• Title/Summary/Keyword: Absorption Heat Pump

Search Result 105, Processing Time 0.029 seconds

Experimental Performance Study of the Bubble Pump for the Diffusion Absorption Refrigerating System (확산형 흡수식 냉동시스템의 기포펌프 성능실험)

  • 이재효;정의갑;윤재호;정의갑
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.3
    • /
    • pp.287-292
    • /
    • 2004
  • An experimental investigation was carried out to study the performance of a bubble pump for the diffusion absorption refrigerating system. Ammonia was used as the refrigerant and the helium was charged in order to balance the pressure between the low and high pressure side. As experimental variables, the concentration of ammonia charged into system, heat input, and the pressure of helium were selected. Experimental results show that the generation rate of ammonia vapor and the circulation rate of diluted ammonia solution were increased as the heat input increases, but the ratio of the solution to vapor flow rate was decreased. The generation rate of refrigerant vapor and the circulation rate of diluted ammonia solution increased as the system pressure decreased. Finally under the condition of 25 bars, the concentration of rich ammonia solution was not affected by the generation rate of ammonia vapor and the circulation of diluted ammonia solution.

Experimental Study on Compression/Absorption High-Temperature Hybrid Heat Pump with Natural Refrigerant Mixture (천연혼합냉매를 이용한 압축/흡수식 고온히트펌프의 실험적 연구)

  • Kim, Ji-Young;Park, Seong-Ryong;Baik, Young-Jin;Chang, Ki-Chang;Ra, Ho-Sang;Kim, Min-Sung;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.12
    • /
    • pp.1367-1373
    • /
    • 2011
  • This research concerns the development of a compression/absorption high-temperature hybrid heat pump that uses a natural refrigerant mixture. Heat pumps based on the compression/absorption cycle offer various advantages over conventional heat pumps based on the vapor compression cycle, such as large temperature glide, temperature lift, flexible operating range, and capacity control. In this study, a lab-scale prototype hybrid heat pump was constructed with a two-stage compressor, absorber, desorber, desuperheater, solution heat exchanger, solution pump, liquid/vapor separator, and rectifier as the main components. The hybrid heat pump system operated at 10-kW-class heating capacity producing hot water whose temperature was more than $90^{\circ}C$ when the heat source and sink temperatures were $50^{\circ}C$. Experiments with various $NH_3/H_2O$ mass fractions and compressor/pump circulation ratios were performed on the system. From the study, the system performance was optimized at a specific $NH_3$ concentration.

Study on the Simulation of Heat Pump Heating and Cooling Systems to Resident Building (숙박업소 건물의 히트펌프 냉난방 시스템 적용을 위한 시뮬레이션 연구)

  • Choi, Young-Don;Han, Seong-Ho;Cho, Sung-Hwan;Kim, Du-Sung;Um, Chul-Jun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.1
    • /
    • pp.65-74
    • /
    • 2008
  • In Korea, air source heat pump system is less efficient than conventional heat source facilities, such as ground source, river water, because the air temperature in winter season is so low that COP of air source heat pump system drops below 3.0. Therefore, the study on the application of heat pump heating and cooling systems is crucial for the efficient popularization of heat pump. In this work, we present the dynamic analysis of energy consumption for the large resident building by heat resistance-capacitance method. The system simulation of water storage air source heat pump is additionally performed by changing of sizes and locations of the hospital building. The computed results show that energy cost of water storage air source heat pump is low, so it is more economical than absorption chiller & heater.

Performance and Parameter Comparison between single stage and Two-Stage Compression/Absorption Heat Pump System (단단 및 2단 압축/흡수 히트펌스시스템의 성능 및 중요인자비교 분석)

  • Tian, Huaizhang;Park, Seong-Ryong
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.451-456
    • /
    • 2005
  • The mathematical model for the heat exchangers of absorber and desorber is made in the elementary control volume method and the thermodynamic properties of working fluid. water/ammonia mixture. are calculated by some fundamental subroutines in RefProp 7.0 and flash subroutines made by authors The simulation results show that two-stage cycle has higher COP than single stage if temperature lift is high: the performance of single stage compression cycle can be improved by increase of absorber pressure. but the performance of two-stage compression cycle can not be improved in this way : the compressor discharging temperature of two-stage compression is much lower than that of single stage cycle. which is very important to the safety operation of CA heat pump. Major parameter comparison between the cycles at their optimal configurations is also given.

  • PDF

A Study on Partial Load Performance of Absorption Type Heat Pump for Waste Heat Recovery of Closed Cooling Water (기기냉각수 폐열회수용 흡수식 히트펌프의 부분부하 성능에 관한 연구)

  • Park, Byungchul;Kim, Taehyeong;Kim, Kwangsu
    • Journal of Energy Engineering
    • /
    • v.28 no.2
    • /
    • pp.47-54
    • /
    • 2019
  • As absorption type heat pump for waste heat recovery is installed in combined cycle power plant for Energy Service Company, performance test is implemented to confirm the operation data on partial load. The operation data changes according to the heat pump operation on partial load are as follows. Total heat output increases, because waste heat of closed cooling water and a portion of LP steam from HRSG is supplied. But electric power output of steam turbine is reduced, because LP steam to steam turbine is reduced. And heat output from HP district heater and LP district heater is reduced, because HP turbine exhaust steam to HP district heater and LP district heater is reduced. On partial load operation, turbine output reduction is higher than the base load operation. Therefore, on partial load, heat pump should be operated in consideration of the heat output increase and electric power output reduction.

