• Title/Summary/Keyword: Deep-seated fire

Search Result 12, Processing Time 0.027 seconds

Experimental Study on Moisture Content According to Addition of Surfactants (계면활성제 첨가에 따른 함수율에 관한 실험적 연구)

  • Kim, Nam-Kyun;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.29 no.2
    • /
    • pp.79-83
    • /
    • 2015
  • The fire accident is a representative type of disaster that can largely impact on business. Therefore, precautionary measures and rapid initial response is very important when a disaster occurs. The storage of porous combustibles is inevitable in coal yard, plywood processing industry, and others that are currently operating. Initial fire fighting of fire and identifying the ignition point in such a porous combustible storage space are so difficult that if the initial response is failed, being led to deep-seated fire, surface fire is likely to result in secondary damage. In addition, deep-seated fire can cause personal injuries and property damage due to a large amount of toxic gases and reignition. Therefore damage reduction measures is required around the storage space to handle a porous flammable. Improving the penetration performance of the concentration of the surfactant is carried out as underlying study, which is about an deep-seated fire extinguishing efficiency augmentation when using wetting agents. The porous materials used in the experiments is radiata pine wood flour, which occupies more than 75% of the domestic wood market. Fire fighting water is selected as Butyl Di Glycol (BDG), which is being used for infiltration extinguishing agent, and the experiment was carried out by producing a standard solution. The experiment was carried out on the basis of the Deep-Seated Fire Test of NFPA 18. The amount of watering, porous material to the internal amount of penetration, and runoff measurement out of the porous material was conducted. According to experimental results, as the surface tension is reduced, the surfactant concentration macroscopic penetration rate decreases, but infiltration to a porous material is shown to have growth characteristics.

A Study for Characteristics of Water that Penetrates Wood Flour due to Changes of Concentration of BDG (BDG 농도변화에 따른 용수의 목분 침투특성 연구)

  • Kong, Il-Chean;Park, Il-Gyu;Lim, Kyung-Bum;Rie, Dong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.28 no.3
    • /
    • pp.74-79
    • /
    • 2013
  • As the feature of fire, it is hard for deep-seated fire to spread to the deeper site, and it also has danger for being re-ignited cause of recontacting with oxygen after being put off. Now it is ruled in the certification criteria of wetting agent used for extinguishing deep-seated fire that the criteria for surface tension is below 33[mN/m] in Korea. For figuring out how much water for fire-fighiting can permeate into combustibles, in this research, the permeating performance is analyzed by measuring the speed of permeating and transmission quantity released after that, by pouring solution whose surface tension is changed by adjusting concentration of surfactant BDG(Butyl Di Glycol) in column From this result, it is can be determined that transmission quantity becomes less and wet area goes wider as surface tension is lower, and it is also able to be analyzed as quantity of absorbed liquid and wet area is increased because fluid permeates into the core.

Study on the Deep Stead Fire Spread Temperature by the Change of the Wood Flour Density (목분의 밀도변화에 따른 온도전이에 관한 실험적 연구)

  • Kim, Jin Su;Rie, Dong Ho
    • Fire Science and Engineering
    • /
    • v.29 no.3
    • /
    • pp.1-5
    • /
    • 2015
  • The productivity and demand of porous material has been increasing by development of industry and increasing income. In particular, the fire caused by using wood flour risks wood processing industry and stock farm. The heat transfer of wood flour is carried into the depth direction by effect of oxidizer around flame, flame sometimes is progressed as smoldering. In the case of progressing as combustion fire, identifying the location of fire is difficult, and it leads to failing fire aid fire fighting. Therefore potential cause is acted as raising additional damage. This paper conducts experiments of downward deep seated fire of natural convection conditions. The samples is New Zealand wood flour that is demanded much in the domestic and oversea market. In this experiment, temperature of deep seated side is measure by changing wood flour density in holder The densities used in experiment are 3%, 5%, 10%, 15%. As a result, the tendency of temperature inside decreases as wood flour density increases. But, in the case of density which is above $0.2140g/cm^3$, the phenomenon, decreasing temperature, is not shown. The result of measurement show that average flame spread speed of wood flour is 0.249 mm/min.

