• 제목/요약/키워드: Borehole heat Exchanger

검색결과 85건 처리시간 0.025초

열응답 실험 해석 및 국내 현황 (Thermal Response Test (TRT) interpretation and the status in Korea)

  • 심병완;최충현
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.168.2-168.2
    • /
    • 2010
  • The growing market for geothermal heat pump system requires great consideration of quality control and assurance in design and construction. The borehole heat exchanger of GHP system should be sustainable, economical and ecological. Thermal Response Test (TRT) is a useful method for site investigation to obtain reliable data for a optimal system design from the technical and economical aspect. Intensive researches combined with exchange of experiences on an international level within the IEA ECES Annex 21 improved the technology. Major subjects on the interpretation of TRT are development of improved evaluation models, evaluation of the TRT with respect to geological layers and investigation of the influence of ground water. Current status of TRT in South Korea, as well as a new version of the Korean TRT standard test procedure was presented. TRT is mostly used for governmental supported projects with corresponds to more than 100 GCHP systems per year. More than 200 tests are applied, mostly on single U-tube heat exchangers (about 95%). Bentonite is the most common grouting to be used. KIGAM (Korea Institute of Geoscience & Mineral Resources) is also keeping a GIS geological and geothermal database. In the institute also laboratory measurements of rock properties are carried out. About 90% of the laboratory measurements of the rock heat conductivity shows higher values than the in-situ TRT.

  • PDF

지열 히트펌프 시스템의 계절별 지중 열교환 특성 및 지반내 온도 변화 (Temperature monitoring and seasonal borehole heat exchange rate characteristics of a geothermal heat pump system)

  • 심병완
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2007년도 춘계학술대회
    • /
    • pp.452-455
    • /
    • 2007
  • The geothermal heat pump system is designed for cooling and heating for three stories building (2,435 $m^2$) includes total 79 heat pumps. Therefore, the monitoring system is installed for each floor and the data is automatically transmitted to the monitoring system. Heat exchange rate and temperature of a geothermal heat pump system have been monitored for a long period. The seasonal operation of geothermal heat pump shows the different shape of heat exchange rate for cooling and heating. Ground water flow can influence on heat exchange rate and thermal storage of the system. In order to define the hydraulic characteristics and groundwater temperature variation, the relationships among air temperatures, groundwater temperatures, water table, and precipitation are analysed.

  • PDF

단순 선형열원 모델을 이용한 지중 유효 열전도도와 보어홀 유효 열저항 산정 (Evaluation of Ground Effective Thermal Conductivity and Borehole Effective Thermal Resistance from Simple Line-Source Model)

  • 손병후
    • 설비공학논문집
    • /
    • 제19권7호
    • /
    • pp.512-520
    • /
    • 2007
  • The design of a ground-source heat pump system includes specifications for a ground loop heat exchanger where the heat transfer rate depends on the effective thermal conductivity of the ground and the effective thermal resistance of the borehole. To evaluate these heat transfer properties, in-situ thermal response tests on four vertical test boreholes with different grouting materials were conducted by adding a monitored amount of heat to circulating water. The line-source method is applied to the temperature rise in an in-situ test and extended to also give an estimate of borehole effective thermal resistance. The effect of increasing thermal conductivity of the grouting materials from 0.818 to $1.104W/m^{\circ}C$ resulted in overall increases in effective thermal conductivity by 15.8 to 56.3% and reductions in effective thermal resistance by 13.0 to 31.1%.