Performance Characteristic of the Compression-Absorption Hybrid Heat Pump Cycles (흡수압축 하이브리드 히트펌프 사이클의 성능특성)

  • Yoon J. I.;Kwon O. K.;Yang Y. M.
    • Journal of the Korean Institute of Gas
    • /
    • v.3 no.1
    • /
    • pp.14-20
    • /
    • 1999
  • This study describes the results of Coefficient of Performance(COP) analysis by cycle simulation for two types of absorption-compression hybrid cycle using the Water/Lithium Bromide solution pair. These types are basic hybrid systems introducing a mechanical compression process into the refrigerant vapor phase of the single effect absorption cycle. In absorption-compression hybrid cycles, coefficient of performance is improved compared with absorption cycle. Hybrid cycle Type 2 is considered as a key technology to support energy utilization system, given its capability of utilizing waste heat to drive system with a high level of efficiency.

  • PDF

The heat transfer characteristics of a desorber for 150 RT absorption heat pump (150 RT급 흡수식 열펌프용 고온재생기의 열전달 특성)

  • 박찬우;정종수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.369-376
    • /
    • 1999
  • Experiments were carried out to study the heat transfer characteristics of a disrober for 150 RT LiBr-water absorption heat pump. An experimental apparatus was divided into four sections, a combustion chamber area, two bare-tube areas, and finally a finned-tube area to quantify the heat transfer rate of each section by measuring the generation rate of vapor. Dividing plates was installed at the upper inside part of deserter to prohibit the moving of vapor generated at heating tubes of a section to another section near. In the first bare-tube area, the generation rate of vapor was the largest among the four sections. The finned-tube area only contributed to give sensible heat increase of solution to the saturation temperature. The heat transfer area of the finned-tube area was 52.2%, which absorbed only 9.2% of the total heat from the combustion gas. On the contrary, the heat transfer area of the first bare-tube area was 16.6%, but it absorbed 52.4% of the total absorbed heat. The temperature of the solution at upper part at the finned-tube area was lower than that of the lower part, because weak solution came in upper part of the finned-tube area. But, this tendency was changed at the first and second bare-tube area due to the vigorous heat transfer and fluid flow enhanced by vapor generation through heating tubes. The overall heat transfer coefficient and heat flux were the largest at the first bare-tube area among the other sections.

  • PDF

Performance Characteristics of Type II LiBr-H2O Absorption Heat Pump in Accordance with the Refrigerant Heat Exchanger Configuration (냉매 열교환기 구성방법에 따른 제 2종 흡수식 히트펌프의 성능 특성 변화에 관한 연구)

  • Lee, Chang Hyun;Yoon, Jun Seong;Kim, In Gwan;Kwon, Oh Kyung;Cha, Dong An;Bae, Kyung Jin;Kim, Min Su;Park, Chan Woo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.7
    • /
    • pp.373-384
    • /
    • 2017
  • The objective of this study was to determine the effect of refrigerant heat exchanger on the performance of type II absorption heat pump performance using numerical analysis. Two heat exchange installation methods were used: solution to refrigerant and waste hot water to refrigerant. These methods were compared to the standard model of hot water flow without using refrigerant heat exchanger. When waste hot waters were bypassed to refrigerant heat exchanger, COP was not affected. However, steam mass generation rates were increased compared to those of the standard model. When solutions were bypassed to the refrigerant heat exchanger, results were different depending on the place where the solution rejoined. COP and steam mass generation rates were lower compared to those when waste heat water was passed to refrigerant heat exchanger. Thus, it is possible to obtain higher steam mass generation rates by using waste water and installing refrigerant heat exchanger.

The Energy Consumption Characteristics of Building Accordance with Air-Conditioning and Heating System (건축물 냉.난방 시스템에 따른 에너지 소비 특성 -서울 소재 A 대학교 건축물을 중심으로-)

  • Park, Kang-Hyun;Cha, Jung-Hoon;Kim, Su-Min
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2011.11a
    • /
    • pp.333-337
    • /
    • 2011
  • Central control air-conditioning systems are being replaced with individually controlled air-conditioning system in the university. The amount of growth of electricity consumption is due to the increasing demand of electric heat pump. In winter and summer, the energy consumption showed a tendency to increase. On the other hand, showed less energy in spring and autumn. Increase the amount of electricity than the degree of decline in gas consumption was higher. Can be considered as transitional phenomena. Because electric heat pump, gas driven heat pump and the absorption chiller-heater are used at the same time in some of the buildings.

  • PDF

Analysis of the Operation Conditions and Energy Consumption for Each Energy Source (에너지원별 냉방기기 에너지 소비 및 운영현황 분석)

  • Kang, Yong-Tae;Kim, Min-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.195-200
    • /
    • 2009
  • The objectives of this study are to analyze of energy consumption and operation conditions of each cooling system for gas and electric driven systems, and to compare operating cost for five different cooling systems; ice storage system, system air-condition, turbo chiller as the electric driven cooling systems, and absorption chiller and Gas driven Heat Pump (GHP) as the gas driven cooling systems. The sample designs are carried out based on the types of business, capacity, installation region and year.

  • PDF