A Study on the Direct Discharge Test for Verifying Design Concentration and Soaking Time for CO2 Fire Extinguishing System of Total Flooding (전역방출방식 CO2 소화설비의 설계농도 및 유지시간 검증을 위한 직접방사실험에 관한 연구)

  • Lee, Se-Myeoung;Moon, Sung-Woong;Ryu, Sang-Hoon
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.15-23
    • /
    • 2012
  • Indirect Test Method is often used instead of direct test method in test method for extinguishing performance of $CO_2$ extinguishing facility because of high cost, environment problems and difficulties of procedure. But in the danger facilities for a unit of nation, such as a petrochemical plant, a nuclear power plant, or etc. is better to verify the performance of the extinguishment through direct discharge test. In $CO_2$ extinguishing system for total flooding system installed in dangerous facilities in Korea, each protected area in surface fire and deep-seated fire had selected and verified of extinguishing performance of $CO_2$ extinguishing facilities. To get recognized as extinguishing performance, discharged $CO_2$ concentration to protected area should be equivalence with design concentration standards (NFSC and NFPA). The Design Concentration means that $CO_2$ extinguishing agent is considerate of concentration for percentage of allowance (20 %) from extinguishing concentration which available to control of flame. As test result, surface fire and deep seated fire in protected area is obtained $CO_2$ design concentration and maintained design concentration more than 20 minutes as deep-seated fire. Through this study, we introduced direct discharging test method and decision method. And furthermore, especially in the dangerous facilities as a unit of Nation, we suggested necessity about reliability of extinguishing facilities to use direct test method.

Development of Loaded Stream Fire Extinguishing Systems for Underground Transmission Cables (지중송전선로 접속부용 미분무 강화액 소화설비의 개발연구)

  • Lee, Sung-Mo
    • Fire Science and Engineering
    • /
    • v.22 no.1
    • /
    • pp.93-98
    • /
    • 2008
  • Full-scale fire extinguishment tests were conducted to develop loaded stream fire extinguishing systems for protecting underground transmission cables. The dimension of test mock-up was 5.5m height${\times}3m$ width ${\times}6m$ length, and six 154kV OF cables were piled up. Gasoline was used to ignite cates. Linear heat detection cables were installed on top of 154 kV OF cable and discharge nozzles were installed on the top and sidewalls, respectively. As a result, both surface fires and deap-seated fires were extinguished successfully within the specified 3 minutes by discharging loaded stream agent.

The Ways of Improving Technical Standards to Increase Effectiveness of Wetting Agent (침윤소화약제의 효과성 증대를 위한 기술기준 개선방안)

  • Jang, Kwan Su;Kim, Jung Min;Cho, Young Jae
    • Journal of the Society of Disaster Information
    • /
    • v.18 no.3
    • /
    • pp.581-588
    • /
    • 2022
  • Purpose: This study is about offering ways of improving existing technical standards in order to propose how to deal with coal deep-seated fire and to increase effectiveness of wetting agent. Method: This study conducts infiltration experiment using eight tons of coal, three types of wetting agents and fire water. And this study analyzes domestic and international technical standards, overseas experimental cases. Result: It is found that two findings are identified; one is fire water cannot infiltrate into the coal due to high level of surface tension, and the other is three types of wetting agent can infiltrate into the coal to the depth of 5~25cm. Also, domestic wetting agent technical standards include measuring surface tension only and testing wood on extinguishing capacity test. On the other hand, this study found that deep-seated fire experiment using cotton, B-class fire test using heptane are used from abroad. Besides it is analyze that capillary rise test, sink test, contact angle measurement are conducted to increase effectiveness of wetting agent at the U.S. Bureau of Mines. Conclusion: Based on standards and cases of U.S. NFPA and Bureau of Mines, this study suggests that domestic technical standards should include adding a new test standard which measures infiltration directly.

