• Title/Summary/Keyword: DC cable loss

Search Result 22, Processing Time 0.044 seconds

Loss characteristics analysis of HTS DC cable using FEM (FEM을 이용한 초전도 직류 케이블의 손실 특성 분석)

  • Kim, Sung-Kyu;Kim, Seok-Ho;Kim, Jin-Geun;Park, Min-Won;Yu, In-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.822-823
    • /
    • 2011
  • The authors analyzed harmonic current based loss of a high temperature superconducting (HTS) DC model cable. The loss in HTS DC cable is generated due to the variation of magnetic field caused by harmonic current in a HVDC transmission system. The authors designed and fabricated two meters of HTS DC model cable for verification of real loss characteristic. In this paper, the loss characteristics caused by harmonic current in the HTS DC model cable are analyzed using commercial finite element method software package. The loss of the HTS DC cable is much less than the loss of the HTS AC cable but the loss should be considered to decide a proper capacity of cooling system.

  • PDF

Harmonics based loss characteristics analysis of HTS DC power cable (고조파에 의한 초전도 직류 전력케이블의 손실 특성 분석)

  • Kim, S.K.;Kim, S.H.;Park, M.W.;Yu, I.K.;Lee, S.J.;Cho, J.W.;Sim, K.D.;Won, Y.J.;Hwang, S.D.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.13 no.3
    • /
    • pp.19-23
    • /
    • 2011
  • An HTS DC power cable is expected to perfectly eliminate transmission loss caused by resistance. However, when the HTS DC power cable is applied to the power system, loss of the HTS DC power cable is generated due to harmonics caused by HVDC converter. We designed and analyzed the HTS DC power cable with a critical current of 1 kA to investigate the loss characteristics using a finite element method package. In this paper, the loss characteristics caused by harmonics in the HTS DC power cable were analyzed according to order and magnitude of harmonics. Based on the analysis results, the critical current of HTS DC power cable considered with the rated current could be determined to minimize the capacity of cooling system for the design the HTS DC power cable.

Feasibility study on the design of DC HTS cable core

  • Sim, Ki-Deok;Kim, Seok-Ho;Jang, Hyun-Man;Lee, Su-Kil;Won, Young-Jin;Ko, Tae-Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.12 no.4
    • /
    • pp.24-30
    • /
    • 2010
  • The renewable energy source is considered as a good measure to cope with the global warming problem and the fossil energy exhaustion. The construction of electric power plant such as an offshore wind farm is rapidly increasing and this trend is expected to be continued during this century. The bulky and long distance power transmission media is essential to support and promote the sustainable expansion of renewable energy source. DC power cable is generally considered as the best solution and the demand for DC electric power has been rapidly increasing. Especially, the high temperature superconducting (HTS) DC cable system begins to make a mark because of its advantages of huge power transmission capacity, low transmission loss and other environmental friendly aspects. Technical contents of DC HTS cable system are very similar to those of AC HTS cable system. However the DC HTS cable can be operated near its critical current if the heat generation is insignificant, while the operating current of AC HTS cable is generally selected at about 50~70% of the critical current because of AC loss. We chose the specifications of the cable core of 'Tres Amigas' project as an example for our study and investigated the heat generation when the DC HTS cable operated near the critical current by some electric and thermal analyses. In this paper, we listed some technical issues on the design of the DC HTS cable core and described the process of the cable core design. And the results of examination on the current capacity, heat generation, harmonic loss and current distribution properties of the DC HTS cable are introduced.

