• Title/Summary/Keyword: Dry Air Insulation

Search Result 42, Processing Time 0.033 seconds

Analysis on the Dielectric Characteristics of Dry Air According to Pressures for Developing an Eco-friendly High Voltage Switchgear (친환경 고압배전반 개발을 위한 dry air의 압력별 절연내력특성 분석에 관한 연구)

  • Nam, Seok-Ho;Kang, Hyoung-Ku
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.8
    • /
    • pp.1560-1565
    • /
    • 2011
  • The environmental pollution caused by green-house gases such as $CO_2$ and $SF_6$ has been becoming the main issue of industrial society. Many developed countries are making efforts to minimize the amount of $CO_2$ emission come from the operation of high voltage electrical apparatuses. As a part of these efforts, 180 countries signed the Kyoto Protocol in 1997 to cut back on their green-house gas emissions. Nowadays, the study on the development of dry air insulated switchgear (DAIS) which is known as an eco-friendly electrical apparatus is in progress. A DAIS is advantageous for minimizing the effect of impurities and enhancing the dielectric characteristics over an air insulated switchgear (AIS) by applying constant pressure to an enclosed cubicle. Therefore, a study on the electrical insulation performance of dry air as a gaseous insulation medium is conducted in this paper to substitute a gas insulated switchgear (GIS) for DAIS. As results, it is verified that the AC dielectric characteristics of dry air are similar to those of air and the lightning impulse dielectric characteristics of dry air are superior to those of air at 1bar pressure condition. However, dry air is of inferior dielectric characteristics to $SF_6$ at 4bar pressure condition. Finally, it is suggested that the internal pressure of DAIS should be over 4bar pressure to develop a high voltage switchgear which has similar electrical performance to a conventional GIS. Also, the empirical formulae on calculating the maximum electric field intensity at sparkover of dry air are deduced by experiments according to pressures. It is expected that these results are helpful to design and develop a high voltage electrical apparatus.

AC Breakdown Analysis by Epoxy Thickness in Composite-Insulation (복합절연물내의 에폭시 두께에 따른 AC 절연파괴 분석)

  • Jung, Hae-Eun;Yun, Jae-Hun;Kim, Byoung-Chul;Kang, Seong-Hwa;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.468-469
    • /
    • 2007
  • $SF_6$ gas used widely as insulating component in electric power industry has excellent in insulation and arc extinguishing performance in gas-insulated switchgear. However, the concern about eco-friendly alternative gas is currently rising, because $SF_6$ gas is one of the main greenhouse gases. As one of the study for $SF_6$ free technology, composite-insulation technology is focused in this paper. To analyze the influence by epoxy thickness change, the composite-insulation composed of dry-air and epoxy was used in this paper. To analyze AC breakdown by the epoxy thickness, needle-plane electrode was used and needle was molded by epoxy. Under the gas pressure ranged from 0.1 to 0.6MPa, the breakdown voltage of dry-air were measured in AC electric field. The data of composite-insulation were acquired by changing the thickness of epoxy used in each composite-insulation under the same condition.

  • PDF

Surface Discharge Characteristics in Dry-Air on Laminated Epoxy Solid Dielectrics and Conductive Particle (적층된 에폭시 고체유전체와 도전성 파티클에 대한 Dry-Air의 연면방전특성)

  • Lim, Dong-Young;Jeon, Jong-Cheul;Bae, Sungwoo;Lee, Kwang-Sik;Park, Won-Zoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.2
    • /
    • pp.93-101
    • /
    • 2016
  • This paper presents the surface discharge characteristics in Dry-Air on laminated epoxy solid dielectrics and conductive particles in order to provide the valuable information for the insulation design of eco- friendly gas insulated switchgear. To improve insulation performance, the three types of the laminated epoxy solid dielectrics were proposed, and it was revealed that their surface discharge characteristics were similar to the bakelite dielectrics of same-laminated types. From the surface discharge characteristics of dry air, it was demonstrated that the effect of conductive particles on surface discharge voltage was dominant when there are this particles at the shortest electrode gap and that the degradation of insulation performance on the conductive particles was evident in epoxy than teflon. These phenomena were interpreted in terms of particle-triggered discharge mechanism and electric field of triple junction, respectively.

