• Title/Summary/Keyword: Containment Building

Search Result 157, Processing Time 0.021 seconds

A nonlinear stress analysis of nuclear containment building using microscopic material model (미시적 재료모델을 사용한 원전 격납건물의 비선형 응력해석)

  • 이상진;김현아;서정문
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2000.10a
    • /
    • pp.320-324
    • /
    • 2000
  • Nonlinear stress analysis of nuclear containment building is carried out using microscopic concrete material model. The present study mainly focuses on the evaluation of the ultimate pressure capacity of idealized containment building in nuclear power plant. For this purpose, an eight-node degenerated shell element it adopted and an imaginary opening in the apex of containment building is allowed in FE model. From numerical analysis, the adopted concrete material model performs well and has a good agreement with the result obtained by using ABAQUS. Finally, we propose the present study as a benchmark test for nonlinear analysis of containment building.

  • PDF

Structural Health Monitoring of Nuclear Containment Building Using Fiber Bragg Grating Sensor (광섬유 브래그 격자 센서를 이용한 원자력발전소 격납건물의 구조 건전성 계측)

  • Lee, Seung-Hwan;Lee, Nam-Kwon;Lee, Geum-Seok;Lee, Hong-Pyo;Yu, Yun-Sik
    • Journal of Sensor Science and Technology
    • /
    • v.22 no.1
    • /
    • pp.71-75
    • /
    • 2013
  • Nuclear containment building is used as second blockage to protect us from a radiation leakage caused by the natural disaster or any accidents, so it's safety is important and must be kept with continuous surveillance. In this study, we measured the strain of a nuclear containment building's wall by using FBG sensor and investigated the structural safety of a nuclear containment building. 50 FBG strain sensors and 18 FBG strain sensors were attached on the side wall and upper dome of a nuclear containment building, respectively. We measured the strains of the outside concrete wall during the Structural Integrity Test (SIT) of a nuclear containment building. The strain of an upper dome was larger than that of a side wall, about $200{\mu}{\varepsilon}$. And the very small strain was measured at vertical direction of a side wall. These experimental results were used to evaluate the structural health of nuclear containment building.

External exposure specific analysis for radiation worker in reuse of containment building for Kori Unit 1

  • Byon, Jihyang;Park, Sangjune;Kim, Yangjin;Ahn, Seokyoung
    • Nuclear Engineering and Technology
    • /
    • v.54 no.5
    • /
    • pp.1781-1788
    • /
    • 2022
  • The containment building Kori Unit 1 may require sequential steps for full decommissioning. This study assumes that the containment building is to be used as an auxiliary building that handles nuclear power systems and materials during decommissioning before conversion into a greenfield. Through the derivation of guidelines and dose evaluation, it was confirmed whether the radiation workers were satisfied with the ALARA decision. The specific modeling of the external radiation exposure was performed based on the facility investigation procedures. The external radiation specific derived concentration guideline levels (DCGLs) for radiation workers in containment building were obtained using the RESRAD-BUILD code and were applied to the VISIPLAN 3D ALARA Planning Tool code to calculate the working dose and check worker safety. The derivation of site-specific and realistic DCGLs and dose evaluation via 3D modeling can contribute to the scenario development for the decommission and remediation of containment building.

A Study on Evaluation of Ultimate Internal Pressure Capacity of CANDU-type Nuclear Containment Buildings (CANDU형 원자로 격납건물의 극한내압능력 평가에 관한 연구)

  • Kim, Sun-Hoon
    • Journal of the Computational Structural Engineering Institute of Korea
    • /
    • v.24 no.3
    • /
    • pp.343-351
    • /
    • 2011
  • Nuclear containment building is the last barrier for being secure from any nuclear power plant accident. Therefore, it is very important to understand the ultimate capacity of nuclear containment building to loads associated with severe accidents. LOCA (loss of coolant accident) is considered as the basic accidental load and CANDU-type containment building is considered as a target structure in order to conduct the numerical analysis for the structural safety of a containment building. The CANDU-type containment building is a prestressed concrete shell structure which has the dome and the cylindrical wall and is reinforced with bonded tendons. In this paper, the evaluation of ultimate internal pressure capacity was carried out by nonlinear analysis of a prestressed concrete containment building using 3-dimensional structural analysis system.

Evaluation of Ultimate Pressure Capacity of Prestressed Concrete Containment Building Considering Aging of Materials (재료의 경년상태를 고려한 PSC격납건물의 극한내압능력 평가)

  • 이상근;송영철;권용길;한상훈
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2000.04a
    • /
    • pp.805-810
    • /
    • 2000
  • The purpose of this study is to predict long-term structural safety on the Yonggwang Unit 3 prestressed concrete containment building. The aging-related degradations of its main structural materials are investigated and the effects of the property variation of time-dependent materials on the structural behavior of containment building are also assessed through the analysis on the ultimate pressure capacity. The nonlinear finite element analyses for both the design criteria condition a the present aging condition are conducted to assess the present structural capacity of the containment building As a result, it is verified that the structural capacity of the Yonggwang Unit 3 containment building under the present aging condition is judged to be still rugged. n addition, the sensitivity of the ultimate pressrue capacity of containment building according to th degradation levels of the structural materials are assessed. Finally, it is showed that the sensitivity levels are in the order of the tendon, rebar and concrete in case of individual material degradations, and the tendon-rebar, tendon-concrete and rebar-concrete in case of coupled material degradations.