Dielectric Breakdown Characteristics of PPLP and GFRP for HTS DC Cable System (고온초전도 DC 케이블 시스템용 PPLP 및 GFRP의 절연 특성)

  • Kim, S.H.;Choi, J.H.;Kim, W.J.;Jang, H.M.;Lee, S.K.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.13 no.3
    • /
    • pp.5-9
    • /
    • 2011
  • DC high-temperature superconducting(HTS) cable system has attracted a great deal of interest from the view point of low loss, dense structure and large capacity. A HTS cable system is made of cable and termination. The insulating materials and insulation technology must be solved for the long life, reliability and compact of cable system. In this paper, we will report on the dielectric breakdown characteristics of insulating materials for HTS cable and termination. The AC, DC and lightning impulse breakdown strength of laminated polypropylene paper(PPLP) and glass fiber reinforced plastic(GFRP) have been measured under nitrogen pressures in the range of 0.l-0.4MPa. PPLP and GFRP are found to have a significantly higher DC breakdown strength. Also, DC surface flashover voltage of negative polarity is slightly higher than that of positive polarity in GFRP.

A Study on the Optimal Design of Large-scale Photovoltaic Array (대용량 PV 어레이의 최적설계에 관한 연구)

  • Hwang, In-Ho;Kim, Eui-Hwan;Ahn, Kyo-Sang
    • Journal of the Korean Solar Energy Society
    • /
    • v.31 no.1
    • /
    • pp.8-14
    • /
    • 2011
  • Recently, a number of large-scale photovoltaic(PV) power generation system has been installed all over the world. Thus, in order to improve the system efficiency, the optimal design of the large-scale PV systems has become an important issue. DC cable loss of PV array is one of the design factors related to the system efficiency. This paper introduces the array design method of a 500kW Photovoltaic power plant. Three types of the PV array are suggested. Also, string cables, sub-array cables and array cables are designed within 1% of voltage drop in the line, and the DC cable losses are analyzed. The results of this paper show that the DC cable loss of large-scale PV array can be reduced by adopting a proper sub-array design method.

DC and Impulse Insulation Characteristics of PPLP for HTS DC Cable (고온초전도 직류 케이블용 절연재료인 PPLP의 직류 및 임펄스 절연 특성)

  • Kim, Woo-Jin;Pang, Man-Sik;Kim, Hae-Jong;Cho, Jeon-Wook;Kim, Sang-Hyun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.26 no.7
    • /
    • pp.545-549
    • /
    • 2013
  • To realize the high-Tc superconducting (HTS) DC cable system, it is important to study not only high current capacity and low loss of conductor but also optimum electrical insulation at cryogenic temperature. A model HTS DC cable system consists of a HTS conductor, semi-conductor, cooling system and insulating materials. Polypropylene laminated paper (PPLP) has been widely adopted as insulating material for HTS machines. However, the fundamental insulation characteristics of PPLP for the development of HTS DC cable have not been revealed satisfactorily until now. In this paper, we will discuss mainly on the breakdown characteristics of 3 sheets PPLP in liquid nitrogen ($LN_2$). The characteristics of the diameter, location of butt-gap, distance between butt-gap length, pressure effect, polarity effect under DC and impulse voltage were studied. Also, the DC polarity reversal breakdown voltage of mini-model cable was measured in $LN_2$ under 0.4 MPa.

The study on the DC Ic measurement and AC loss in the 22.9kV, 50MVA HTS power cable (22.9kV/50MVA급 고온초전도 전력케이블의 DC Ic 측정 및 교류손실에 관한 연구)

  • Choi, Suk-Jin;Lee, Sang-Jin;Sim, Ki-Deok;Cho, Jeon-Wook
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.808-809
    • /
    • 2008
  • 22.9kV 50MVA HTS power cable has been developed and tested by Korea Electrotechnology Research Institute and LS Cable Company and it was supported by a grant from Center for Applied Superconductivity Technology of the 21st Century Frontier R&D Program. In this paper, DC Ic of 100m HTS cable which is installed at Kochang testing station was measured and analyzed. A measurement technique of DC Ic used by resistance and inductance removal method is established. The HTS power cable is composed of 2 layers for transmission and 1 layer for shield. For the analysis of AC losses in an HTS power cable, 2-dimensional numerical calculation was carried out to define the magnetic field distribution. We calculated the magnetization losses in the HTS core of that cable from these fields. These calculated results are in accordance with those of experiment.

