• 제목/요약/키워드: Dead-end Clamp

검색결과 5건 처리시간 0.023초

Characteristics of a Corona between a Wiring Clamp (Dead End Clamp) and a Porcelain Insulator Used in a 154kV Power Receptacle

  • Han, Woon-Ki
    • International Journal of Safety
    • /
    • 제7권1호
    • /
    • pp.21-25
    • /
    • 2008
  • The occurrence of a corona is that electrical discharge due to the heterogeneity that occurs when an electrical field is concentrated in an electrode due to a cusp formed on said electrode. Wire treatment at the end of a 154kV dead end clamp for end users accelerates the occurrence of corona, which in turn leads to power loss and noise. In this study, the characteristics of the corona which occurs between porcelain insulators and support clamps of overhead lines used in l54kV power receiving facilities for end users were investigated. The corona, which cannot be identified by one common method, was measured utilizing a UV image camera. A risk assessment for fire damage and its status was suggested. The stress distribution of the electrical field by length of bare wire was suggested by means of the finite element method (FEMLAB). As a result, it was found to affect a porcelain insulators. These results can be utilized for the enhancement of clamp installation and safety in power facilities.

Characteristics of a Corona between a Wiring Clamp(Dead End Clamp) and a Porcelain Insulator Used in a 154[kV] Power Receptacle

  • Han, Un-Ki;Kim, Jong-Min;Bang, Sun-Bae;Kim, Han-Sang;Choi, Hyeong-Jun
    • 조명전기설비학회논문지
    • /
    • 제21권9호
    • /
    • pp.57-63
    • /
    • 2007
  • The occurrence of a corona is that electrical discharge due to the heterogeneity that occurs when an electrical field is concentrated in an electrode due to a cusp formed on said electrode. Wire treatment at the end of a 154[kV] dead end clamp for end users accelerates the occurrence of corona, which in turn leads to power loss and noise. In this study, the characteristics of the corona which occurs between porcelain insulators and support clamps of overhead lines used in 154[kV] power receiving facilities for end users were investigated. The corona, which cannot be identified by one common method, was measured utilizing a UV image camera. A risk assessment for fire damage and its status was suggested. The stress distribution of the electrical field by length of bare wire was suggested by means of the finite element method(FEMLAB). As a result, it was found to affect a porcelain insulators. These results can be utilized for the enhancement of clamp installation and safety in power facilities.

Preventing Method against the Occurrence of a Corona between a Dead End clamp and a Porcelain Insulator Used in 154kV Substation

  • Han, Woon-Ki;Choi, Jong-Soo;Lee, Jun;Kim, Jae-Chul
    • International Journal of Safety
    • /
    • 제6권2호
    • /
    • pp.22-26
    • /
    • 2007
  • An episode of corona is a heterogeneity-caused electric discharge that occurs when electric fields are formed layer on layer and concentrated on an electrode. Electric wires built at the tip of 154kV private facilities use dead end clamp spawns corona from homogeneity caused by field concentration. Corona induces power loss, noise, insulator failure and more. In this research, we've studied the characteristics of coronas that take place in porcelain insulators and terminal electric wires of supporting hard wares (dead end clamp) that are set up as spares in the 154kV private facilities use hydroelectricity installations to support electric wires. Corona, which cannot be identified by regular methods, was measured utilizing UV image camera. As the result of measuring corona via UV image camera, we've confirmed that the depletion of insulators was accelerated following the wire end treatment method and validated the stress intensity of insulators at various lengths of bare wires caused by electric fields via FEMLAB. We have also proposed a new model for relieving homogeneity-caused field concentration, and after analyzing the proposed model via FEMLAB, we've confirmed that the concentration of field distribution was indeed reduced. Such results are exploited in installation of private facilities use equipments, maintenance of insulators and hard wares as well as safety enhancement, and are anticipated to be effectively utilized in corona prevention measures.

송배전 선로 고장력 인장시험기 개발 (Development of High Tension Tensile Tester for Transmission Line)

  • 신동화;이병호
    • 한국산업융합학회 논문집
    • /
    • 제21권5호
    • /
    • pp.219-225
    • /
    • 2018
  • In this paper, for the testing of tensile strength of dead-end clamp used in transmission line, resulting values were estimated by designing and producing the horizontal version of widely-used vertical tensile tester. Tensile strength test of dead-end clamp for transmission line is essential for quality test of products. Moreover, tensile tester is an equipment that requires high level of reliability which needs to be examined through sampling tests commensurate with total inspection. Frames of tensile tester were made up of H-beams so that it can endure more than 20 [tons] of load capability and the test was implemented for 60[seconds] applying five types of tension. In consequence, the tester could withstand up to 21,600[kg] of weight as well as all types of tension. This newly developed horizontal tensile tester can be utilized in figuring out properties of various materials by estimating tensile strength of materials such as metal, rubber and fiber.

154kV 수전설비용 가선금구(인류형 클램프)와 자기애자에서 발생하는 코로나 특성 (Corna Characteristics of Between Compression Clamp or Dead End clamp and Porcelain Insulator Used 154kV Receiving Electrical Facility)

  • 한운기;김종민;방선배;김한상;최형준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.2044-2045
    • /
    • 2007
  • 코로나 발생은 전극의 첨점이 형성되어 전극에 전계가 집중될 경우 불균질성에 의한 방전이다. 수용가용 154kV 인류형 클램프 말단의 전선처리는 코로나 발생을 가속시켜 전력손실, 노이즈 발생 등의 영향을 미친다. 본 연구에서는 수용가용 154kV 수전설비용 자기애자 (Porcelain Insulator)와 가공선로(Overhead Line)의 지지용 금구사이에서 발생하는 코로나 특성을 고찰하였다, 일반적 방법으로 확인 되지않는 코로나를 UV Image 이용하여 애자의 소손 위험성 및 상태를 제시하였으며, 유한요소법(FEMLAB)을 이용하여 나전선의 길이별로 전계분포에 의한 위험성을 제시하였다. 수전설비의 설치조건 및 금구류의 유지보수 및 안전성 향상에 활용될 것으로 기대한다.