• Title/Summary/Keyword: 7th-tuned passive filter

Search Result 10, Processing Time 0.025 seconds

A Study on Tuning Factor(δ) and Quality Factor(Q) Values in Design of Single-Tuned Passive Harmonic Filters (단일동조 수동고조파필터 설계시의 동조계수(δ) 및 양호도(Q)값 연구)

  • Cho, Young-Sik;Cha, Han-Ju
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.1
    • /
    • pp.64-70
    • /
    • 2010
  • This paper presents how to decide on tuning factor(${\delta}$) and quality factor(Q) values in design of single-tuned passive harmonic filters. Tuning factor(${\delta}$) and quality factor(Q) values have to consider before decision on circuit parameters of passive filters. A Study on these two value has not been scarcely performed and only experienced values has been used in passive harmonic filter design by far. As a experienced value, in cases of 5th and 7th filter, tuning factor(${\delta}$) is about 0.94 and 0.96 respectively and quality factor(Q) is, in all cases of, 50. If Single-tuned passive harmonic filter will be off-tuned, performance of filter will be decreased steeply and occur to parallel resonance between system reactance and filter capacitance. Therefore During the operation, In order not to off-tuning, Filter must be tuned at former order than actual tuning order. This is the same that total impedance of filter must have a reactive impedance. In this paper, Tuning factor(${\delta}$) is decided via example of real system and using the bode-plot and then performance of filters confirmed by filter current absorbtion rate. And Quality factor(Q) decided using the bode plot in example system and then performance of filters confirmed by filter current absorbtion rate also, which makes a calculated filter parameters to satisfy IEEE-519 distortion limits. Finally, Performance of the designed passive harmonic filter using the tuning factor(${\delta}$) and quality factor(Q) values, decided in this paper is verified by experiment and shows that 5th, 7th, 9th, 11th and 13th current harmonic distortions are decreased within IEEE-519 distortion limits, respectively.

A New Low Cost Hybrid Power Filter for Thyristor-Controlled Rectifier Load (싸이리스터 정류부하를 위한 새로운 저원가 복합형 전력필터)

  • 한성룡;김수근;석원엽;조정구;송의호;전희종
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.1
    • /
    • pp.24-29
    • /
    • 2004
  • A new low cost hybrid active filter for thyristor-controlled rectifier load is presented to overcome the high cost problem of the active or the other hybrid active filters. The proposed hybrid active filter which consists of tuned (5th and 7th harmonics) LC passive filters, power factor improvement(PFI) capacitor bank, and active filter compensates power factor as well as harmonic currents. Since most of harmonic currents are filtered by the passive filter and most of reactive power is compensated by the PFI capacitor bank, the power rating of active filter can be minimized, resulting in cost minimization of the proposed hybrid active filter. A 300kVA hybrid active filter system is implemented and tested using 1MVA thyristor rectifier load to verify the operation and performance.

A Study on the Series Active Power Filter for Harmonic Reduction and Unbalanced Source Voltage Compensation (전류 고조파와 불평형 전원 전압 보상을 위한 직렬형 능동전력필터에 관한 연구)

  • Oh, Jae-Hoon;Han, Yoon-Seok;Kim, Young-Seok;Won, Chung-Yuen;Choi, Se-Wan
    • Proceedings of the KIEE Conference
    • /
    • 2001.04a
    • /
    • pp.191-194
    • /
    • 2001
  • In this paper, we propose a series active power filter control method to compensate current harmonics and unbalanced source voltage. The system is composed of series active power filter and shunt passive filer that are tuned 5th and 7th harmonics. In this conventional system, series active power filter complements drawbacks of the shunt passive filter, namely improves harmonic compensation characteristics, and compensates unbalanced source voltage. In the proposed algorithm, compensation voltage for harmonic reduction is calculated by performance function, and compensation voltage for unbalanced source voltage is calculated in based on a synchronous reference frame. So, ultimate compensation voltage is sum of those two compensation voltages. By computer simulation, we verify the excellency of proposed method.

