• Title/Summary/Keyword: Drop transfer

Search Result 862, Processing Time 0.026 seconds

An Experimental Study on the Performance of the Louver Fin Type Heat Exchanger by the Change of the Driving Condition (운전조건 변화에 따른 루버휜 열교환기 성능변화에 관한 실험적 연구)

  • Kim, Jung-Kuk;Koyama, Shigeru;Kuwahara, Ken;Kim, Dong-Hwi;Park, Byung-Duck
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.440-445
    • /
    • 2008
  • The present study was investigated the effect of the driving condition on the performance of a louver fin and tube type heat exchanger under frosting condition. Heat transfer rate and pressure drop by frost were experimentally investigated. Effects of the wet blub temperature and the shape of a fin on heat transfer performances has been also investigated. The key parameters were fin type(louver and corrugate fin) and the wet blub temperature of air (0.5, 1.0, $1.5^{\circ}C$). The heat transfer performance of the louver fin and tube type heat exchanger was higher by 0.89% than the corrugate fin type. As the wet blub temperature of air were increased, the heat transfer rate, pressure drop and mass of frost of three test models(Type A, B, C) were increased. Especially, the maximum heat transfer rate and maximum pressure drop were shown for the louver fin and tube type heat exchanger. As a experimental result, the enhancement factor(EF) of louver fin and tube type heat exchanger was $0.2{\sim}0.4$ due to the high pressure drop.

  • PDF

A Study on Heat Transfer and Pressure drop Characteristics in Plate Heat Exchange (판형 열교환기의 열전달 및 압력강하 특성에 관한 연구)

  • 서무교;박재홍;김영수
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.25 no.3
    • /
    • pp.581-587
    • /
    • 2001
  • Plate heat exchange(PHE) will be applied to the refrigeration and air conditioning systems as evaporators or condensers for their high efficiency and compactness. The purpose of this study is the analyze the characteristics of heat transfer and pressure drop of plate heat exchanger. Numerical work was conducted using the FLUENT code k-$\varepsilon$model. Also the dependence of heat transfer coefficient and friction factor on Reynolds number was investigated. As the Reynolds number increases, it is found that heat transfer coefficient also increases, but friction factor decreases. The study examines the internal flow, thermal distribution and the pressure distribution in the channel of plate heat exchanger. The results of CFD analysis compared with experimental data, and the difference of friction factor and Nusselt number in plate heat exchanger are 10% and 20%, respectively, Therefore the CFD analysis model is effective for the performance prediction of plate heat exchanger.

  • PDF

Design of the Impact Absorber used for a Shuttle Car for LMTT with respect to the Drop Height of a Container (컨테이너의 낙하높이에 따른 LMTT 용 Shuttle Car 의 충격흡수기 설계)

  • 한동섭;한근조;심재준;김태형
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2004.10a
    • /
    • pp.1479-1482
    • /
    • 2004
  • LMTT (Linear Motor-based Transfer Technology) is horizontal transfer system in the maritime container terminal for the port automation. The system is driven by PMLSM (Permanent Magnetic Linear Synchronous Motor) that is consists of stator modules on the rail and shuttle car. This paper investigates the effect of the drop height of container on impact reaction force of the Impact Absorber (IA) in shuttle car for LMTT. The results of this investigation are obtained from detailed finite element analysis for various parameters, such as the spring coefficient, the drop height of container.

  • PDF

Pressure Drop and Heat Transfer Characteristics of Internal Flow of the Rectangular Tube for Automobile Heat Exchanger (차량용 열교환기 사각관 내부 흐름에서 압력강하 및 열전달 특성)

  • Kang, Hie-Chan;Jun, Gil-Woong;Kim, Kwang-Il
    • 유체기계공업학회:학술대회논문집
    • /
    • 2006.08a
    • /
    • pp.489-492
    • /
    • 2006
  • The present work was performed to investigate the thermal and hydraulic characteristics of flow inside the plain and turbulator flat tubes for the automobile application. The pressure drop and heat transfer coefficient at laminar, transition and turbulent regimes were studied experimentally and numerically. The flow transition was confirmed by flow visualization and quantitative data. It is proposed equations for the friction and heat transfer coefficient in the fully developed laminar flow inside rectangular tube as function of aspect ratio.

  • PDF

Forced Convection Characteristics of V type Circular-finned Tube Heat Exchanger (V형 원형휜-원형관의 강제대류 열유동 특성)

  • Lee, Jong-Hwi;Lim, Mu-Gi;Kang, Hie-Chan
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1348-1354
    • /
    • 2009
  • The purpose of the present study is to investigate the flow resistance and the heat transfer characteristics of V type circular fin-tube heat exchanger. Four kinds of V type fin having the same fin area and the different span wise angle tested numerically. Test data for the heat transfer, pressure drop and fin temperature were shown and discussed. The pressure drop and heat transfer increased for decreasing the span wise angle up to 58% and 25% respectively.

