• 제목/요약/키워드: Blackout zone

검색결과 5건 처리시간 0.022초

A Special Protection Scheme Against a Local Low-Voltage Problem and Zone 3 Protection in the KEPCO System

  • Yun, Ki-Seob;Lee, Byong-Jun;Song, Hwa-Chang
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권3호
    • /
    • pp.294-299
    • /
    • 2007
  • This paper presents a special protection scheme, which was established in the KEPCO (Korea Electric Power Corporation) system, against a critically low voltage profile in a part of the system after a double-circuit tower outage. Without establishing the scheme, the outage triggers the operation of a zone 3 relay and trips the component. This sequence of events possibly leads to a blackout of the local system. The scheme consists of an inter-substation communication network using PITR (Protective Integrated Transmitter and Receiver) for acquisition of the substations' data, and under-voltage load shedding devices. This paper describes the procedure for determining the load shedding in the scheme and the experiences of the implementation.

Pilot Bus의 정보를 이용한 효율적인 지역별 전압제어 (Effective Localized-Voltage Control Scheme using the Information from Pilot Bus)

  • 송성환;윤용태;문승일;이호철
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제55권12호
    • /
    • pp.505-513
    • /
    • 2006
  • One of the major reasons for recent blackout, like August 14, 2003 blackout in the US and Canada has been insufficient voltage/reactive power support. For the stable reactive power management, a new approach for the voltage monitoring and control structure is required in the market environment. This paper proposes the effective localized-voltage control scheme using the information from pilot buses at each zone. In this paper, the steady state voltage monitoring and control (SSVMC) is adopted and illustrated for the voltage control scheme during steady state because it is thought as the systemic algorithm to explain voltage profile phenomenon before and after contingencies. And the concept of electrical distance is applied to simultaneously achieve both clustering the voltage control zone, and selecting the pilot bus as the representative node at each control zone. Applying SSVMC based on the structure with clustering and pilot bus enables system operators to monitor and understand the system condition much more easily, to monitor and control the voltage in real-time more manageably, and to respond quickly to a disturbance. The proposed voltage control scheme has been tested on the IEEE 14-bus system with the numerical analysis to examine the system reliability and structure efficiency.

25.8kV급 GIS에 Matrix System을 적용한 전력설비 최적화 연구 (A Study on Optimization of Electric Power Facilities Applied Matrix System at 25.8kV GIS)

  • 이양미;남재우;김철환
    • 전기학회논문지
    • /
    • 제66권3호
    • /
    • pp.507-512
    • /
    • 2017
  • Recently, more electric power facilities have been miniaturized and it is noted that the facilities maintenance will be essential through operation optimization. In this paper we applied and examined the operation optimization of electric power facilities by applying Matrix system which can improve reliability to minimize outage and recover failure rapidly when blackouts happen at 25.8kV Gas Insulated Switchgear(GIS). The fundamental problem for facilities maintenance of GIS can happen due to indeterminable internal state in real time. Matrix optimization organizes action states in all containers which contain pressurized $SF_6$ Gas such as circuit breaker, disconnector switch, bus for utilizing them each area. Then, we connect it with power system to monitor and control internal state remotely in real time, and we can minimize blackout zone or outage. Considering above process, we improved stability of overall facilities.

광역정전 방지를 위한 적응형 거리계전 기법 (Adaptive Distance Relaying Scheme to Prevent Large Blackout)

  • 배재광;임성일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.44-45
    • /
    • 2008
  • The zone 3 elements of distance relays play an important role during the propagation of cascaded events. The most challenging problem to mitigate catastrophic failures is to distinguish between actual faults with line flow transfer from other disconnected lines. This paper presents an adaptive protective relaying scheme based on Line Outage Distribution Factor(LODF) and Generation Shift Factor(GSF) to prevent zone 3 tripping during the cascaded events. Internet based secure peer to peer communication is recommended as a communication method of proposed scheme. Several communication issues such as reliability, speed and cyber security are discussed. In order to establish the feasibility of the proposed scheme, computer simulations for a six bus system has been performed.

  • PDF

네트워크 통신장비의 진동 해석 (Vibration Analysis of Network Communication Equipment)

  • 이재환;김영중;김진섭
    • 한국전산구조공학회논문집
    • /
    • 제20권4호
    • /
    • pp.463-468
    • /
    • 2007
  • 최근 일본에서 발생한 지진으로 이동통신용 전자장비들이 많이 파손되었으나. 국내에서 제작되어 일본에 설치된 모제품은 강진에서도 대부분 구조적 손상이 없었다. 본 논문에서는 이동통신 네트워크 장비의 정/동적 특성을 평가하기 위하여 제품의 유한요소 모델을 생성하여 정적 및 동적 구조해석을 수행하였다. 또한 Zone 3 GR-63-CORE 동적 실험을 수행하여 제품의 안정성을 검증하였고, 유한요소 구조해석 결과와 비교하여 실험과 해석 결과가 유사함이 입증되었다. 구조해석 결과인 동적 응답특성은 실험보다 다소 크게 나왔으며, 부재의 특성파악을 위해 구조물의 치수를 설계변수로 하여 진동특성에 대한 민감도 해석으로 고유진동수에 민감한 부재를 판별하였고, 치수변경으로 경량화 설계치를 산출하였다. 경량화된 디자인의 동적 응답변위가 원래 디자인보다 작게 나와 최적화 결과가 유용할 것으로 보인다.