• Title/Summary/Keyword: Distance Relay

Search Result 237, Processing Time 0.039 seconds

Application Analysis for Loss of Excitation Relay of Generator Protection (발전기 보호용 계자상실 계전기의 적용 분석)

  • Oh, Yong-Taek;Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.4
    • /
    • pp.322-326
    • /
    • 2014
  • Recently, the LOE(loss of excitation) incidents are occurred in domestic synchronous generator frequently, the synchronous generator protection system has been much attention for the LOE protection of the incidents that threats synchronous generators and power systems. This paper was showed the characteristics and practices of distance relay that widely used LOE protection relaying in generator. Firstly, the operating characteristics and the impedance locus for LOE of the generator protection were introduced. Even if the conventional simulation program is used for modeling, but it is difficult to implement a LOE modeling and simulation of synchronous generator. So, the LOE relay operation data collected from thermal power plant and nuclear power plant in real fields were analyzed. By reviewing the applications of GE Mho relays, the reliability of LOE for synchronous generator protection in domestic were improved.

A Study on Protection of Generator Asynchronization by Impedance Relaying (임피던스 계전기를 이용한 발전기 비동기 투입 보호 연구)

  • Lee, Jong-Hweon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.11
    • /
    • pp.2000-2006
    • /
    • 2011
  • Asynchronous phenomenon occurs on the synchronous generators under power system when a generator's amplitude of electromagnetic force, phase angle, frequency and waveform etc become different from those of other synchronous generators which can follow instantly varying speed of turbine. Because the amplitude of electromagnetic force, phase frequency and waveform differ from those of other generators with which are to be put into parallel operation due to the change of excitation condition for load sharing and the sharing load change, if reactive current in the internal circuit circulates among generators, the efficiency varies and the stator winding of generators are overheated by resistance loss. Where calculation method of protection settings and Logic for Protection of Generator Asynchronization will be recommended, A distance relay scheme is commonly used for backup protection. This scheme, called a step distance protection, is comprised of 3 steps for graded zones having different operating time. As for the conventional step distance protection scheme, Zone 2 can exceed the ordinary coverage excessively in case of a transformer protection relay especially. In this case, there can be overlapped protection area from a backup protection relay and, therefore, malfunctions can occur when any fault occurs in the overlapped protection area. Distance relays and overcurrent relays are used for backup protection generally, and both relays have normally this problem, the maloperation, caused by a fault in the overlapped protection area. Corresponding to an IEEE standard, this problem can be solved with the modification of the operating time. On the other hand, in Korea, zones are modified to cope with this problem in some specific conditions. These two methods may not be obvious to handle this problem correctly because these methods, modifying the common rules, can cause another coordination problem. To overcome asynchronizing protection this paper describes an improved backup protection coordination scheme using a new Logic that will be suggested.

A Light-Weight RFID Distance Bounding Protocol (경량 RFID 경계 결정 프로토콜)

  • Ahn, Hae-Soon;Bu, Ki-Dong;Yoon, Eun-Jun;Nam, In-Gil
    • The KIPS Transactions:PartC
    • /
    • v.17C no.4
    • /
    • pp.307-314
    • /
    • 2010
  • Recently, it is proved that contactless smart-card based RFID tags, which is used for proximity authentication, are vulnerable to relay attacks with various location-based attacks such as distance fraud, mafia fraud and terrorist fraud attacks. Moreover, distance bounding protocols have been researched to prevent these relay attacks that can measure the message transmitted round-trip time between the reader and the tag. In 2005, Hancke and Kuhn first proposed an RFID distance bounding protocol based on secure hash function. However, the Hancke-Kuhn protocol cannot completely prevent the relay attacks because an adversary has (3/4)$^n$ attack success probability. Thus, this paper proposes a new distance-bounding protocol for light-weight RFID systems that can reduce to (5/8)$^n$ for the adversary's attack success probability. As a result, the proposed protocol not only can provide high-space efficient based on a secure hash function and XOR operation, but also can provide strong security against the relay attacks because the adversary's attack success probability is optimized to (5/8)$^n$.

Analysis of the response of a distance relay for wind farm intertie protection (풍력발전단지 연계선 보호 거리계전기의 응동 특성 분석)

  • Kang, Yong-Cheol;Lee, Hye-Won;Zheng, Tai-Ying;Kang, Hae-Gweon
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.484_485
    • /
    • 2009
  • Power output of a wind farm fluctuates throughout a day. This affect a distance relay for wind farm intertie protection because a voltage of a relaying point varies due to fluctuating output of a wind farm. This paper describes the analysis of the response of a distance relay for intertie protection when the power output of a wind farm increases. A series of single phase to ground faults were also simulated and analyzed with PSCAD/EMTDC generated data.

