• Title/Summary/Keyword: Digital Protective Relay

Search Result 73, Processing Time 0.026 seconds

Digital Relaying Algorithm for Power Transformer Protection using Fuzzy Logic Approach

  • Park, Chul-Won;Shin, Myong-Chul
    • KIEE International Transactions on Power Engineering
    • /
    • v.2A no.4
    • /
    • pp.153-159
    • /
    • 2002
  • Power transformer protective relay should block the tripping during magnetizing inrush and rapidly operate the tripping during internal faults. Recently, the frequency environment of power system has been made more complicated and the quantity of 2nd frequency component in inrush state has been decreased because of the improvement of core steel. And then, traditional approaches will likely be maloperate in the case of magnetizing inrush with low second harmonic component and internal faults with high second harmonic component. This paper proposes a new relaying algorithm to enhance the fault detection sensitivities of conventional techniques by using a fuzzy logic approach. The proposed fuzzy based relaying algorithm consists of flux-differential current derivative curve, harmonic restraint, and percentage differential characteristic curve. The proposed relaying was tested with relaying signals obtained from EMTP simulation package and showed a fast and accurate trip operation.

The Consideration on the Selection of Power System Model used for the Reach Test of Digital Protective Relay Using RTDS (RTDS를 이용한 디지털 보호계전기 Reach Test계통모델 선정 방안)

  • Lee Jae Wook;Cha Seung Tae;Choi Chang Yeol;Jang Byung Tae;Lee Jae Gyu;Kim Cheol Hwan
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.388-390
    • /
    • 2004
  • 디지털 보호계전기의 성능 검증에 있어서 RTDS(Real Time Digital Simulator)와 같은 디지털 시뮬레이터를 사용하는 경우가 점점 증가하고 있다. 특히 보호계전기의 동특성(Dynamic Performance) 시험에 있어서는, 디지털 시뮬레이터를 이용한 성능 검증이 거의 필수적이다. 본 논문에서는 디지털 보호계전기 중 거리계전기의 Reach Test에 있어서 성능 검증에 사용할 계통 모델 선정 방안을 PSCAD/RTDS에서의 구현 관점에서 기술하고 있다. 양단 전원을 가지는 4모선 2회선 송전선로를 Bergeron 모델을 이용하여 모델링하고, 모델의 유효성을 귀납적인 방법을 사용해서 검증하는 방안을 제시하고 있다.

  • PDF

Commercial Grade Item Dedication of Digital Devices for Safety-related System in Nuclear Power Plant (원자력발전소 안전등급 계통 적용을 위한 디지털 상용기기 품질검증)

  • Hong, Young Hee;Bae, Byung Hwan;Park, Jaehyun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.12
    • /
    • pp.1637-1639
    • /
    • 2014
  • In the past, the analog protection relays have been widely used for the safety-related systems in the nuclear power plants due to their stability and reliability. Meanwhile, as the high performance digital system has been developed, the digital systems have been adopted in the non-safety systems. However, since the digital systems currently used in the non-safety systems were not developed according to Q-class standard, Commercial Grade Item Dedication (CGID) procedure should be performed in order to apply them to the safety-related system. The purpose of this paper is to describe the CGID procedure including the analysis of the hardware architecture as well as the software embedded in protective relay to apply to the emergency diesel generator in the nuclear power plant. The entire CGID procedure was performed strictly according to the international standard and regulations.

Disturbance State Identification of Power Transformer Based on Dempster's Rule of Combination (Dempster 결합룰에 의한 전력용 변압기 외란상태판정)

  • Kang, Sang-Hee;Lee, Seung-Jae;Kwon, Tae-Won;Kim, Sang-Tae;Kang, Yong-Cheol;Park, Jong-Keun
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.12
    • /
    • pp.1479-1485
    • /
    • 1999
  • This paper proposes a fuzzy decision making method for power transformer protection to identify an internal fault from other transient states such as inrush, over-excitation and an external fault with current transformer (CT) saturation. In this paper, analyzing over 300 EMTP simulations of disturbances, four input variables are selected and fuzzified. At every sampling interval from half to one cycle after a disturbance, from the EMPT simulations, different fuzzy rule base is composed of twelve if-then fuzzy rules associated with their basic probability assignments for singleton- or compound-support hypotheses. Dempster's rule of combination is used to process the fuzzy rules and get the final decision. A series of test results clearly indicate that the method can identify not only an internal fault but also the other transients. The average of relay operation times is about 12(ms). The proposed method is implemented into a Digital Signal Processor (TMS320C31) and tested.

  • PDF

An Autonomous Optimal Coordination Scheme in a Protection System of a Power Distribution Network by using a Multi-Agent Concept

  • Hyun, Seung-Ho;Min, Byung-Woon;Jung, Kwang-Ho;Lee, Seung-Jae;Park, Myeon-Song;Kang, Sang-Hee
    • KIEE International Transactions on Power Engineering
    • /
    • v.2A no.3
    • /
    • pp.89-94
    • /
    • 2002
  • In this paper, a protection system using a Multi-Agent concept for power distribution networks is proposed. Every digital over current relay(OCR) is developed as an agent by adding its own intelligence, self-tuning and communication ability. The main advantage of the Multi-Agent concept is that a group of agents work together to achieve a global goal which is beyond the ability of each individual agent. In order to cope with frequent changes in the network operation condition and faults, an OCR agent, suggested in this paper, is able to detect a fault or a change in the network and find its optimal parameters for protection in an autonomous manner considering information of the whole network obtained by communication between other agents. Through this kind of coordination and information exchanges, not only a local but also a global protective scheme is completed. Simulations in a simple distribution network show the effectiveness of the suggested protection system.

