• 제목/요약/키워드: Disconnector

검색결과 23건 처리시간 0.033초

Optimal Design of a Follow Current Disconnector for DC Arresters in Traction Vehicles

  • Wang, Guoming;Kim, Sun-Jae;Park, Seo-Jun;Kil, Gyung-Suk;Ji, Hong-Keun
    • Transactions on Electrical and Electronic Materials
    • /
    • 제17권5호
    • /
    • pp.289-292
    • /
    • 2016
  • This paper dealt with the optimal design of a follow current disconnector for DC arresters used in electric traction vehicles. The disconnector separates the ground lead from an arrester to prevent a line-to-ground fault of an aged arrester and should not affect the operation and function such as the reference and the clamping voltage of the connected arrester. The designed disconnector is composed of a resistor, a spark gap, and a cartridge. The results showed that the sparkover voltage increased with the gap distance whereas the reference voltage was almost the same as that without the disconnector. The sparkover voltage was 3.95 kV when the gap distance was 0.5 mm. Regardless of the gap distance, the reference and the clamping voltage of the assembled disconnector with an arrester were measured to be the same as those of the arrester alone.

피뢰기용 단로기의 특성 및 성능 평가 (Properties & Performance Evaluation of Disconnector for Surge Arrester)

  • 김석수;최익순;정낙헌;박태곤
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.546-547
    • /
    • 2005
  • This study aims to evaluate the properties and the performance of the newly designed disconnector for surge arrester. This disconnector was verified with the performance in long-duration current impulse test and high current impulse test. And time-current characteristic test was done at 20A, 200A and 800A(3points) for simulating the internal fault condition of the arrester. The results of this test was very good. Consequently, the newly designed disconnector was, evaluated that it is possible to be used for surge arrester in distribution line system.

  • PDF

신뢰성이 향상된 배전급 피뢰기 설계 기술의 동향 (Trend in New Distribution Class Arrester Ground Lead Disconnector Design)

  • 이주홍;윤주호;김인희;최용성;이경섭
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.541-542
    • /
    • 2007
  • The paper also introduces a new Distribution Class ground lead disconnector design that not only extends the claimable detonation range well below the 20 amps specified in industry standards, but is very durable when exposed to severe arrester durability tests. Finally. this paper shows how this next generation disconnector interacts with the connected arrester to improve the overvoltage withstand capability of the arrester assembly. The interaction of the disconnector grading capacitor with the series-connected arrester metal oxide disc elements actually improves the arrester assembly temporary overvoltage withstand capability, making the design less vulnerable to TOV failures. Since the vast majority of distribution class arresters are sold domestically with ground lead disconnectors, this design improvement in the disconnector to improve detonation reliability also translates into a significantly improved distribution class arrester design.

  • PDF

배전급 피뢰기의 신뢰성 평가에 관한 기술 동향 (A Technical Trend on New Distribution Class Arrester Ground Lead Disconnector Design)

  • 김선빈;김인희;홍현욱;오용;황종선;최용성;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1980-1981
    • /
    • 2007
  • This paper introduces performance characteristics of existing distribution class arrester ground lead disconnecting devices. The paper also introduces a new distribution class ground lead disconnector design that not only extends the claimable detonation range well below the 20 amps specified in industry standards, but is very durable when exposed to severe arrester durability tests. Finally, this paper shows how this next generation disconnector interacts with the connected arrester to improve the overvoltage withstand capability of the arrester assembly.

  • PDF

배전급 피뢰기의 설계 (Design and Improves Arrester Performance for Distribution Class Arrester)

  • 최용성;황종선;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2118-2119
    • /
    • 2008
  • The paper introduces a new Distribution Class ground lead disconnector design that not only extends the claimable detonation range well below the 20 amps specified in industry standards, but is very durable when exposed to severe arrester durability tests. Finally, this paper shows how this next generation disconnector interacts with the connected arrester to improve the overvoltage withstand capability of the arrester assembly.

