보강제 변화에 따른 실리콘 고무의 트래킹 열화 특성에 관한 연구 (A Study on Tracking Degradation Properties of Silicone Rubber due to Reinforcing Agent)

  • 이성일
    • 한국전기전자재료학회논문지
    • /
    • 제27권12호
    • /
    • pp.841-846
    • /
    • 2014
  • It found that the maximum temperature of the arc discharge occurred on the Silicone rubber sample significantly decreased with increasing the reinforcing agent. It was confirmed that the current value decreased with increasing the aluminium trihydrate($Al(OH)_3$) and the current value increased with reducing the primary resistance over time. Regarding these results, may be it is because the degradation due to the electro-conductive carbonization was improved and the properties of dielectric breakdown was reduced by the flame retardant reinforcing agent. It found that the electro-conductive carbonized road has not happened by increasing the flame retardant reinforcing agent. Regarding to the arc discharge, this study show that the arc arising near the lower electrode of sample has disappeared.

부분 방전에 의한 실리콘 케이블의 열화 특성에 관한 연구 (A Study on Degradation Properties of Silicone Cable due to Partial Discharge)

  • 이성일
    • 한국전기전자재료학회논문지
    • /
    • 제28권1호
    • /
    • pp.34-39
    • /
    • 2015
  • In this study, the characteristics of partial discharge was measured for the four core silicone cable (0.6/1.0 kV, $1.0SQ{\times}4C$) with insulated part of 15 cm and conductor of 1cm. The following results have been confirmed as a result of this study. When the first line of cable is connected to the positive electrode and the second, third line of cable is connected to the negative electrode, it found that the inception voltage and extinction voltage decreased with increasing the line of negative electrode, and the partial discharge charge quantity(Q) increases, while the number of discharge occurrence has decreased. The inception voltage and extinction voltage of partial discharge has decreased with increasing the degradation rate in the 33%, 67%, 100%. Also, it confirmed that the partial discharge charge quantity(Q) and the number of discharge occurrence has decreased.

NaCl에 의한 PVC 케이블의 부분방전 열화 특성에 관한 연구 (A Study on Partial Discharge Degradation Properties of PVC Cable due to NaCl)

  • 이성일
    • 한국전기전자재료학회논문지
    • /
    • 제28권10호
    • /
    • pp.636-641
    • /
    • 2015
  • In this study, the partial discharge degradation properties for 2-core PVC cable($2cores{\times}1.5mm^2$ cross section, length of 10 cm, 20 cm, 30 cm) following immersion with the salt water that the 2%, 4%, 8% of NaCl is dissolved in 100 g of distilled water for 48 and 96 hours has been measured. The results of this study are as follows. When the degradation time in salt water of 2% NaCl is 48 hours, it found that the number of partial discharge increased as about 40 pps, 50 pps, 90 pps with increasing the length of cable to 10 cm, 20 cm, 30 cm. In case the concentration and degradation time is same, the inception and extinction voltage decreased with increasing the length of cable. When the degradation time in salt water is 96 hours and the length of cable is 20 cm, it found that the number of partial discharge decreased as 3,000 pps, 500 pps, 100 pps with increasing the concentration of NaCl to 2%, 4%, 8%.