The Influence of Transverse Magnetic Field for Shortening DC Arc Time (직류 아크 소호 시간을 단축시키는 직교자계의 영향)

  • Lee, Eun-Woong;Cho, Hyun-Kil
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.3
    • /
    • pp.146-154
    • /
    • 2006
  • We derived a theory of increasing electromagnetic force which acts on arc column for reducing arcing time between electric contacts. A simulation method of arc velocity is presented by calculating blowout force using 3D FEM and drag force acting on arc column. This paper proposes 3 types arc extinguish chamber of different flux path and presents the specific electromagnetic force and arc velocity of each model by the analysis. The result of analysis and experimental proposes the prediction method of arc time when all conditions are same except external magnetic field.

Effect of S on Spatter Generation and Droplet Transfer Phenomena of MAG Welding (MAG용접의 스패터 발생 및 용적이행현상에 미치는 S의 영향)

  • 안영호;이종봉;최원규
    • Journal of Welding and Joining
    • /
    • v.19 no.5
    • /
    • pp.486-491
    • /
    • 2001
  • The effect of S content in welding wires on spattering characteristics and droplet transfer phenomena was studied. In MAG welding using 80%Ar-$20%CO_2$ shielding gas, spattering characteristics and droplet transfer phenomena were varied with S content of wire. Sulfur addition in wire reduced surface tension of droplet and weld pool, and made arc more stable in MAG welding. With increasing S content, the spattering ratio and the ratio of large size spatter ($d{\geq}1.0mm$) were reduced in short circuit transfer mode. In spray transfer mode, spattering ratio, however was increased when sulfur was added more than 0.020wt.% because surface tension of droplets and weld pool was reduced too much even though arc stability was improved.

  • PDF

Effects of Ageing Factors on Low Molecular Weight Silicone Fluids Content Fluids Content and Surface Hydrophobicity in HTV Silicone Rubber (HTV 실리콘 고무에서 열화인자에 따른 저분자량 성분과 표면 발수성의 변화)

  • 허창수;연복희;조한구
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.12 no.1
    • /
    • pp.1-10
    • /
    • 1999
  • In this paper, we have investigated the effects of the environmental factors on Low Molecular Weight (LMW) silicone fluid contents existing in high temperature vulcanized (HTV) silicone rubber sample, using dipping method and contact angle, current measurement. Artificial treatments such as immersion in water, elevated temperature, UV irradiation and dry band arcing under salt-fog condition are selected as the environmental factors. This results will be helpful to investigate the degradation with time and to expect a life time, because the LMW silicone content, which is important to recovery the hydrophobicity of silicone rubber surface, show different results by each environmental factors.

  • PDF

A Study on the Developing Method of HIF Monitoring Data using Wavelet Coefficient (웨이브렛 계수를 이용한 고저항 지락고장 감시데이터 산출방법 연구)

  • Jung, Young-Beom;Jung, Yeon-Ha;Kim, Kil-Sin;Lee, Byung-Sung;Bae, Seung-Chul
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.2
    • /
    • pp.155-163
    • /
    • 2013
  • As the increasing HIF(High Impedance Fault) with the arc cannot be easily detected for the low fault current magnitude compared to actual load in distribution line. However, the arcing current shows that the magnitude varies with time and the signal is asymmetric. In addition, discontinuous changes occur at starting point of arc. Considering these characteristics, wavelet transformation of actual current data shows difference between before and after the fault. Althogh raw data(detail coefficient) of wavelet transform may not be directly applied to HIF detection logic in a device, there are several developing methods of HIF monitoring data using the original wavelet coefficients. In this paper, a simple and effective developing methods of HIF monitoring data were analized by using the signal data through an actual HIF experiment to apply them to economic devices. The methods using the sumation of the wavelet coefficient squares in one cycle of the fundamental frequency as the energies of the wavelet coefficeits and the sumation of the absolute values were compared. Besides, the improved method which less occupies H/W resouces and can be applied to field detection devices was proposed. and also Verification of this HIF detection method through field test on distribution system in KEPCO power testing center was performed.

S-Transform Based Time-Frequency Analysis of Leakage Current Signals of Transmission Line Insulators under Polluted Conditions

  • Natarajan, A.;Narayanan, Suthanthiravanitha
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.616-624
    • /
    • 2015
  • Flashover of power transmission line insulators due to contamination is a major threat to the reliable operation of power system. This paper deals with the analysis of leakage current characteristics of polymeric insulator using S-Transform technique in order to develop a better diagnostic tool to identify the surface condition of outdoor polymeric insulators. In this work, experiments were carried out on 11 kV silicone rubber insulator under AC voltage at different pollution levels. Moving average technique was adopted to find the trend followed by LC peak at different relative humidity conditions. S-Transform was used to find the relationship between energy and frequency content of the leakage current signal with respect to increase in pollution level over a period of time. From the S-Transform time-frequency contour analysis, point of transition to severe arcing due to increase in pollution and its thershold limit were evaluated. Reported results show that the surface condition of insulators could be easily identified from the S-Transform time-frequency analysis of leakage current signals.

