• Title/Summary/Keyword: Condenser section

Search Result 64, Processing Time 0.031 seconds

Effect of refrigeration lubricants on the heat transfer performance in the microfin tube evaporator (마이크로핀관 증발기내 전열 성능에 미치는 냉동기유의 영향)

  • Cho, Keumnam;Tae, S.J.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.1
    • /
    • pp.61-72
    • /
    • 1999
  • The present study experimentally investigated the effect of refrigeration lubricant on the heat transfer performance in the straight sections and U-bend of a microfin tube evaporator by using R-22/mineral oil and R-407C/POE oil. The apparatus consisted of test section with U-bend, preheater, condenser, oil injection and sampling devices, magnetic pump, mass flow meter etc. The experimental parameters were oil concentration of 0 to 5 wt%, inlet quality of 0.1 to 0.5, mass flux of 219 and $400kg/m^2s$ and heat flux of 10 and $20kW/m^2$. The effects of parameters on the heat transfer coefficients were large in the order of inlet quality, mass flux and heat flux as oil concentration got increased. As oil concentration was increased, heat transfer coefficients were continuously decreased for R-22 and increased by 3% up to the concentration of 1% and then decreased for R-407C under the condition of large inlet quality, and small mass flux and heat flux. But, the heat transfer coefficients were increased up to the concentration of 3% and then decreased for both R-22 and R-407C refrigerants under the opposite conditions. The variation of enhancement factors for R-407C was under 50% of that for R-22 and the variation with respect to the positions in the test section was small. The pressure drops were increased for both R-22 and R-407C refrigerants as oil concentration was increased. The pressure drops for R-407C were smaller by the maximum of 18% than those for R-22.

  • PDF

Experimental Study for Evaporation Heat Transfer and Pressure Drop of R-22 and R-407C in an Inner Diameter of 4.3 mm and 6.4 mm (내경 4.3 mm와 6.4 mm관내 R-22와 R-407C의 증발 열전달과 압력강하에 관한 실험연구)

  • Son, Chang-Hyo;Roh, Geon-Sang
    • Journal of the Korean Institute of Gas
    • /
    • v.12 no.3
    • /
    • pp.43-49
    • /
    • 2008
  • The evaporation heat transfer coefficient and pressure drop of R-22 and R-407C in horizontal copper tubes were investigated experimentally. The main components of therefrigerant loop are a receiver, a compressor, a mass flow meter, a condenser and a double pipe type evaporator (test section). The test section consists of a smooth copper tube of 4.3 mm and 6.4 mm inner diameter. The refrigerant mass fluxes were varied from 100 to $300[kg/m^2s]$ and the saturation temperature of evaporator were 5 [$^{\circ}C$]. The evaporation heat transfer coefficients of R-22 and R-407C rise with the increase in mass flux and vapor quality. The evaporation heat transfer coefficient of R-22 for inner diameter tube of 4.3 mm and 6.4 mm is about $7.3{\sim}47.1%$ and $5.68{\sim}46.6%$ higher than that of R-407C, respectively.

  • PDF

Analysis of a Double Pipe Heat Exchanger for Waste Solvent Recovery (폐용제 회수용 이중관형 열교환기 특성 해석)

  • 구재현;이재근
    • Resources Recycling
    • /
    • v.9 no.3
    • /
    • pp.13-21
    • /
    • 2000
  • This study describes to analyze the heat transfer characteristics of waste solvent recovery system using a double pipe heat exchanger heating solvent by the hot oil. The solvent recovery system consists of the feeding pump, the double pipe heat exchanger, the vacuum spray chamber, and the condenser. A double pipe heat exchanger consists of the first section to conduct the heating of solvent to the thermal saturated point and the second section to evaporate the saturated solvent. The heat transfer area for vaporization of water, benzene and alkylbenzene was predicted by the heat balance modelling and experimentally measured from the temperature distribution as a function of solvent flow rate and heating temperature. The required heat transfer area for vaporization was increased with increasing solvent flow rates and with decreasing heating temperatures due to decreased quantity of transferred heat per the unit area. Theoretical modelling of the heat transfer area for solvents vaporization in the pipe showed good agreement with experimental results. Results showed to be suitable for the waste solvent recovery using a double pipe heat exchanger.