  • PDF

A Study of Series Active Power Filter Compensating Unbalanced Source Voltage in 3phase-3wire system (불평형 전원전압을 보상하는 3상3선식 직렬형 능동전력필터에 관한 연구)

  • Oh, Jae-Hoon;Kim, Young-Seok;Han, Yoon-Seok;Won, Chung-Yuen;Chol, Se-Wan
    • Proceedings of the KIPE Conference
    • /
    • 2001.07a
    • /
    • pp.319-322
    • /
    • 2001
  • In this paper, a 3phase-3wire series active power filter compensating current harmonics and unbalanced source voltages is presented. The system is composed of series active power filter and shunt passive filters that are tuned 5th and 7th harmonics. In this system, series active power filter improves harmonic compensation characteristics of the shunt passive filters and compensates the unbalanced source voltages. In the proposed algorithm, compensation voltage for harmonic reduction is calculated by a performance function, and compensation voltage for the unbalanced source voltage is calculated in based on the synchronous reference frame. Some results obtained from the experimental model using the proposed method are presented to demonstrate and confirm its validity.

  • PDF

An Input Current Waveshaping AC-DC Converter for Rectifier Loads

  • Singh, Bhim;Garg, Vipin;Bhuvaneswari, G.
    • Journal of Power Electronics
    • /
    • v.8 no.1
    • /
    • pp.1-9
    • /
    • 2008
  • This paper presents the design and analysis of a new input AC current wave shaping AC-DC converter for cost effective harmonic mitigation under varying loads. The proposed converter consists of a delta-polygon connected autotransformer based twelve-pulse AC-DC converter and a small rating passive shunt filter tuned at $11^{th}$ harmonic frequency. The proposed AC-DC converter eliminates the most dominant $5^{th},\;7^{th}$ and $11^{th}$ harmonics and reduces higher order harmonics; thereby, resulting in an improved power quality at AC mains. Moreover, the design of the autotransformer is modified to make it suitable for retrofit applications, where presently a 6-pulse diode bridge rectifier is used. To validate the proposed approach, various power quality indices are presented under varying loads. Experimental results obtained on the developed converter are given to validate the model and design of the proposed converter.

Three-Phase Z-Source Hybrid Active Power Filter System (3상 Z-소스 하이브리드 능동전력필터 시스템)

  • Lim, Young-Cheol;Kim, Jae-Hyun;Jung, Young-Gook
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.15 no.1
    • /
    • pp.75-85
    • /
    • 2010
  • In this paper, a Z-source hybrid active power filter is proposed to compensate the harmonics and reactive power in power distribution system. The proposed system is composed of a 7th harmonics-tuned passive filter and an active power filter with a Z-source inverter topology, while voltage source PWM inverter or current source PWM inverter are applied as the power converter topology of conventional active power filters. The Z-source impedance network along with shoot through capability would ensure a constant DC voltage across the DC link. A polymer electrolyte membrane fuel cell is employed as an compensation DC energy source of the proposed system and its equivalent R-L-C circuit is modeled for simulation. As the compensation and control algorithm of the proposed system, the current synchronous detection algorithm is applied. The simulation analysis by PSIM is performed under the three-phase 220V/60Hz voltage source and 25A nonlinear diode loads. The effectiveness of the proposed the system is verified in the steady and transient states.

Versatile Shunt Hybrid Power Filter to Simultaneously Compensate Harmonic Currents and Reactive Power

  • Trinh, Quoc-Nam;Lee, Hong-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1311-1318
    • /
    • 2015
  • This paper introduces a novel topology and an effective control strategy for a shunt hybrid power filter (SHPF) to simultaneously compensate harmonic currents and reactive power. The proposed SHPF topology is composed of an LC passive filter tuned to the 7th harmonic frequency and a small-rated active filter connected in parallel with the inductor Lpf of the LC passive filter. Together with the SHPF topology, we also propose a control strategy, which consists of a proportional-integral (PI) controller for DC-link voltage regulation and a PI plus repetitive current controller, in order to compensate both the harmonic current and the reactive power without the need for additional hardware. Thanks to the effectiveness of the proposed control scheme, the supply current is sufficiently compensated to be sinusoidal and in-phase with the supply voltage, regardless of the distorted and phase lagging of the load current. The effectiveness of the proposed SHPF topology and control strategy is verified by simulated and experimental results.