  • PDF

Multi-Layered Shell Model and Seismic Limit States of a Containment Building in Nuclear Power Plant Considering Deterioration and Voids (열화 및 공극을 고려한 원전 격납건물의 다층쉘요소모델과 내진성능 한계상태)

  • Nam, Hyeonung;Hong, Kee-Jeung
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.28 no.4
    • /
    • pp.223-231
    • /
    • 2024
  • For the OPR1000, a standard power plant in Korea, an analytical model of the containment building considering voids and deterioration was built with multilayer shell elements. Voids were placed in the vulnerable parts of the analysis model, and the deterioration effects of concrete and rebar were reflected in the material model. To check the impact of voids and deterioration on the seismic performance of the containment building, iterative push-over analysis was performed on four cases of the analytical model with and without voids and deterioration. It was found that the effect of voids with a volume ratio of 0.6% on the seismic performance of the containment building was insignificant. The effect of strength reduction and cross-sectional area loss of reinforcement due to deterioration and the impact of strength increase of concrete due to long-term hardening offset each other, resulting in a slight increase in the lateral resistance of the containment building. To determine the limit state that adequately represents the seismic performance of the containment building considering voids and deterioration, the Ogaki shear strength equation, ASCE 43-05 low shear wall allowable lateral displacement ratio, and JEAC 4601 shear strain limit were compared and examined with the analytically derived failure point (ultimate point) in this study.

Hydrogen explosion effects at a containment building following a severe accident (중대사고시 수소폭발이 격납건물에 미치는 영향)

  • Ryu, Myeong-Rok;Park, Kweon-Ha
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.40 no.3
    • /
    • pp.165-173
    • /
    • 2016
  • On March 11, 2011, a massive earthquake measuring 9.0 on the Richter scale and subsequent 10-.14 m waves struck the Fukushima Daiichi (FD) Nuclear Power Plant. The main and backup electric power was damaged preventing the cooling system from functioning. Fuel rods overheated and led to hydrogen explosions. If heat in the fuel rods is not dissipated, the nuclear fuel coating material (e.g., Zircaloy) reacts with water vapor to generate hydrogen at high temperatures. This hydrogen is released into the containment area. If the released hydrogen burns, the stability of the containment area is significantly impacted. In this study, researchers performed an explosion analysis in a high-risk explosion area, analyzing the hydrogen distribution in a containment building [1] and the effects of a hydrogen explosion on containment safety. Results indicated that a hydrogen explosion was possible throughout the containment building except the middle area. If an explosion occurs at the top of the containment building with more than 40% of the hydrogen collected or in the bottom right or left side of the of containment building, safety of the containment building could be threatened.

3-D Model-based UAV Path Generation for Visual Inspection of the Dome-type Nuclear Containment Building (UAV를 이용한 돔형 원자력 격납건물 외관조사를 위한 3차원 모델기반 비행 좌표 생성 방법)

  • Kim, Bong-Geun
    • Journal of KIBIM
    • /
    • v.6 no.1
    • /
    • pp.1-8
    • /
    • 2016
  • This paper provides a method for generating flight path of Unmanned Aerial Vehicle (UAV) that is intended to be used in visual inspection of dome-type nuclear containment building. The method basically employs 3-D model to extract accurate location coordinates. Two basic route patterns that provide guide lines in defining moving locations were defined for each side wall and dome section of the containment. The route patterns support sequential capturing of images as well. In addition, several simple equations and an algorithm for calculation of the moving location on the route were developed on the basis of 3-D geometric characteristics of the containment building. A prototype computer program has been implemented to validate the proposed method, and a case study shows the method can visualize covering area in 3-D model as well.

Radionuclide-Specific Exposure Pathway Analysis of Kori Unit 1 Containment Building Surface

  • Byon, Jihyang;Park, Sangjune;Ahn, Seokyoung
    • Journal of Nuclear Fuel Cycle and Waste Technology(JNFCWT)
    • /
    • v.18 no.3
    • /
    • pp.347-354
    • /
    • 2020
  • Site characterization for decommissioning Kori Unit 1 is ongoing in South Korea after 40 years of successful operation. Kori Unit 1's containment building is assumed to be mostly radioactively contaminated, and therefore radiation exposure management and detailed contamination investigation are required for decommissioning and dismantling it safely. In this study, site-specific Derived Concentration Guideline Levels (DCGLs) were derived using the residual radioactivity risk evaluation tool, RESRAD-BUILD code. A conceptual model of containment building for Kori Unit 1 was set up and limited occupational worker building inspection scenario was applied. Depending on the source location, the maximum contribution source and exposure pathway of each radionuclide were analyzed. The contribution of radionuclides to dose and exposure pathways, by source location, is expected to serve as basic data in the assessment criteria of survey areas and classification of impact areas during further decommissioning and decontamination of sites.

Three-Dimensional Structural Analysis System for Nuclear Containment Building (원자로 격납건물의 3차원 구조해석시스템)

  • Kim, Sun-Hoon
    • Journal of the Computational Structural Engineering Institute of Korea
    • /
    • v.23 no.2
    • /
    • pp.235-243
    • /
    • 2010
  • Three-dimensional structural analysis system for nuclear containment building is presented in this paper. This system includes high-performance plate/shell elements as finite element library. It also adopts numerical modeling technique for unbonded tendon as well as bonded tendon in prestressed concrete structures. This system is constructed by connecting several in-house program to a commercial program DIANA, and then is capable of performing nonlinear analysis for ultimate pressure capacity of nuclear containment building. Finally, three-dimensional structural analysis of CANDU-type containment building is carried out in order to test the reliability of this system. These numerical results are compared with reference values, which obtained from axisymmetric structural analysis.