제주도에 설치된 지열 열펌프 시스템용 제주형 지중열교환기의 열특성 연구 (A Study on the Thermal Characteristics of Jeju type Ground Heat Exchanger for Ground Source Heat Pump System applied to Jeju Island)

  • 김민준
    • 한국산학기술학회논문지
    • /
    • 제21권2호
    • /
    • pp.32-38
    • /
    • 2020
  • 본 연구는 제주도에 설치된 제주형 지중열교환기의 열적 특성을 분석하기 위해서 시험 방법 및 평가 방법을 정립하고, 열응답시험 (TRT)을 통하여 다양한 지역에 설치된 지중열교환기의 지중온도와 열적 특성을 분석하였다. 제주도는 화산암반층으로 이루어져 지하수의 유동이 잘 발달되어 있으며, 제주형 지중열교환기는 보어홀을 굴착 한 이후에 지하수 수위로 부터 30 m 까지 지중열교환기를 설치할 수 있다. 지중열교환기는 여러개의 파이프가 보어홀 내부에 삽입되는 구조로 되어있다. 제주형 지중열교환기의 특성을 살펴보기 위해 제주도 관내 4곳 (표선, 제주, 남원, 한림)에 설치된 지중열교환기에 대한 시험을 수행하였다. 분석결과 제주형 지중열교환기의 경우 열교환기에 열량을 투입 후 1 ~ 3시간 안에서 지중 순환수 온도가 안정화 되었으며, 열교환기가 설치된 지역에 따라서 투입열량에 따른 지중 순환수 온도 상승이 다르게 나타났다. 한림의 경우 지중열교환기 용량이 73.4 kW (냉방) / 82.8 kW (난방)로 가장 높게 나타났으며, 제주의 경우 34.1 kW (냉방) / 23.3 kW (난방)로 가장 작게 계산되었다.

지중 열교환기 성능 분석을 위한 지반 열물성 조사 (Investigation of ground thermal characteristics for performance analysis of borehole heat exchanger)

  • 심병완;송윤호;김형찬;조병욱;박덕원;임도형;이영민
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2005년도 제17회 워크샵 및 추계학술대회
    • /
    • pp.587-590
    • /
    • 2005
  • A detailed geothermal characteristics survey with numerical simulations of the heat transfer in a site for ground source heat pump system is necessary for deploying a shallow geothermal utilization system. Density, specific heat, thermal diffusivity, and thermal conductivity are measured on 91 core samples from a 300 m deep borehole in KIGAM(Korea Institute of Geoscience and Mineral Resources). The heat flow is estimated from the thermal gradient and average thermal conductivity and the correlation between fracture system and hydraulic conductivity is analyzed. From the obtained ground information of the study site the performance of the ground heat pump system can be analyzed with some detailed numerical simulations for seasonal heat pump operation skill and optimal system design techniques.

  • PDF

지열 냉난방 시스템을 위한 열전도도의 지역별 분포 (Regional Distribution of Thermal Conductivity of Ground Heat Exchanger for Geothermal Heat Pump System)

  • 임효재;손병후;정계훈
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2007년도 추계학술대회 논문집
    • /
    • pp.511-514
    • /
    • 2007
  • This study was performed to construct a geothermal data base about thermal conductivity of ground heat exchanger and thermal properties of grouting material which used to refill the borehole. We have acquired geothermal data sets from 39 sites over wide area of South Korea except to Jeju island. From data analysis, the range of thermal conductivity is $1.5{\sim}4.0$ W/mK. It means that thermal conductivity varies with grouting material as well as regional geology and ground water system.

  • PDF

지중열원 열펌프시스템의 성능해석 (A Study on the Performance of Ground Source Heat Pump System)

  • 이세균;우정선;노정근
    • 한국태양에너지학회 논문집
    • /
    • 제25권4호
    • /
    • pp.69-76
    • /
    • 2005
  • The performance of water-to-water heat pump system coupled with the ground source vertical heat exchanger is presented in this paper. The CAP program of Florida Heat Pump Co. is used to predict the heat pump performances while the EED program calculates the borehole fluid temperature. It is shown that COPH increases with decreasing the temperature of output water for the operation of heating mode and COPR increases with increasing temperature of output water for the operation of cooling mode. The value of specific heat extraction rate must be moderate to insure the reasonable installation cost of borehole system. With $1^{\circ}C$decrease of $T_{wo}$ the average COPH increase is estimated as about $0.06/^{\circ}C$(for $T_{wo}\;=\;45{\sim}60^{\circ}C$ range) while with $1^{\circ}C$ increase of $T_{wo}$ the estimation of COPR increase is about $0.13/^{\circ}C$(for $T_{wo}\;= \;5{\sim}11^{\circ}C$ range) at the specific heat extraction rate of 30W/m.

