-28
    • /
    • 2015
  • 본 논문은 GHP 에 사용되고 있는 이중 쉘-튜브형 배기가스 열교환기의 설계 변수의 변화에 따라 열전달 및 마찰특성 변화를 알아보기 위해 CFD 와 RSM 을 이용하여 최적화를 수행하였다. CFD 해석은 복잡한 형상의 열교환기 해석에 유용한 도구이나, 해석결과를 얻기까지 많은 시간이 소요된다. 이러한 해석시간을 줄이고, 유용한 결과를 얻기 위해 RSM 과 병행하여 최적화 설계를 진행하였다. 시뮬레이션 결과를 이용한 RSM 해석결과, 배플 6 개, 튜브 25 개에서 최적화되었으며, 기존 보다 차압 및 열전달 성능이 약 12.2% 개선되었다. 이러한 CFD 와 RSM 을 이용한 최적화 기법은 다양하고 복잡한 형상의 열교환기 해석에 유용함을 확인하였다.

공기열원 2중히트싱크 열펌프의 성능해석 (Performance Analysis of Heat Pump System with Air Source Evaporator and Single Unit Dual Sink Condenser)

  • 우정선;이세균;이재효;박효순
    • 태양에너지
    • /
    • 제18권4호
    • /
    • pp.11-22
    • /
    • 1998
  • Floor panel heating system using hot water is the primary heating system of domestic residential building. This paper presents the results of performance analysis of the heat pump system with air source evaporator and single unit dual sink(SUDSk) condenser. The heat exchanger combines two separated condensers into a single condenser and the object of the SUDSk condenser is to release energy to dual sinks, i.e. air for air heating system and water for panel heating system in one single unit. Simulation program is developed for single unit dual source(SUDS) SUDSk heat pump system and some experimental data are obtained and compared with simulation results. Differences of heating capacity and COP in dual source operating mode are 7% and 8% respectively. Simulation results are in good agreement with test results. Therefore, developed program is effectively used for design and performance prediction of dual source dual sink heat pump system with SUDS evaporator and SUDSk condenser.

  • PDF

[ $Ca^{2+}$ ]-dependent Long-term Inactivation of Cardiac $Na^+/Ca^{2+}$ Exchanger

  • Lee, Jee-Eun;Kang, Tong-Mook
    • The Korean Journal of Physiology and Pharmacology
    • /
    • 제11권5호
    • /
    • pp.183-188
    • /
    • 2007
  • Using BHK cells with stable expression of cardiac $Na^+/Ca^{2+}$ exchanger(BHK-NCX1), reverse mode(i.e. $Ca^{2+}$ influx mode) of NCX1 current was recorded by whole-cell patch clamp. Repeated stimulation of reverse NCX1 produced a cytosolic $Ca^{2+}$-dependent long-term inactivation of the exchanger activity. The degrees of inactivation correlated with NCX1 densities of the cells and were attenuated by reduced $Ca^{2+}$ influx via the reverse exchanger. The inactivation of NCX1 was attenuated by(i) inhibition of $Ca^{2+}$ influx with reduced extracellular $Ca^{2+}$, (ii) treatment with NCX1 blocker($Na^{2+}$), and (iii) increase of cytoplasmic $Ca^{2+}$ buffer(EGTA). In BHK-NCX1 cells transiently expressing TRPV1 channels, $Ca^{2+}$ influx elicited by capsaicin produced a marked inactivation of NCX1. We suggest that cytoplasmic $Ca^{2+}$ has a dual effect on NCX1 activities, and that allosteric $Ca^{2+}$ activation of NCX1 can be opposed by the $Ca^{2+}$-dependent long-term inactivation in intact cells.

SUDS증발기를 사용한 2중열원 열펌프의 성능해석 (Performance analysis of dual source heat pump system with single unit dual source evaporator)

  • 우정선;이세균;이재효;박효순
    • 설비공학논문집
    • /
    • 제11권3호
    • /
    • pp.391-400
    • /
    • 1999
  • The efficiency and capacity of an air source heat pump system decrease as the ambient temperature drops. One strategy of avoiding the decrease of the efficiency and capacity in air source heat pump system is to switch to another thermal energy source. Water can be a good candidate for the heat source. This paper presents the results of the performance analysis of heat pump system with a single unit dual source(SUDS) evaporator The heat exchanger combines two separated evaporators into a single evaporator and the object of the SUDS evaporator is to recover energy from dual heat sources, i.e. air and water. Simulation program is developed for the dual source heat pump system with a SUDS evaporator and experimental data are obtained and compared with the simulation results. Differences in heating capacity and COP are 7% and 8% respectively. Simulation results are in good agreement with the test results. Therefore, the developed program is effectively used for the design and performance prediction of the dual source heat pump system with a SUDS evaporator.