An Improved Two-Terminal Numerical Algorithm of Fault Location Estimation and Arcing Fault Detection for Adaptive AutoReclosure (고속 적응자동재폐로를 위한 사고거리추정 및 사고판별에 관한 개선된 양단자 수치해석 알고리즘)

  • Lee, Chan-Joo;Kim, Hyun-Houng;Park, Jong-Bae;Shin, Joong-Rin;Radoievic, Zoran
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.11
    • /
    • pp.525-532
    • /
    • 2005
  • This paper presents a new two-terminal numerical algorithm for fault location estimation and for faults recognition using the synchronized phaser in time-domain. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the assumed PMUs(Phasor Measurement Units) installed at both ends of the transmission lines. Also the arc voltage wave shape is modeled numerically on the basis of a great number of arc voltage records obtained by transient recorder. From the calculated arc voltage amplitude it can make a decision whether the fault is permanent or transient. In this paper the algorithm is given and estimated using DFT(discrete Fourier Transform) and the LES(Least Error Squares Method). The algorithm uses a very short data window and enables fast fault detection and classification for real-time transmission line protection. To test the validity of the proposed algorithm, the Electro-Magnetic Transient Program(EMTP/ATP) is used.

A Study on the High Speed Interruption of Parallel Arcing (병렬아크의 고속차단에 관한 연구)

  • Kil, Gyung-Suk;Ji, Hong-Keun;Park, Dae-Won;Kim, Il-Kwon;Kim, Young-Il;Cho, Young-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.95-100
    • /
    • 2008
  • Conventional Earth Leakage Circuit Breakers (ELCBs) have defects of a breaking failure or a long breaking-time against parallel arc current. In this paper, breaking characteristics of conventional ELCBs were analyzed by simulation of parallel arc in a low-voltage indoor wiring system, and an air-core current sensor and a signal converter being most available for parallel arc detection were developed and applied to a conventional ELCB. The proposed tripped the ELCB regardless of the location of parallel arc. The breaking-time was in ranges of $1.74{\sim}8.3[ms]$ depending on the phase of arc generation, which is about 5 times as fast as conventional ELCBs with the breaking-time of 50[ms].

The study for Improving Arc Extinction Capability of DC Magnetic Switch (직류전자 접촉기의 아크 소호력 향상)

  • Cho, Hyun-Kil;Lee, Eun-Woong;Lim, Su-Saeng;Lee, Hwa-Su;Sea, Jeong-Min;Kim, Gyun-Muk
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.888-890
    • /
    • 2002
  • We derived a theory of increasing electromagnetic force acting on arc column for reducing arcing time between electric contacts. A simulation method of arc velocity is presented by calculating blowout force using 3D FEM and drag acting on arc column. This paper is proposed 3 types arc extinguish chamber of different fulx path and is presented electromagnetic force and arc velocity of each model.

  • PDF

Two-Terminal Fault Location Estimation Algorithm Considering Arcing Ground Fault (아크 지락 사고를 고려한 양단자 사고거리 추정 알고리즘)

  • Kim, Hyun-Houng;Lee, Chan-Joo;Cho, Ki-Sun;Park, Jong-Bae;Shin, Joong-Rin
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.166-168
    • /
    • 2005
  • This paper presents a new numerical algorithm devoted to one window onto fault location calculation in time domain. It is based on two terminal data processing and it is derived on the synchronized phasor measured from the GPS connected the trans-mission line. The data is obtained by the testing through EMTP (Electromagnetic Tran- sient Program). The proposed the algorithm is estimated using linear least error squares method. The results of the algorithm testing through computer simulation (MATLAB) are presented.

  • PDF

Simplified Synthetic Testing Facility with Modified TRV Circuit

  • Chong, Jin-Kyo;Lee, Kyung Seob;Lee, Chang-Hoon;Kim, Gyu-Tak
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.881-885
    • /
    • 2018
  • In order to develop a gas circuit breaker (GCB), the breaking performance of the short line fault (SLF) should be prioritized over that of the breaker terminal fault (BTF). In brief, it is necessary to evaluate the thermal characteristics of the insulating gas that is filled in a GCB. In the process of developing a GCB, many companies use the simplified synthetic testing facility (SSTF).In order to evaluate the SLF breaking performance of a GCB with a long minimum arcing time, a modifications to the conventional SSTF was proposed. In this study, we developed the SSTF with a modified transient recovery voltage circuit. The performance of the newly developed SSTF was verified by an $L_{90}$ breaking performance test on a rating combination of 170 kV, 50 kA, and 60 Hz.