Effective modelling of borehole solar thermal energy storage systems in high latitudes

  • Janiszewski, Mateusz;Siren, Topias;Uotinen, Lauri;Oosterbaan, Harm;Rinne, Mikael
    • Geomechanics and Engineering
    • /
    • 제16권5호
    • /
    • pp.503-512
    • /
    • 2018
  • Globally there is an increasing need to reduce the greenhouse gas emissions and increase the use of renewable sources of energy. The storage of solar thermal energy is a crucial aspect for implementing the solar energy for space heating in high latitudes, where solar insolation is high in summer and almost negligible in winter when the domestic heating demand is high. To use the solar heating during winter thermal energy storage is required. In this paper, equations representing the single U-tube heat exchanger are implemented in weak form edge elements in COMSOL Multiphysics(R) to speed up the calculation process for modelling of a borehole storage layout. Multiple borehole seasonal solar thermal energy storage scenarios are successfully simulated. After 5 years of operation, the most efficient simulated borehole pattern containing 168 borehole heat exchangers recovers 69% of the stored seasonal thermal energy and provides 971 MWh of thermal energy for heating in winter.

수직형 U자 관 지중 열교환기를 갖는 지열원 열펌프의 동적 시뮬레이션 (Dynamic Simulation of Ground Source Heat Pump with a Vertical U-tube Ground Heat Exchanger)

  • 이명택;김영일;강병하
    • 설비공학논문집
    • /
    • 제19권5호
    • /
    • pp.372-378
    • /
    • 2007
  • GHX (Geothermal Heat Exchanger) design which determines the performance and initial cost is the most important factor in ground source heat pump system. Performance of GHX is strongly dependent on the thermal resistance of soil, grout and pipe. In general, GHX design is based on the static simulation program. In this study, dynamic simulation has been peformed to analyze the variation of system performance for various GHX parameters. Line-source theory has been applied to calculate the variation of ground temperature. The averaged weather data measured during a 10-year period $(1991\sim2000)$ in Seoul is used to calculate cooling and heating loads of a building with a floor area of $100m^2$. The simulation results indicate that thermal properties of borehole play significant effect on the overall performance. Change of grout thermal conductivity from 0.4 to $3.0W/(m^{\circ}C)$ increases COP of heating by 9.4% and cooling by 17%. Change of soil thermal conductivity from 1.5 to $4.0W/(m^{\circ}C)$ increases COP of heating by 13.3% and cooling by 4.4%. Change of GHX(length from 100 to 200 m increases COP of heating by 10.6% and cooling by 10.2%. To study long term performance, dynamic simulation has been conducted for a 20-year period and the result showed that soil temperature decreases by $1^{\circ}C$, heating COP decreases by 2.7% and cooling COP decreases by 1.4%.

지종열 활용에 따른 온도변화 모니터링 (Monitoring of Subsurface Temperature Variation as Geothermal Utilization)

  • 이태종;심병완;송윤호
    • 한국지열·수열에너지학회논문집
    • /
    • 제6권1호
    • /
    • pp.29-35
    • /
    • 2010
  • Long-term temperature monitoring has been performed for ground heat exchanger at the Earthquake Research Center (ERC) building in Korea Institute of Geoscience and Mineral Resources (KIGAM). For the 3 years of monitoring, overall temperature increases are observed at various depths within a borehole heat exchanger. But monitoring of ground temperature variation at the monitoring well beforehand showed that geothermal utilization is not the only source for the temperature increase, Because various kinds of sources can cause the ground temperature change, more thorough investigation should be followed.