• 제목/요약/키워드: Absorption Heat Pump

검색결과 105건 처리시간 0.027초

알코올 흡수식 열펌프의 난방성능 예측 (Simulation of Alcohol Absorption Heat Pumps for Heating Performance)

  • 김동선
    • 설비공학논문집
    • /
    • 제27권5호
    • /
    • pp.269-276
    • /
    • 2015
  • Single-effect $CH_3OH-LiI-ZnBr_2$ and $C_2H_5OH-LiI$ absorption heat pumps are simulated to evaluate feasibility as heating device. These systems are predicted to give higher heating COPs in wide operating ranges compared to conventional systems. Among the two systems, the $C_2H_5OH-LiI$ system is found to be more advantageous for operating in extremely cold weather due to the large solubility of Lil in $C_2H_5OH$.

2 중효용 흡수식 히트점프의 난방 성능 해석 (Thermodynamic Analysis of an Absorption Heat Pump Heating System with LiBr-Water Solution)

  • 원승호;이원용;정헌생
    • 태양에너지
    • /
    • 제9권3호
    • /
    • pp.73-80
    • /
    • 1989
  • This paper presents as assessment based on steady-state thermodynamic analysis and computer modeling of a double effect generation absorption heating cycle for solar air-conditioning to find operating temperature ranges. The influences of component temperatures on the heating coefficients of performance and mass flow ratio have been investigated to obtain optimum operating conditions for the proposed air conditioning system. And the single and double effect absorption cycles are compared with each other over the same range of temperatures.

  • PDF

대학 캠퍼스 냉·난방시스템 최적화 방안 연구 (A Study on the Optimization of Heating and Cooling System in University Campus)

  • 박소연;박효순;이상혁;김지연;홍성희
    • KIEAE Journal
    • /
    • 제10권6호
    • /
    • pp.139-144
    • /
    • 2010
  • The demands are increasing for the efficient heating and cooling system and thermal comfort environment because of changes in climate and environment, and deterioration of buildings and facilities can cause education budget to increase. So the study to apply heating and cooling system to university is urgently needed to improve an optimum energy saving system, educational environment and convenience of maintenance. For this reason, we selected a university campus in Seoul then came to understand the current situation and found some problems. We drew alternatives from comparative analysis of them. It selects representative building and carries out economic analysis to evaluate characteristics of energy consumption and economics on each type of heating and cooling system. As a result we drew the optimum system from those processes as previously stated. We studied 3 available systems, absorption chiller, EHP(Electric Heat Pump) and GHP(Gas Engine Heat Pump). According to LCC analysis suppose that the value of EHP is 1, it came out that the value of absorption chiller is 1.5 and the value of GHP is 2.2. This study, suggesting the optimum heating and cooling system, will support educational and research activities furthermore effect to maximize energy efficiency. Ultimately it is expected that it will contribute to make eco-friendly Green Campus.

화학식 냉동기의 성능 및 반응기 거동에 관한 연구 (A Study on Performance and Reactor Behavior of Chemical Refrigerator)

  • Park, Seung-Hoon;Lee, Jong-Ho
    • 에너지공학
    • /
    • 제6권1호
    • /
    • pp.87-95
    • /
    • 1997
  • 금속염화물과 암모니아간의 가역반응을 이용한 화학열펌프는 비프레온계 냉동 냉장시스템으로서 환경규약의 제한이 없고 가스, 전기 및 산업폐열 등 다양한 구동열원을 사용할수 있으며 축열에 의한 에너지 저장이나 산업공정에서의 대용량 에너지관리 시스템 등 응용분야가 다양한 장점을 갖고 있다. 통상 소규모의 실험실 장치에서 파일롯트 플랜트(pilot plant)로 전환하는 과정에서 시스템의 성능에 대한 해석이 필요하며 화학반응기의 거동에 대한 컴퓨터 모사도 필수적이다. 따라서 본 연구에서는 작동조건에 따라 화학식 냉동기 성능계수가 어떻게 변하는지를 예측하였고 반응기 모델링에 의한 동적모사를 수행하여 반응기의 온도거동, 작동조건에 따른 전화율 변화, 반응혼합물의 제조변수가 냉동기 성능에 미치는 영향 등을 고찰하였다.

  • PDF

흡수기 용액 재순환이 흡수식 냉동기 성능에 미치는 영향 (The Influences of LiBr Solution Recirculation in Absorber on the Absorption Chiller Performance)

  • 정종수;진성민;박찬우;최승학;정봉철
    • 대한기계학회논문집B
    • /
    • 제26권5호
    • /
    • pp.733-741
    • /
    • 2002
  • If a part of the poor solution from the absorber outlet is recirculated to the absorber inlet, the solution temperature at the solution spray pump can be reduced, and the solution flow rate in the absorber is increased. We have performed the experiments on the influences of the absorption chiller performance according to the ratio of the recirculation, defined as the ratio of the recirculation flow rate to the total solution flow rate at the absorber outlet. As increasing the ratio of the recirculation, the absorption capacity of the solution can be deteriorated. On the other hand, due to the increasing flow rate, the heat transfer rate can be enhanced. As a result, the performance of the absorber and the cooling capacity of the absorption chiller have nothing to do with the recirculation ratio, and the lifetime of the spray pump will be maintained.