  • PDF

A Characteristics of Large Current and Minimum Quench Energy on Prototype High-$T_c$ Superconducting Cable (Prototype 고온초전도 케이블의 최소 Quench에너지 및 대전류 특성)

  • Kim, Sang-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.236-242
    • /
    • 2000
  • NZP velocities were investigated on Ag sheathed multi filamentary Bi-2223 tape and direction type HTS cable. The critical current($I_c$) of Ag sheathed Bi-2223 tape and direction type HTS cable were 12 A, 63 A at 77 K, 0 T. NZP velocities of tape with two condition of DC and AC were almost same at each temperature. In case of DC, the NZP velocities of numerical analysis and experiment were almost same. NZP velocities of direction type HTS cable were 1.9-2.4 cm/sec. The result shows that the total transport current of spiral type HTS cable in $LN_2$ was 475[A], and transport current passed through almost the outer layer (2-layer). Also, AC transport losses in outer layer of HTS cable was proportion to $I^2$ and higher than losses of inner layer. And in case of $I_p=I_c$, calculated numerical loss density was concentrated on the edge of tape and most of loss density in cable was distributed outer layer more than inner layer.

  • PDF

Transmission Loss from Voltage Drop in a DC Cable for a Floating Photovoltaic System in a Reservoir (저수지 내 수상태양광의 전압 강하에 의한 직류 송전 손실)

  • Bhang, Byeong Gwan;Woo, Sung Cheol;Lee, Wonbin;Choi, Jin Ho;Shin, SeungWook;Lee, ChulSung;Park, MiLan;Won, Changsub;Ahn, HyungKeun
    • New & Renewable Energy
    • /
    • v.16 no.1
    • /
    • pp.47-57
    • /
    • 2020
  • In Floating PV (Photovoltaic) systems, PV modules are installed on water by utilizing the surface of idle water such as a reservoir and multipurpose dam. A floating PV system, therefore, has the advantage of efficiency in national land use and improved energy yield owing to cooling effect compared to on-land PV systems. Owing to the limitation of installation environment for a floating PV system, the system, however, has the disadvantage of an increase in transmission distance of DC (Direct current) cables. A longer transmission distance of a DC cable results in greater power loss due to a voltage drop. This leads to a decline in economic feasibility for the floating PV system. In this paper, the economic analysis for 10 floating PV systems installed in a reservoir has been conducted in terms of a change in annual power sales according to the variation of transmission losses depending on the factors affecting the voltage drop, such as transmission distance, cross-section area of underwater cable, the presence of joint box, and PV capacity.

A Decentralized Optimal Load Current Sharing Method for Power Line Loss Minimization in MT-HVDC Systems

  • Liu, Yiqi;Song, Wenlong;Li, Ningning;Bai, Linquan;Ji, Yanchao
    • Journal of Power Electronics
    • /
    • v.16 no.6
    • /
    • pp.2315-2326
    • /
    • 2016
  • This paper discusses the elimination of DC voltage deviation and the enhancement of load current sharing accuracy in multi-terminal high voltage direct current (MT-HVDC) systems. In order to minimize the power line losses in different parallel network topologies and to insure the stable operation of systems, a decentralized control method based on a modified droop control is presented in this paper. Averaging the DC output voltage and averaging the output current of two neighboring converters are employed to reduce the congestion of the communication network in a control system, and the decentralized control method is implemented. By minimizing the power loss of the cable, the optimal load current sharing proportion is derived in order to achieve rational current sharing among different converters. The validity of the proposed method using a low bandwidth communication (LBC) network for different topologies is verified. The influence of the parameters of the power cable on the control system stability is analyzed in detail. Finally, transient response simulations and experiments are performed to demonstrate the feasibility of the proposed control strategy for a MT-HVDC system.