  • PDF

Effect of Polymer Additives on Drag Reduction for a Plate Type Heat Exchanger in OTEC Applications (고분자 첨가제에 의한 OTEC용 판형 열교환기의 마찰저항감소 효과 연구)

  • Kim, N.S.;Yoon, S.M.;Seo, T.B.;Kim, C.B.
    • Solar Energy
    • /
    • v.19 no.2
    • /
    • pp.37-44
    • /
    • 1999
  • Experimental investigation has been carried out to determine drag reducing effects of polymer additives for a plate type heat exchanger(evaporator or condenser) in OTEC power plant applications, where the pressure drop in the heat exchangers takes up $70{\sim}80%$ of the total pumping power in the existing system. The rate of drag reduction was investigated with various polymer concentrations and mass flow rates. Experiments were undertaken for a test section in Alfa-Laval plate heat exchanger utilizing Poly Ethylene Oxide(Mw $5{\times}10^6$) as polymer additives. Concentrations of polymer additives were 5, 10, 20, 30, 40, 50, 100, 200, 400 wppm at $25^{\circ}C$ and mass flow rates were 0.6kg/s, 0.7kg/s, 0.8kg/s and 0.9kg/s in normal operating ranges for a 15kW Alfa-Laval plate heat exchanger. The maximum effects of drag reductions were found at approximately 0.7kg/s of mass flow rate. The results show that there exists the optimum mass flow rate for the plate heat exchanger to obtain maximum drag reductions. Drag reduction of 20% means considerable savings in pumping power for a large size of OTEC plant.

  • PDF

Condensation heat transfer characteristics of R-22 and R-407C in micro-fin tubes (마이크로핀관에서의 냉매 R-22, R-407C의 응축전열특성에 관한 연구)

  • Roh, Geon-Sang
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.32 no.1
    • /
    • pp.50-56
    • /
    • 2008
  • Experimental results for forced convection condensation of Refrigerant-22 and ternary Refrigerant-407C(HFC-32/125/134a 23/25/52 wt%) which is being considered as a substitute R-22 inside a horizontal micro-fin tube are presented. The test section was horizontal double-tube counterflow condenser with a length 4,000 mm micro-fin tube, having 8.53 mm ID, 0.2 mm fin height and 60 fins. The range of parameters of mass velocity were varied from 102.1 to 301.0 kg/(m2.s) and inlet quality 1.0. At the given experimental conditions. the average heat transfer coefficients for R-407C were lower than that for R-22 at a micro-fin tube. Over the mass velocity range tested. the PF(penalty factor) for R-22, R-407C were lower than the increasing ratio of heat transfer area by fins, and the EF(enhancement factor) for R-22, R-407C were higher than the increasing ratio of heat transfer area by fins.

Study on the pressure drop of ternary refrigerant R-407c during condensation inside horizontal micro-fin tubes (3성분 혼합냉매 R-407c의 수평 마이크로핀관내 응축압력강하에 관한 연구)

  • 정재천
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.22 no.2
    • /
    • pp.210-218
    • /
    • 1998
  • Experimental results for forced convection condensationof Refrigerant-22 and ternary Refrigerant-407c(HFC-32/125/134a 23/25/52 wt%) considered as a substitute R-22 inside horizontal micor-fin tubes are presented. The test section was horizontal double-tubed counterflow condenser with a length 4000 mm micro-fin tube having 9.53 mm OD., 0.2 mm fin height and 60 fins. The refrigerants R-22 and R-407c were cooled by a coolant circulated in a surrounding annulus. The range of parameters of mass velocity was varied from 102.1 to 301.0kg/($\textrm{m}^{2}.s$) with inlet quality 1.0. Both refrigerant R-22 and its alternative refrigerant R-407c were tested within the same range of parameters. At the given experimental conditions for R-22 and R-407c the pressure drops for R-407c were considerably higher than those for R-22 at micro-fin tubes. Over the mass velocity range tested the PF(penalty factor)was lower than the increasing ratio of heat transfer area by fins. Based on the data correlation was proposed for predicting the frictional pressure drops for R-22 and R-407c for a duration of condensation inside a horizontal micro-fin tube.