냉각수 보급이 가정용 흡수식 냉난방기의 성능에 미치는 영향 (Effect on Household Absorption Chiller by the Supply of the Cooling Water)

  • 이호생;김동휘;최병권;김재돌;윤정인
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2002년도 춘계학술대회논문집
    • /
    • pp.267-272
    • /
    • 2002
  • The electric heat pump requiring HCFCs as a refrigerant has been for most residential air-conditioners in Korea. They cause a surge up electric power demand during summer. Moreover, the use of HCFCs and HFCs causes a serious problem to the global environment such as global warming and ozone layer destruction. An absorption chiller and heater could solve such problems. It was built and tested for analyzing the performance of the absorption chiller/heater. Experiment was done with a 1.5RT household absorption chiller and heater. It was experimented that the cooling capacity, gas capacity, COP were researched by the temperature of cooling water. The change of the cooling water temperature have effect the temperature(or pressure) of the parts on absorption chiller The result of the change of the cooling water temperature have the effects of the absorption chillers. This data will help to operate the household absorption chiller and heater.

  • PDF

흡수식 2중효용 시스템의 증발기 열원으로 태양열을 이용하는 LiCl 수용액 난방시스템 해석 (Analysis of Thermodynamic Design Data of Double-Effect Absorption System for Heating using LiCl-water for Evaporator Heating Source of Solar Energy)

  • 원승호
    • 한국태양에너지학회 논문집
    • /
    • 제24권3호
    • /
    • pp.39-46
    • /
    • 2004
  • In this paper, thermodynamic design data for heating of double-effect absorption system using LiCl-water for evaporator heating source of sofar energy are investigated for the water-LiCl pair and a comparative study of the water-LiCl pair with the water-LiBr pair is given used for the computer simulation. The computer simulation is based on mass, material and heat balance equations for each part of the system. Coefficients of performance and flow ratios for effects of different operating temperatures are investigated. It is found that the heating COP is higher for the water -LiCl pair than for the water-LiBr pair, and FR is lower for the water-LiCl pair than for the water LiBr pair.

2종류의 건조기로 제조한 돌기해삼(Apostichopus japonicus)의 복원율과 지방산조성 비교 (Comparison of Recovery Rate and Fatty Acid Composition of Dried Sea Cucumbers Apostichopus japonicus Dried by Hybrid Heat Pump Decompression and by Hot Air)

  • 정우철;;;최병대;정현철;이상로;강석중
    • 한국수산과학회지
    • /
    • 제52권3호
    • /
    • pp.232-240
    • /
    • 2019
  • Approximately 80% of the world's sea cucumbers Apostichopus japonicas are processed into dried sea cucumbers. The hot air-drying method is currently used in industry, but it has many problems, such as a short drying time, severe browning, high nutrition loss, and low recovery. In this study, the moisture absorption rate, dry recovery rate, and lipid nutrient composition of sea cucumber dried by heat pump decompression and with a hybrid dryer were investigated. The moisture absorption rates for hybrid-dried sea cucumbers at 24, 48, 72, 96, and 120 h were 241.3%, 427.7%, 652.0%, 721.0%, and 742.2%, respectively. The moisture absorption rates for hot air-dried sea cucumbers were 155.8%, 240.0%, 390.3%, 655.5%, and 667.4%, respectively. Thus, moisture absorption was faster and greater with hybrid drying than with hot air drying. The dry recovery rate at 24 h was greater for hybrid-dried sea cucumber (70.7%) than for hot air-dried sea cucumber (59.8%). Saturated fatty acid contents of the hybrid- and hot air-dried sea cucumbers were 30.0% and 37.5%, respectively. Moreover, greater ${\Sigma}n-3$ polyunsaturated fatty acid content was found in hybrid-dried sea cucumber (15.8%) than in hot air-dried sea cucumber (11.7%).

흡수식 냉온수기의 부분부하에 따른 냉각수 변유량시 성능특성에 관한 연구 (A Study on the Performance Characteristics of an Absorption Chiller for Variable Cooling Water Flow Rate at Partial Load Conditions)

  • 박찬우;조현철;강용태
    • 설비공학논문집
    • /
    • 제16권1호
    • /
    • pp.26-33
    • /
    • 2004
  • In general, an absorption chiller or heat pump is operated under the constant cooling water flow rate condition even though the system works with a partial load. The objective of this paper is to study the effect of the cooling water flow rates and the temperature of cooling water on the system performance to find the energy saving methode for the partial load operation of the double effect $H_2O$/LiBr absorption chiller. It is found that the performance of the system is sensitive to the temperature of cooling water than the cooling water flow rate, so the decrease of the performance due to reducing the cooling water flow rate can be overcome with the reduction of the cooling water temperature by 1$^{\circ}C$. The flow rate of the cooling water flow rate ranges from 50% to 100% of the flow rate at normal conditions with a partial load. It is also found that the operation cost of the cooling water pump and the cooling tower can be reduced by 23%.