  • PDF

듀얼셀 모델을 이용한 오일쿨러의 방열성능 연구 (A Study on the Thermal Performance of an Oil Cooler with Dual-cell Model)

  • 박상준;이영림
    • 한국산학기술학회논문지
    • /
    • 제12권3호
    • /
    • pp.1111-1116
    • /
    • 2011
  • 열교환기는 자동차, 공조시스템 및 기타 다양한 산업시설에 이용되고 있어 그 수요가 매우 넓다. 보통 고효율의 루버핀 열교환기는 비오염 환경에 많이 사용되고 파형핀 열교환기는 건설 현장 등 오염이 문제가 되는 곳에 사용된다. 본 논문에서는 공기측과 오일측에 각기 다른 형태의 격자를 사용할 수 있는 듀얼셀 모델을 이용하여 오일쿨러나 연료쿨러에 쓰이는 전형적인 열교환기에 대한 방열 성능을 수치해석하였다. 먼저 풍동 실험을 통한 열교환기 방열성능 실험을 수행하여 1차원 방열성능 데이터를 확보하였다. 다음으로 3차원 수치해석 듀얼셀 열교환기 모델을 이용하여 통과 풍량에 따른 열교환량을 예측하였다. 이러한 모델은 통과 풍속의 불균일도에 따른 열교환량을 예측할 수 있어 방열설계 정확성 향상에 크게 기여할 수 있다.

Development of Induction Heated Hot Water Producer using Soft Switching PWM High Frequency Inverter

  • Fujita Kentarou;Moisseev Serguei;Gaimage Laknath;Chandhaket Sarawouth;Muraoka Hidekazu;Nakaoka Mutsuo
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2003년도 춘계전력전자학술대회 논문집(2)
    • /
    • pp.491-494
    • /
    • 2003
  • This paper presents a new conceptual electromagnetic induction eddy current-based stainless steel plate spiral type heater for heat exchanger or Dual Packs Heater in hot water producer, boiler steamer and super heated steamer, which is more suitable and acceptable for new generation consumer power applications. In addition, all active clamped edge resonant PWM high frequency inverter using trench gate IGBTs power module can operate under a principle oi zero voltage soft communication with PWM is developed and demonstrated for a high efficient Induction heated hot water producer and boiler in the consumer power applications. This consumer induction heater power appliance using active clamp soft switching PWM high frequency inverter is evaluated and discussed on the basis of the simulation and experimental results.

  • PDF

Dual Mode Phase-Shifted ZVS-PWM Series Load Resonant High-Frequency Inverter for Induction Heating Super Heated Steamer

  • Hisayuki Sugimura;Hidekazu Muraoka;Tarek Ahmed;Srawouth Chandhaket;Eiji Hiraki;Mutsuo Nakaoka;Lee, Hyun-Woo
    • Journal of Power Electronics
    • /
    • 제4권3호
    • /
    • pp.138-151
    • /
    • 2004
  • In this paper, a constant frequency phase shifting PWM-controlled voltage source full bridge-type series load resonant high-frequency inverter using the $4^{th}$ generation IGBT power modules is presented for innovative consumer electromagnetic induction heating applications, such as a hot water producer, steamer and super heated steamer. The bridge arm side link passive capacitive snubbers in parallel with each power semiconductor device and AC load side linked active edge inductive snubber-assisted series load resonant tank soft switching inverter with a constant frequency phase shifted PWM control scheme is evaluated and discussed on the basis of the simulation and experimental results. It is proved from a practical point of view that the series load resonant and edge resonant hybrid high-frequency inverter topology, what is called, DE class type, including the variable-power variable-frequency regulation function can expand zero voltage soft switching commutation area even under low output power setting ranges, which is more suitable and acceptable for newly developed induction heated dual pack fluid heaters. Furthermore, even the lower output power regulation mode of this high-frequency load resonant tank inverter circuit is verified so that this inverter can achieve ZVS with the aid of the single auxiliary inductor snubber.