  • PDF

현장 고장난 배전용 피뢰기의 특성분석 (Characteristic Analysis of Distribution Lighten ins Arrester Failed in the Field)

  • 김찬영;김주용;송일근;이병성;한재홍;윤태상
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.687-690
    • /
    • 2000
  • This paper provides the result of the analysis of the lightening arresters which were disconnected from the power line due to the overvoltage having high current. The effect of thermal runaway on the microstructures of lightening arrester's block was intensively investigated. The chance of the microstructures of the blocks was limited only on the breakdown paths and near them. Also even though a disconnector was disconnected from the arrester, some of the lightening arrester were showed normal characteristics.

  • PDF

초고압 $SF_6$가스중의 선구방전기구 (Precursor Discharge Mechanism under EHV in $SF_6$ Gas)

  • 이형호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1807-1809
    • /
    • 1996
  • The axial discharge at switching operations of EHV $SF_6$ disconnector can lead to the breakdown to the enclosure. Precursor in periphery zone leads to formation of leader over some time delay. Injected charge value depends on electric field and gap geometry. The calculation method for parameters of $SF_6$ insulation for DS in EHV-GIS is suggested by using the new criterion of leader inception in connection with periphery field nearby the boundary of streamer zone.

  • PDF

전계 측정용 센서의 개발 (Development of the Sensor for Measuring the Electric Fields)

  • 백용현;이복희;안창환
    • 대한전기학회논문지
    • /
    • 제40권6호
    • /
    • pp.630-637
    • /
    • 1991
  • For the measurement of time-varying electric fields and related quantities, a field sensor should be sensitive to the field to be measured, and also designed having an accurate transfer function. In this paper, a theoretical model which adequately describes the operation principle and design of the sensor is presented. A calibration and/or correction technique of the sensor is also studied which enables a precise determination of the response of the sensor to an electric field. As a result, the developed electric field sensor and measuring system are known to be accurate within a bandwidth from a few Hz to 200 MHz. It is found that the sensor can be used directly in the measurement of very fast transient voltages and time-varying electric fields occurring during disconnector operations in a gas-insulated substation. It may be useful also for the study on the electromagnetic environmental parameters.

시변성(時變性) 전계(電界) 측정용(測定用) 센서에 관한 연구 (A study on the sensor for measuring the transient electric fields)

  • 이복희;백용현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1991년도 하계학술대회 논문집
    • /
    • pp.318-321
    • /
    • 1991
  • For measuring the transient electromagnetic fields and related quantities created by disconnector operations in GIS, one needs the wide bandwidth sensors with simple transfer functions. This paper describes a new developed electric field sensor to measure the very fast transient electric fields and voltages, and the measuring principle, design and construction of planar electric field sensor are described. A calibration and/or correction technique of the sensor is investigated which enables an accurate determination of the sensor response to the time-changing electric fields. As a consequence, the low voltage calibrations certify that a rise time of 1.7 [ns] is achieved for the planar electric field sensor and a total bandwidth extending from several Hz to 200 MHz for the measuring system which presents the constant division ratio as a function of frequency.

  • PDF

단로기 조작 시 변압기 단자에서 측정된 VFTO의 상승률 분석 (Analysis of Rate-of-rise of VFTO Measured in Transformer During the Operation of Disconnector)

  • 이지영;오윤식;서훈철;김철환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.45-46
    • /
    • 2011
  • 단로기와 회로 차단기의 스위칭 동작에 의해 발생하는 Very Fast Transient Overvoltage(VFTO)는 변압기, 회로차단기 등 GIS 전력소자에 큰 충격을 주어 잠재적인 위험이 된다. VFTO는 전력기기 소자 및 절연체 손상의 주된 원인이므로 시스템을 설계할 때 반드시 VFTO 최대값을 고려해야 한다. 본 논문에서는 55kV Gas Insulated Substation(GIS)를 분포정수회로기반으로 모델링하여 다양한 투입위상각에 따른 VFTO 상승률을 모의하였다. 이때, EMTP-RV를 이용하여 변압기로 전파된 VFTO를 측정하여 그 경향을 분석하였다.

  • PDF