  • PDF

Algorithm of Line dangerous Index and Predicting Distance Relay Zone 3 acting time by using real time data (실시간 데이터를 이용한 선로 위험도 산출 알고리즘 및 거리계전기 Zone 3 동작 예측 알고리즘)

  • Kim, Jin-Hwan;Lee, Seung-Jae;Choi, Myeon-Song;Lim, Il-Hyung;Lim, Seong-Il;Kim, Sang-Tae
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.278_279
    • /
    • 2009
  • Nowaday, many people study about Black-Out. In this paper, I introduce how to calculate the Dangerous Index against Black-Out, and prediction of Distance relay error action on Zone 3. we consider the real data by I-PIU which will be set on the system. The dangerous Index is calculated three index about Cascading. The prediction of Distance relay is considered by other facilities of power system. This two algorithm can be used on the center system, when the system is on danger, also on the normal states for security.

  • PDF

An Improvement of Distance Relay Technique Reliability using Elman Network (Elman Network를 이용한 거리계전기법의 신뢰성 향상)

  • Jung, H.S.;Lee, J.J.;Shin, M.C.;Lee, B.K.;Park, C.W.;Jang, S.I.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07a
    • /
    • pp.212-214
    • /
    • 2000
  • The distance relay technique used for transmission line protection operates overreach and underreach to the self protection region because the power system becomes complex and fault conditions are different. To solve these problems, this paper describes new technique to set the reliable self protection lesion. The trip region of the quadrilateral distance relay is set by training of multi layer recurrent elman network. The proposed network is able to reach the trip zone for the fault impedance, fault initial angle and source impedance variance correctly.

  • PDF

Development of Digital Distance Relay Algorithm Using Fuzzy Inference System on Underground Power Cable Systems (퍼지추론 시스템을 이용한 지중송전계통 보호용 디지털 거리계전 알고리즘 개발)

  • Jung, Chae-Kyun;Lee, Jong-Beom
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.502-503
    • /
    • 2006
  • If the fault occurs on the underground Power cable system, the fault current on the sheath has the influence on all sections because it's returned through earth at the directly grounded point and operation point of SVL(Sheath Voltage Limiter) at joint box. Therefore, the earth resistance and the operation of SVL have an effect on the zero-sequence current. Then the impedance between relaying point and fault point is Increased. That causes the overreach of distance relay. For these reasons, the distance relay algorithm for protecting of the underground power cable systems was developed. It effectively advance the errors using ACI(Advanced Computing Intelligence) technique. In this algorithm, the optimization was performed by fuzzy inference system and genetic algorithm.

  • PDF

A Digital Distance Relaying Algorithm using a Wavelet Transformation (Wavelet 변환을 이용한 디지털 거리계전 알고리즘)

  • Kang, Sang-Hee;Lee, Joo-Hun;Nam, Soon-Ryul;Park, Jong-Keun
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.10
    • /
    • pp.1215-1221
    • /
    • 1999
  • A high speed digital distance relaying algorithm based on a Wavelet Transformation is proposed. To obtain stable phasor values very quickly, first, a lowpass filter which has low cutoff frequency is used. Secondly, db2(Daubechies 2) Wavelet which has the data window of 4 samples is used. A FIR filter which removes the DC-offset component in current relaying signals is applied. In accordance with a series of tests, the operation time of the relaying algorithm is less than 3/4 cycles after faults in a 80 [km], 154[kV], 60[Hz] over-head transmission line system.

  • PDF

Dynamic Response Characteristics of Distance Relay Including the Instrumental Devices (계기용 변성기를 포함한 거리계전기의 동특성 해석)

  • 김남호;박종근
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.41 no.3
    • /
    • pp.227-236
    • /
    • 1992
  • In this paper, a simulation program of relaying system including the CT and CPD ( capacitive potential device ) is developed to study the effect of its operation under various system conditions. To deal with the dynamic characteristics of relaying system, state space technique is applied, and then the state equations of CT, CPD and mho distance relay are constructed. Also the dynamic response characteristics of overall relaying system is verified by digital simulation. Since the proposed model is capable of taking arbitrary input waveforms from EMTP in analyzing its dynamic responses, the effects of CT-saturation and CPD-subsidence transient characteristics on the operating points of who distance relay can be accurately prodicted. It gives more effective results, compared with the model without considering those characteristics by checking the exprimental data.

Protective Management System followed Distance Relay characteristics for Transmission Line with the Unified Power Flow Controller (UPFC연계시 거리계전기 동작특성에 따른 보호 관리 시스템)

  • Suh, Jung-Nam;Jung, Chang-Ho;Cho, Jong-Man;Kim, Jin-O
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.296-298
    • /
    • 2001
  • This paper represents protective management system for transmission line involving the UPFC(Unified Power Flow Controller) device, which is the most vigorous component of FACTS. The presence of the UPFC significantly affects the line parameters of transmission system, which are also influenced by the distance relay setting. Moreover, depending on the UPFC location and its parameters, zones of setting the distance relay will be changed. Therefore, established protective system should be taken into account the variable injected voltage of the UPFC and constructed data base system.

  • PDF