Analysis of AC Breakdown Voltage accoding to epoxy thickness of Composite Insulation for Dry-Air/Epoxy under non-uniform electric field (불평등전계에서의 건조공기/에폭시 복합절연물의 에폭시 두께에 따른 AC 파괴전압 분석)

  • Heo, Jun;Lee, Seung-Su;Lim, Kee-Joe;Jung, Hae-Eun;Kang, Seong-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2008.10a
    • /
    • pp.113-114
    • /
    • 2008
  • The purpose of this paper is to analyze AC Breakdown of solid/air composite insulation depending on the thickness and the pressure of dry air for eco-friendly insulation. SF6 gas has been widely used in electric equipment as gas insulation because of high dielectric strength and arc extinguishing performance. However, because SF6 gas is one of the green house effect gases, alternative insulation such as SF6 mixture, extremely low temperature gas, vacuum, liquid and solid insulating are being investigated.

  • PDF

Surface Discharge Characteristics Study on the Laminated Solid Insulator in Quasi-Uniform Electric Field with Dry Air

  • Min, Gyeong-Jun;Bae, Sungwoo;Kang, Byoung-Chil;Park, Won-Zoo
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.603-609
    • /
    • 2015
  • Dry air is an excellent alternative to $SF_6$ gas and is used as an insulation gas in Eco-friendly Gas Insulated Switchgears (EGISs), which has gained popularity in industry. Solid insulators in EGIS play an important role in electrical insulation. On the other hand, surface discharge can occur easily when solid insulators are used. This paper explored the surface discharge characteristics on the structure of three-layered laminated solid insulators to elevate the flashover voltage. A laminated solid insulator was inserted after the quasi-uniform electric field was formed in the test chamber. Dry air was then injected to set the internal pressure to 1 ~ 6 atm, and the AC voltage was applied. When identical solid insulators were stacked, the surface discharge characteristics were similar to those of a single solid insulator. On the other hand, the flashover voltage rose when the middle part was thicker and had lower permittivity than the top and bottom parts in the laminated solid insulator. Based on experimental results, when stacking a solid insulator in three layers, the middle part of the solid insulator should be at least four times as thick as the top and bottom parts and have lower permittivity than the others. In addition, the flashover voltage increased with increasing gas pressure on the surface of the laminated solid insulator due to the gas effect. This study may allow insulation design engineers to have useful information when using dry air for the insulation gas where the surface discharge can occur.

Evaluation of Building Envelope Performance of a Dry Exterior Insulation System Using Truss Insulation Frame (트러스 단열 프레임을 이용한 건식 외단열 시스템의 외피 종합 성능 평가)

  • Song, Jin-Hee;Lee, Dong-Yun;Shin, Dong-Il;Jun, Hyun-Do;Park, Cheol-Yong;Kim, Sang-Kyun
    • Journal of the Architectural Institute of Korea Structure & Construction
    • /
    • v.35 no.6
    • /
    • pp.153-164
    • /
    • 2019
  • The presence of thermal bridges in a building envelope cause additional heat loss which increases the heating energy. Given that a higher building insulation performance is required in these cases, the heat loss via thermal bridges is a high proportion of the total heat energy consumption of a building. For the dry exterior insulation system that uses mullions and transoms to fix insulation and exterior materials such as stone and metal sheet, the occurrence of thermal bridges at mullions and transoms is one of the main reasons for heat loss. In this study, a dry exterior insulation system using the truss insulation frame (TIF) was proposed as an alternative to metal mullions. To evaluate the building envelope performance, structural, air-leakage, water-leakage, fire-resistance, thermal, and condensation risk tests were conducted. In addition, the annual energy consumption associated with heating and cooling was calculated, including the linear thermal transmittance of the thermal bridges. As a result, the dry exterior insulation system using TIF achieved the allowable value for all tests. It was also determined that the annual heating load of a building was reduced by 36.7 % when the TIF dry exterior insulation system was used, relative to the dry exterior insulation system using steel pipes without additional insulations.