Study on the establishment of dynamic performance test environment for the digital protective relay using RTDS (RTDS를 이용한 디지털 보호계전기 동특성 성능검증 기반 구측에 관한 연구)

  • Lee, Jae-Wook;Jang, Byung-Tae;Choe, Chang-Yeol;Lee, Myeong-Hee;No, Jang-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.453-455
    • /
    • 2005
  • 디지털 보호계전기의 성능 검증은 정특성 성능 검증, 동특성 성능 검증, 내 환경 성능 검증으로 나누어진다. 이 중 동특성 성능 검증에 대한 중요성이 증가하고 있으나, 실시간 디지털 시뮬레이터에 대한 접근의 어려움으로 인해서 해당 기술의 보급이 용이하지 않았다. 전력연구원에서는 이러한 점을 해결하고 관련 기술의 보급을 위해서 디지털 보호계전기 동특성 성능 검증의 기반을 마련하였으며, 이 기반은 성능 검증을 위한 계통 모델과 성능 검증 절차서로 각각 구성되어 있다.

  • PDF

Back Fed Earth Fault Detection in Three Wire-Unigrounded Distribution-System By Zero Sequence Admittance (영상어드미턴스에 의한 직접접지 배전방식에서의 역가압 지락사고 검출)

  • Yoo, Myeong-Ho;Kim, Il-Dong;Han, Hong-Seok;Pak, Chul-Won
    • Proceedings of the KIEE Conference
    • /
    • 1993.07a
    • /
    • pp.120-123
    • /
    • 1993
  • This paper presents the developing a new algorithm for detecting the Back fed Earth Fault in three wire-unigrounded distribution system by zero sequence admittance. So called "Backfed Earth Fault" of the electric power distribution line refers to a class of earth faults that the load-side line only is grounded, following after the distribution line broken into two parts, the source-side and the load-side. Because its mechanism differs from that of other earth faults, it is therefore, required to examine. This paper deals with the detailed software of the digital protective relay for Backfed earth fault. In order to prove that the proposed schemes is good, we performed off-line simulation using data from EMTP and ETSA(Electrcity Trust Of South Austrilia). It is shown that the suggested algorithm is never mal operated.

  • PDF

A summary of KEPCO's 765kV substation design (한전 765kV 변전소의 기본설계 개요)

  • Kim, M.D.;Jung, S.H.;Kim, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2139-2142
    • /
    • 1999
  • 765kV substations which will be the core installation of the bulk power transmission system in Korea for the upcoming $21^{st}$ century, were designed of outdoor full GIS type to minimize required area. As principal equipment, main transformers of 2,000 MVA per bank and 50kA 8,000A gas insulated switchgears of up-to-date technology were adopted in designing substations to transmit bulk power of 10GW. Dual digital protective relay systems and distributed indication and control systems with fiber optic LAN were used.

  • PDF

A Study on the Intelligent Electronic Device for Non-Linear Loads (비선형 부하에 적용이 가능한 IED에 관한 연구)

  • 박종찬;김병진;김수곤;전희종
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.8 no.5
    • /
    • pp.381-388
    • /
    • 2003
  • In this paper, the IED(Intelligent Electronic Devices) with the consideration of harmonic problems is discussed, With significant development of power electronics technology, the proliferation of a nonlinear load has more deteriorated power quality, As continuous harmonic current makes for a shortening lifetime, overheat and abnormal operation, it should be considered to improve these problems. However, the conventional digital protective relay which eliminates harmonic elements with orthogonal filter has a defect on actually implementation. The prototype IED is constructed with Digital Signal Processor(TMS320C32) and Complex Programmable Logic Device. According to the experiment and simulation results, it is proved that the proposed system has good performance of measuring harmonic factors and protecting electrical equipment.

An Improvement of Digital Distance Relaying Algorithm on Underground Transmission Cables (지중송전케이블룡 디지털 거리계전 알고리즘 개선)

  • Ha, Che-Ung;Lee, Jong-Beom
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.12
    • /
    • pp.595-601
    • /
    • 2000
  • This paper describes the improvement method of distance relaying algorithm for the underground transmission cables. Distance relaying algorithms have been mainly developing to protect the overhead transmission lines than the underground cables. If the cable systems are directly protected using distance relaying algorithm developed for overhead line without any improvement, there will be really occurred many misoperation in cable systems, because the cable systems consist of the conductor, the sheath, several grounding method, cable cover protection units(CCPUs), and grounding wire. Accordingly, the complicated phenomena are occurred, if there is a fault in cable systems. Therefore, to develope a correct distance relaying algorithm, such cable characteristics should be taken into account. This paper presents the process to improve distance relaying algorithm which is now used. REal cable system was selected to establish modeling in EMTP and ATP Draw. It was discovered through the detailed simulation during the fault that the large error existed between impedance measured at the relay point and real impedance is due to the resistance of grounding wire in each grounding method. And also compensation factor obtained by the simulation is proposed in this paper. It is proved that the factor proposed can fairly improve the accuracy of impedance at the relay point. It is evaluated that the protective ability will be really much improved, if the algorithm proposed in this paper is applied for cable systems of utility.

  • PDF