  • PDF

Design of a Solar Thermal Storage System Employing Heat Pipes and Molten Salts (히트파이프와 용융염을 사용하는 태양열 축열조의 설계)

  • Lee, Jung-Ryun;Boo, Joon-Hong
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2011.04a
    • /
    • pp.86-91
    • /
    • 2011
  • Thermal design was conducted for a solar thermal storage system in a medium-temperature range between $200^{\circ}C$ and $400^{\circ}C$. The system was composed of heat pipes as heat carrier and molten salts as phase-change storage material. Each heat pipe penetrated through the storage system and had two heat-exchanging sections at both ends to interact with high-and low-temperature steams, while it exchanged heat with molten salts in the middle section. During a heat-storage mode, the heat pipes transferred heat from the hot steam at one side to the molten salts and it transferred heat from the molten salt to the cold steam at the other side during the heat-dissipating mode. A tube-bank type heat exchanger theory was applied to this design task to meet the required inlet and outlet temperatures of the steams depending on the operation modes. Several design variables were considered including the lengths of evaporator and condenser of a heat pipe, traverse and longitudinal pitches of the pipe, and the number of rows of the heat pipes for two different molten salt baths. An optimum design results were presented with discussion.

  • PDF

Condensing Performance Evaluation in Smooth and Micro-Fin Tubes for Natural Mixture Refrigerant (Propane/Butane) (프로판/부탄 혼합자연냉매의 평활관과 마이크로핀관 내의 응축성능평가)

  • Lee Sang-Mu;Lee Joo-Dong;Park Byung-Duck
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.9
    • /
    • pp.816-823
    • /
    • 2005
  • This paper deals with the heat exchange performance prediction of a counter flow type double-tube condenser for natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane in a smooth tube and a micro-fin tube. The local characteristics of heat transfer, mass transfer and pressure drop are calculated using a prediction method developed by the authors. The total pressure drop and the overall heat transfer coefficient are also evaluated on various heat exchange conditions. The calculated results of the natural refrigerant mixtures are compared with HCFC22. In conclusion, natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane are appropriate candidates for alternative refrigerant from the viewpoint of heat transfer characteristics.

Full Wave Cockroft Walton Application for Transcranial Magnetic Stimulation

  • Choi, Sun-Seob;Kim, Whi-Young
    • Journal of Magnetics
    • /
    • v.16 no.3
    • /
    • pp.246-252
    • /
    • 2011
  • A high-voltage power supply has been built for activation of the brain via stimulation using a Full Wave Cockroft-Walton Circuit (FWCW). A resonant half-bridge inverter was applied (with half plus/half minus DC voltage) through a bidirectional power transistor to a magnetic stimulation device with the capability of producing a variety of pulse forms. The energy obtained from the previous stage runs the transformer and FW-CW, and the current pulse coming from the pulse-forming circuit is transmitted to a stimulation coil device. In addition, the residual energy in each circuit will again generate stimulation pulses through the transformer. In particular, the bidirectional device modifies the control mode of the stimulation coil to which the current that exceeds the rated current is applied, consequently controlling the output voltage as a constant current mode. Since a serial resonant half-bridge has less switching loss and is able to reduce parasitic capacitance, a device, which can simultaneously change the charging voltage of the energy-storage condenser and the pulse repetition rate, could be implemented. Image processing of the brain activity was implemented using a graphical user interface (GUI) through a data mining technique (data mining) after measuring the vital signs separated from the frequencies of EEG and ECG spectra obtained from the pulse stimulation using a 90S8535 chip (AMTEL Corporation).

Condensation Heat Transfer Characteristics of R-410A as an Alternative R-22 in the Condenser with Small Diameter Tubes (세관을 사용한 응축기에서 R-22의 대체냉매인 R-410A의 응축 열전달 특성)

  • Son, Chang-Hyo
    • Clean Technology
    • /
    • v.13 no.2
    • /
    • pp.151-158
    • /
    • 2007
  • An experimental study to investigate the condensing heat transfer characteristics of small diameter horizontal double pipe heat exchangers with R-22 and R-410A was performed. Experimental facility was constructed to calculate and observe HTC(heat transfer coefficients), flow patterns and pressure drop. The main components include a liquid pump, an evaporator, a condenser(test section), a sight-glass, pressure taps and measurement apparatus. Two pipes of different diameters are tested; One 5.35 mm ID 0.5 mm thick, the other 3.36 mm ID 0.7 mm thick. The mass flow rate ranged from 200 to $500\;ks/m^2{\cdot}s$ and heating capacity were form 1.0 to 2.4 kW. The flow patterns of R-22 and R-410A were observed with a high speed camera through the sight-glass. The tests revealed that HTC of R-410A was higher than that of R-22 by maximum 5%. Annular pattern was observed for the most cases but stratified flow was also detected when x<0.2. The pressure drop in 3.36 mm ID pipe was higher than that of 5.35 mm by $30{\sim}50%$. Comparing with previous correlations such as Shah, Fujii and Soliman's, Fujii' showed the best good agreement with my data with a maximum deviation of 40%.

  • PDF