Impulse Breakdown Behaviors of Dry Air as an Alternative Insulation Gas for SF6

  • Li, Feng;Yoo, Yang-Woo;Kim, Dong-Kyu;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.3
    • /
    • pp.24-32
    • /
    • 2011
  • [ $SF_6$ ]gas, which has an excellent dielectric strength and interruption performance, is used in various applications such as gas insulated switchgear (GIS) in substations. However, since $SF_6$ has a high global warming potential (GWP), it is necessary to find an eco-friendly alternative insulation gas. In order to examine the possibility of using alternative insulation gases for $SF_6$ in power distribution system equipment, the dielectric strength and physical phenomena of dry air in a quasi-uniform electric field are investigated experimentally in this paper. As a result, the breakdown voltages for positive polarity are higher than those for negative polarity under impulse voltage applications. The negative 50[%] flashover voltage, $V_{50}$ of dry air under conditions above 0.4[MPa] gas pressure, is higher than 150[kV], that is the basic impulse insulation level of distribution equipment. The $V_{50}$ increases linearly with increasing the gas pressure, regardless of the waveform and polarity of the applied impulse voltages. The voltage-time curves are dependent on the rise time of the impulse voltage and gas pressure. Furthermore, streamer discharge was observed through light emission images by an ICCD camera under impulse voltage applications.

Electrical Breakdown Characteristics of Composite Insulation Composed of Epoxy Resins with N2, Dry-air in Non-uniform Field (불평등 전계 시 에폭시와 N2, dry-air 혼합절연체의 절연파괴특성)

  • Jung, Hae-Eun;Park, Seong-Hee;Kang, Seong-Hwa;Lim, Kee-Jo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.06a
    • /
    • pp.462-463
    • /
    • 2007
  • SF6 widely used as insulating gas is rising as the environment problem. For decreasing this greenhouse gas, electrical breakdown characteristics of composite insulation composed of epoxy resins with N2, air are studied in non-uniform field. The gap of needle to plane was 3mm, 5mm. The pressure of air, nitrogen was varied within the range of 0.1~0.6MPa. The thickness of a needle is 1mm and the curvature radius of the end of needle is 100um. The diameter of a plane made of the stainless steel is 50mm. As a result of the experiment, the breakdown voltage is increased about 3 times when epoxy resins is composited. The thickness of epoxy resins filled opposite to electrode concentrated electric field weakly influences on breakdown voltage.

  • PDF

Electrical Breakdown Characteristics of Epoxy and dry-air Composite Insulation (에폭시와 dry-air 혼합절연물의 절연파괴특성)

  • Jung, Hae-Eun;Oh, Jin-Heon;Lim, Jong-Nam;Kang, Seong-Hwa;Lim, Kee-Jo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1389-1390
    • /
    • 2007
  • SF6 gas used widely as insulating component is rising as the environment problem. Electrical breakdown characteristics of epoxy and dry-air composite insulation was investigated on thickness of epoxy and pressure of dry-air under non-uniform field. The gap of needle to plane was from 2mm to 5mm. The pressure of dry-air was varied within the range of $0.1{\sim}0.6$ MPa. The thickness of a needle was 1mm and the curvature radius of a needle end was 100um. The diameter of a plane made of the stainless steel was 50mm. As a result of the experiment, breakdown voltage was increased about 3 times when epoxy was used. The impact that the thickness of epoxy influences on breakdown voltage was poor. It needs suitable thickness computation because the insulating gap of the gas is short as epoxy thickness increases.

  • PDF

A Study on Characteristics of Insulation Breakdown and Surface Discharge by the Mixing Ratio of Dry Air/O2 gas mixtures (Dry Air/O2 혼합가스의 혼합비에 따른 절연파괴 및 연면방전 특성 연구)

  • Seok, Jeong-Hoo;Beak, Jong-Hyun;Lim, Dong-Young;Bae, Sungwoo;Kim, Ki-Chai;Park, Won-Zoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.6
    • /
    • pp.49-57
    • /
    • 2015
  • This paper presents the discharge characteristics and economic feasibility of a Dry $Air/O_2$ and a $N_2/O_2$ mixture gas in order to review $SF_6$ alternative. From AC discharge experiment in an quasi-uniform field, it was found that the optimal $N_2/O_2$ mixing ratio which breakdown voltage and surface flashover voltage were the highest was 70/30 and that the pressure dependence on the breakdown voltage was higher than that of the surface flashover voltage in the Dry $Air/O_2$ and the $N_2/O_2$ mixture gas. The mixing ratio (70/30) and the tendency of the pressure dependence were described in detail based on physical factors (impact ionization coefficient, electron attachment coefficient, secondary electron emission coefficient) involved in discharge mechanism and a electron source, respectively. In addition, the performance insulation and the economic feasibility of the Dry $Air/O_2$ and the $N_2/O_2$ mixture gas were discussed so that Dry $Air/O_2$ mixture gaswas more suitable than $N_2/O_2$ mixture gas to the $SF_6$ alternative.