  • PDF

Flow Analysis of Heat Exchanger with Delta Winglet Vortex Generators on CFD (와류 생성기가 설치된 핀 튜브 열교환기의 열 유동해석)

  • Hwang, Seong-Won;Jeong, Ji-Hwan
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1166-1171
    • /
    • 2009
  • Fin-tube heat exchangers are widely used in refrigeration systems. To improve the performance of fin-tube heat exchangers, the shape of plain fin was developed in slit fin and louver fin. These pins have higher heat transfer performance as well as larger pressure drop. Recent studies of a delta winglet vortex generators(DWVG) show less heat transfer capacity than louver fin. However, the DWVG have very small pressure drop. This paper compares the performance for the plain fin and DWVG fin in terms of flow characteristics and heat transfer based on CFD analyses. The DWVG generate vortex and delayed flow separation and leads to a reduction of a wake region behind a tube. The results show that the DWVG produce improved heat transfer and reduced pressure drop compared to a plain fin. This result is opposite to the Reynolds analogy.

  • PDF

Dynamic Analysis of Metal Transfer using VOF Method in GMAW (II) - Short Circuit Transfer Mode - (VOF 방법을 이용한 GMA 용접의 금속 이행에 관한 동적 해석 (II) - 단락 이행 모드의 해석 -)

  • 최상균;고성훈;유중돈;김희진
    • Journal of Welding and Joining
    • /
    • v.15 no.3
    • /
    • pp.47-55
    • /
    • 1997
  • Dynamic characteristics of the short circuit mode are investigated using the Volume of Fluid (VOF) method. When the initial molten drop volume, contact area and wire feed rate are given, rate change of the molten bridge profiles, pressure and velocity distributions are predicted. The electromagnetic force with proper boundary conditions are included in the formulation to consider the effects of welding current. It is found that the molten metal is transferred to the weld pool mainly due to the pressure difference caused by the curvatures in the initial stage, and electromagnetic force becomes dominant factor in the final stage of short circuit transfer. Necking occurs at the contact position between the molten drop and weld pool, and the initial molten drop volume and welding current have significant effects on break-up time.

  • PDF

Numerical prediction of shell-side flow with inclined baffles (경사진 배플이 있는 셀측의 수치적 해석)

  • 김은필
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.24 no.5
    • /
    • pp.119-124
    • /
    • 2000
  • A finite element method is applied to investigate the characteristics of the fluid flow and heat transfer performance in a channel in terms of the various effects of baffle cuts, baffle angles, and leakages. The results show that the decrease of a baffle cut gives a good heat transfer enhancement. However, it also increases pressure drop. In the case of an inclined baffle, the result shows that the pressure drop decreases with a reasonable heat transfer performance. But a steeply inclined baffle gives adverse effects on the performance of the channel. The clearances between baffle-to-shell and tube-to-baffle affect the overall performance. The effects of these parameters are discussed in details.

  • PDF

The Drag Reduction and Convective Heat Transfer Characteristics of Two-Phase Flow with Polymer Additives (고분자 물질 첨가에 의한 2상 유동의 마찰 항력 감소와 대류 열전달 특성)

  • Lee, Dong-Sang;Kim, Jae-Guen;Cha, Kyong-Ok
    • Proceedings of the KSME Conference
    • /
    • 2000.04b
    • /
    • pp.71-76
    • /
    • 2000
  • This experimental study was conducted to figure out the drag reduction and convective heat transfer in vertical downward two-phase flow with polymer additives. The drag reduction effect were analyzed by using the difference of the pressure drop between the flow with polymer additives and without it. Experimental results show that the pressure drop with polymer additives is less than the pressure drop without polymer in vertical downward two-phase flow. And the convective heat transfer has decreased with increasing the polymer concentration in vertical downward two-phase flow.

  • PDF

A study on airside performance of finned-tube heat exchanger according to fin combination and fin pitch variation of using large scale model (확대모형을 이용한 휜-관 열교환기의 휜 형상 및 휘 간격 변화에 따른 공기측 성능에 관한 연구)

  • Byun, Ju-Suk;Jeon, Chang-Duk;Lee, Jin-Ho;Kim, Jin-Woo
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.281-287
    • /
    • 2005
  • This study investigates the pressure drop and heat transfer characteristics of heat exchanger according to the combination of fin configuration and fin pitch of each row by the similitude experiments with the finned-tube geometry scaled as large as four times Finned-tube heat exchanger has 2 rows, and fin geometry consists of two cases, louver-louver and louver-slit. Fin pitch is varied with three types in each case, 6-6 mm, 8-8 mm and 8-6 mm. Results show that total heat transfer can be occurred evenly at each row by varying the fin pitch of 1st row and 2nd row. Heat transfer rate and pressure drop characteristics change according to the combination for fin geometry and fin pitch.

  • PDF