A Study of Fire Extinguishment Characteristic for the Real Scale Deap-Seated Fire (실규모 심부화재 소화특성에 관한 연구)

  • Kim, Nam-Kyun;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.29 no.2
    • /
    • pp.13-19
    • /
    • 2015
  • Real scale fire tests was carried out for extinguishing performance evaluation of the wetting agent. The experiment was conducted in accordance with a Class A fire extinguishing test methods specified in the 'Type Approval of the Manual System Fire Extinguisher and Technical Standards of Test'. In addition, the subjects of this experiment were the wood flour and rice husk. Fire-fighting water, the three kinds of wetting agents used in the country and this study was used, was undertaken to determine a clear discrimination of the water and wetting agent. In the experimental results, it was confirmed that the internal temperature is maintained long time in the case of water. The internal temperature were rapidly lowered in the experiment of wetting agents. Therefore, the discrimination of extinguishing ability was confirmed by the temperature distribution in accordance with time. Based on the results of this experiment, this study is expected to be used as a underlying material on presenting a method of optimized performance evaluation of wetting extinguishing agent.

Discharge and Fire Extinguishing Test of Inert Gas Clean Agent (불활성 가스계 청정 소화약제의 방출 및 소화)

  • Song Eun-Seok;Kim Jae-Duck;Park Yang-Won
    • Fire Science and Engineering
    • /
    • v.19 no.2 s.58
    • /
    • pp.29-36
    • /
    • 2005
  • We carried out discharge and fire extinguishing tests of new inert gas clean agent, which consists of $92\%$ nitrogen and $8\%$ carbon dioxide, as an alternative of Halon that is banned by Montreal Protocol to protect the ozone layer of the earth. Discharge and fire extinguishing tests were performed in $27m^3$ and $190m^3$ rooms with piping which allows gaseous agent to transport from storage to test rooms. We confirmed that it took less than regulation time, 60 seconds for the discharge of over $95\%$ initial charged amounts. Discharge test variables were piping length and orifice size. Fire extinguishing tests verified that this new inert gas clean agent is suitable for both n-Heptane fire and deep seated fire of wood crib.

An Experimental Study on Improvement of Fire Extinguishing Performance of Basic Sprinkler System (간이스프링클러 설비의 소화성능 향상에 관한 실험적 연구)

  • Hur, Min Noung;Shin, Changsub
    • Journal of the Korean Society of Safety
    • /
    • v.33 no.3
    • /
    • pp.46-51
    • /
    • 2018
  • A basic sprinkler system is a fire extinguishing system that can be easily installed in a fire-vulnerable place such as a publicly used establishments. However, the publicly used establishments are not only complicated in structure, but also have a large amount of flammable interior materials, and the users are not normally in a normal state, which is a very dangerous fire-fighting object. Therefore, due to the low fire extinguishing performance of the basic sprinkler system installed in the publicly used establishments, the fire suppression control can not be performed quickly in case of fire, which may increase the life and property damage. In this study, the cases of quantitative changes of extinguishing water used in basic sprinkler system and the cases of addition of additives such as wetting agents, reinforced agents to improve extinguishing performance were compared. Experimental results showed that the extinguishing performance was improved as the quantity of extinguishing water increase and the reinforced agents showed similar performance to that of 60% increase in the amount of extinguishing water. The cooling time to $200^{\circ}C$ and oxygen concentration were improved up to 14.3% and 34.5%, respectively. In the case of using the wetting agent, the cooling time to $200^{\circ}C$ and oxygen concentration did not show any significant improvement, but showed the effect of preventing deep seated fire. In order to prevent loss of life and property, it is necessary to improve the performance of the basic sprinkler system by increasing amount of extinguishing water or using additives like reinforced agents.

Wetting Agent Performance Evaluation Using Scale Model (축소모형 실험을 통한 침윤소화약제 소화성능 평가)

  • Kim, Nam-Kyun;Lim, Kyung-Bum;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.28 no.2
    • /
    • pp.20-25
    • /
    • 2014
  • In this study, the extinguishing performance evaluation of wetting agent for wood crib was conducted by using a scale model equipment that we designed. To confirm the optimal conditions of the experiment, a test was changed amount of fire extinguishing water and the number of timber. As a result, the discrimination of the fire extinguishing performance was seen only when 20 pieces of wood and the extinguishing water of 100 mL were used. After evaluating the extinguishing performance of domestic and foreign wetting extinguishing agents under these conditions, a reignition was occurred in only when we used water. In addition, the discrimination of extinguishing performance was seen through the temperature distribution according to the time of watering. Based on the results of this experiment, this study is expected to be able to use as a basis on presenting a method of optimized performance evaluation of wetting extinguishing agent.