A New Waveshaper for Harmonic Mitigation in Vector Controlled Induction Motor Drives

  • Singh, Bhim;Garg, Vipin;Bhuvaneshwari, G.
    • Journal of Electrical Engineering and Technology
    • /
    • v.3 no.2
    • /
    • pp.152-161
    • /
    • 2008
  • This paper deals with a new wave shaping technique for cost effective harmonic mitigation in ac-dc converter feeding Vector Controlled Induction Motor Drives(VCIMD's) for improving power quality at the point of common coupling(PCC). The proposed harmonic mitigator consists of a polygon connected autotransformer based twelve-pulse ac-dc converter and a small rating passive shunt filter tuned for $11^{th}$ harmonic frequency. This ac-dc converter eliminates the most dominant $5^{th},\;7^{th},\;and\;11^{th}$ harmonics and imposes the reduction of other higher order harmonics from the ac main current, thereby improving the power quality at ac mains. The design of autotransformer is carried out for the proposed ac-dc converter to make it suitable for retrofit applications, where presently a 6-pulse ac-dc converter is used. The effect of load variation on VCIMD is also studied to demonstrate the effectiveness of the proposed ac-dc converter in a wide operating range of the drive. Experimental results obtained on the developed laboratory prototype of the proposed harmonic mitigator are used to validate the model and design of the ac-dc converter.

A Study on Series Active Power Filter Compensating Unbalanced Source Voltage in 3phase-3wire system (불평형 전원전압을 보상하는 3상3선식 직렬형 능동전력필터에 관한 연구)

  • 오재훈;한윤석;김영석;원충연;최세완
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.6 no.5
    • /
    • pp.386-393
    • /
    • 2001
  • A series active power filter compensating current harmonics and unbalanced source voltages in a 3phase-3wire power system is presented. The system is composed of series active power filter and shunt passive filters that are tuned at 5th and 7th harmonics. The proposed series active power filter improves harmonic compensation characteristics of the shunt passive filters, reduces source side harmonic currents and compensates the unbalanced source voltages. In the proposed algorithm, compensation voltage for harmonic reduction is calculated by a performance function, and compensation voltage for the unbalanced source voltage is calculated based on the synchronous reference frame. Some results obtained from the experimental model using the proposed method are Presented to demonstrate and confirm its validity.

  • PDF

Harmonic Elimination and Reactive Power Compensation with a Novel Control Algorithm based Active Power Filter

  • Garanayak, Priyabrat;Panda, Gayadhar
    • Journal of Power Electronics
    • /
    • v.15 no.6
    • /
    • pp.1619-1627
    • /
    • 2015
  • This paper presents a power system harmonic elimination using the mixed adaptive linear neural network and variable step-size leaky least mean square (ADALINE-VSSLLMS) control algorithm based active power filter (APF). The weight vector of ADALINE along with the variable step-size parameter and leakage coefficient of the VSSLLMS algorithm are automatically adjusted to eliminate harmonics from the distorted load current. For all iteration, the VSSLLMS algorithm selects a new rate of convergence for searching and runs the computations. The adopted shunt-hybrid APF (SHAPF) consists of an APF and a series of 7th tuned passive filter connected to each phase. The performance of the proposed ADALINE-VSSLLMS control algorithm employed for SHAPF is analyzed through a simulation in a MATLAB/Simulink environment. Experimental results of a real-time prototype validate the efficacy of the proposed control algorithm.