• Title/Summary/Keyword: Circulating Pump Speed Control

Search Result 5, Processing Time 0.021 seconds

The Analysis of Life Cycle Cost and Cooling Water Circulating Pump Energy Saving According to Variable Speed Pressure Differential Setpoint Control Strategy

  • Kim, Seo-Hoon;Kim, Jong-Hun;Jang, Cheol-Yong;Song, Kyoo-dong
    • KIEAE Journal
    • /
    • v.15 no.4
    • /
    • pp.37-43
    • /
    • 2015
  • Purpose : The study applied control strategy to reduce through optimal control and operation of pump by applying control on variable speed to the circulation pump of HVAC system in the office building. The study has the purpose to review validity of control on variable speed as ESMs(Energy Saving Measures) and establish the control technology on variable speed pump. The study performed reduction analysis of building energy and economic evaluation of pump through energy effectiveness control strategy of HVAC system. Method: The study sought possible reduction through energy control strategy which can provide proper flow fitting to building load by applying control on variable speed pump. The study applied control strategy to reduce through pressure differential set-point control and operation of pump by applying control on variable speed to the circulation pump of HVAC system in the office building. Result : The results showed that about 16-35% of pump energy could be saved by using these optimal control strategies. In the result of analysis on 10 years life cycle cost of analysis on payback period of initial investment pump, variable speed pump control showed 5.1 years.

Temperature control for a hot water heating circulating pump system using a nonlinear sliding surface (비선형 슬라이딩 면을 이용한 온수난방 순환펌프 시스템의 온도 제어)

  • Ahn, Byung-Cheon;Cang, Hyo-Whan
    • Journal of Institute of Control, Robotics and Systems
    • /
    • v.3 no.2
    • /
    • pp.162-168
    • /
    • 1997
  • Digital variable structure controller(DVSC) is implemented to control the temperature for the hot water heating circulating pump control system. For the DVSC, a control algorithm is suggested, which using a nonlinear sliding surface and a PID sliding surface outside and inside of steady state error boundary layer, respectively. Smith predictor algorithm is used for the compensation of long dead time. The DVSC of the suggested algorithm yields improved control performance compared with the one of existing algorithm. The system responses with the suggested DVSC shows good responses without overshoot and steady state error inspite of heating load change. By decreasing sampling time, dead time and rise time are increasing, and system output noise by flow dynamics is amplified.

  • PDF

Digital Variable Structure Control for a Hot Water Heating System (온수나방 시스템의 디지틀 가변구조제어)

  • 안병천;장효환
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.1
    • /
    • pp.65-75
    • /
    • 1996
  • A pilot plant, which is simplified the hot water heating control system of a large scale residential building, is used to investigate the effects of control methods and operating conditions on the system performance and to compare control characteristics. Digital variable structure controller(DVSC) and digital PI controller are implemented to control the speed of the circulating pump for the pilot plant using PC. For the DVSC, a control algorithm is suggested, which using a nonlinear sliding surface and a PID sliding surface outside and inside of output error boundary layer, respectively. Smith predictor algorithm is used for the compensation of long dead time. The suggested DVSC yields improved control performance compared with existing DVSC using linear sliding surface only. the system responses with the suggested DVSC shows good responses without overshoot for various operating conditions and robust under external disturbances compared with digital PI controller.

  • PDF

The Energy Analysis and Control Characteristics of a Hot Water Heating System for Apartment Houses (공동주택용 온수난방 시스템의 에너지해석 및 제어특성)

  • 장효환;안병천
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.1
    • /
    • pp.76-87
    • /
    • 1996
  • Energy analysis for the hot water heating control system of apartment house complex is accomplished by computer simulation. Mathematical model of a boiler, pipe network and a unit-house is developed. The effects of heating control methods on the heating performance and energy consumption of the system are investigated. The heating control methods considered in this study are a continuous heating control, and on-off heating control and an intermittent heating control methods. For each control method, the effects of an outdoor temperature, indoor temperature sensing position and the capacities of the boilers and circulating pumps on the heating performance and energy consumption are obtained and "the best" control method is recommended.commended.

  • PDF

Daily Heating Performance of a Ground Source Multi-heat Pump at Heating Mode (지열원 물대공기 멀티 히트펌프의 일일 난방 운전 특성에 관한 실증 연구)

  • Choi, Jong-Min;Lim, Hyo-Jae;Kang, Shin-Hyung;Moon, Je-Myung;Kim, Rock-Hee
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.9
    • /
    • pp.527-535
    • /
    • 2009
  • The aim of this study is to investigate the daily heating performance of ground source multi-heat pump system with vertical single U-tube type GLHXs, which were installed in a school building located in Cheonan. Daily average COP of heat pump unit on Jan. 12th, 2009 at heating mode was lower than it on Nov. 10th, 2008 and Dec. 15th, 2008, because of lower EWT of the outdoor heat exchanger and relatively smaller size of condenser and evaporator. But, the system COP on the former was higher than it on the latter because ground loop circulating pump was operated in rated speed. It is suggested that the new algorithms to control the flow rate of secondary fluid for GLHX according to load change have to be developed in order to enhance the performance of the system COP.