• 제목/요약/키워드: 345kV Transmission Lines

검색결과 61건 처리시간 0.024초

국내 가공송전선로 절연설계기술의 발전 및 적용 (Progress and application on the insulation design of overhead transmission line in Korea)

  • 유철환;김경호;박순규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.416-418
    • /
    • 2000
  • Main power transmission network in Korea is consist of 154kV, 345kV transmission lines. Also 765kV transmission lines are on construction currently. There are some differences in the insulation design concept, methods and contents on 154kV, 345kV and 765kV overhead transmission lines respectively. In this paper, we described and summarized the applied insulation design concept, methods and features on each transmission lines.

  • PDF

765 kV 송전선로의 345 kV 운전에 따른 계통 해석 (The analysis result of temporary operation of 765 kV transmission line as 345 kV rating)

  • 우정욱;심응보;강연욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1647-1649
    • /
    • 1998
  • This paper describes the power frequency voltage and its countermeasure when a 765 kV transmission line is directly connected to a 345 kV line and operated at 345 kV voltage. The summary of this result is as follows : The western route of 765 kV transmission line doesn't need any countermeasure to reduce the power frequency voltage at the receiving end. The eastern route of 765 kV transmission needs 100 Mvar(3 phase) capacity of shunt reactor at the receiving end to reduce the power frequency voltage. The use of shunt reactors in the 765 kV transmission lines has unexpected problems, one of which is induction of high voltages on a de-energized circuit of two parallel lines. This paper examined the problem of resonance on two parallel transmission circuits in one routes.

  • PDF

초고압 송전선로의 자계크기 해석과 실측 비교 (Analysis and Comparision of Measured and Calculated Value on Magnetic Fields Strength under Transmission Lines)

  • 조성배;이은웅
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권7호
    • /
    • pp.832-838
    • /
    • 1999
  • Recently, there are growing concerns about power frequency electric and magnetic fields coming out from the high voltage transmission lines, because of the wide spread perception of their probable harmful effect on human body. In connection with this trend, this paper describes the electric and magnetic fields measurement result around 154 kV and 345 kV transmission lines, a comparison of measured EMF to calculated one and the correlations between transmission lines currents and measured magnetic fields. Daily maximum and minimum magnetic field quantities under the selected 154 kV and 345 kV transmission lines had been measured for 1 year of 1997 and the average value of magnetic field exposure under the lines were calculated and presented based on the measured data.

  • PDF

345kV 가공선로에서 진동발생 다발 소경간에 대한 진동저감 대책(II) (A study on measures against subspan oscillation by twin spacers in 345kV overhead transmission lines(II))

  • 이형권;한형주;박창기;최웅규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.200-202
    • /
    • 2008
  • The oscillation is very dangerous in bundled transmission lines, especially 345kV 4 bundle transmission lines are very weak for subspan oscillations. In some cases, subspan oscillations are continuously occurred in the same subspan. In order to develop the control method of the above subspan oscillation, this paper suggests a method of applying twin spacers to the subspans. We have carried out some tests to analyze the oscillation phenomena after installing twin spacers on 34sky real lines, and we got a good effect for controling subspan oscillations.

  • PDF

345kV 인천화력 송전선로 철탑도괴 원인분석 및 대책 (Analysis and Countermeasures of 345kV Incheon-TP Overhead Transmission Lines Collapse)

  • 민병욱;신태우;최진성;최한열;박재웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.323_324
    • /
    • 2009
  • 345kV Incheon Thermal Power Plant Transmission Line Collapse Analysis and Countermeasures. The Typhoon Galmaegi which had been formed in July 15, 2008 diminished into a tropical cyclone and cooled the air above the West Sea. The cooled air colliding with the warm inland air caused a strong whirlwind at some places in the west seaside; the whirlwind battered the 345kV Incheon Thermal Power Plant Transmission Line to be collapsed. The resistance against wind pressure, one of the key elements in transmission line engineering, is designed to endure the pressure corresponding to the maximum instantaneous wind speed. Before the above accident happened, no transmission line has ever been collapsed by a whirlwind. So this paper is aimed to analyze causes that collapsed 345kV Incheon Thermal Power Plant transmission line and to introduce countermeasures.

  • PDF

345 kV 송전선로의 오손지역용 아킹혼 설계 (Design of the arcing horns for the contaminated areas in 345 kV transmission line)

  • 조성배;강연욱;위화복
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2083-2085
    • /
    • 1999
  • The same sized arcing horns have been installed on 345 kV transmission lines. Then arcing horn gaps are different according to the insulator string set. We need to examine the problems about the gap differences. So, we investigated the installation status of acing horn in 345 kV T/L. Based on these results. Drawing and making of the arcing horns for the contaminated areas is studied.

  • PDF

345/154kV 초고압 송변전설비 주변에서의 자장의 측정과 분석 (Measurement and Analysis of Magnetic Field near 345/154kV UHV Overhead Transmission Lines and Substations)

  • 이정기;안창환;이복희;길경석;박동화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1813-1815
    • /
    • 1996
  • With the three dimensional magnetic field measuring system dealt with in this paper, accurate measurements and analyses of ELF magnetic fields in the vicinity of UHV overhead transmission lines and substations have been conducted. For the field measurements multiturn loop-type sensors have been developed with special consideration of taking lower frequency and spatial components without any distortion. So the measuring system has the frequency bandwidth of 8[Hz] to about 53[kHz] and the response sensitivity of $9.88[mV/{\mu}T]$ in average. A brief description of design rules of the measuring system and measurement procedures is given. The actual surrey near 154 and 345[kV] overhead transmission lines and power subststions was carried out and analyzed. It may be inferred from these results that the maximum magnetic field intensities under typical UHV overhead transmission lines do not exceed $20[{\mu}T]$ so that the field measurements satisfy sufficiently all limits or guidelines that various authorized international institutes recommend.

  • PDF

345kV 미금${\sim}$성동변전소간 장거리 지중송전선로 준공 (The first installation of 345kV long-length transmission line between Mikyum and Sungdong substation in Korea)

  • 김영;성정규;고창성;한기종
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1731-1733
    • /
    • 1997
  • The first 150lkV underground transmission line of Korea was installed between Danginri and Yongsan substation in 1974. Since then, the underground transmission lines of about 720 circuit-km had been installed up to 1995. As the national economy has been enlarged and the population of city has been rapidly increased, the demand of an electric power has been very increased. Therefore the first 345kV long-length transmission line of Korea was installed between Mikyum and Sungdong substation on Jan., 1997. This paper describes the design of the 345kV oil-filled cable and its accessories, the design of the system, the methods of installation, field tests, and the future trends of the underground transmission line in Korea.

  • PDF

345/154kV 초고압 송변전설비 주변에서의 전장의 측정과 분석 (Measurement and Analysis of Electric Field near 345/154kV UHV Overhead Transmission Lines and Substations)

  • 이정기;안창환;이복희;길경석;박동화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1861-1863
    • /
    • 1996
  • In this paper, measurements and analyses of ELF electric fields in the vicinity of UHV overhead transmission lines and substations have been conducted. Planar-type sensors have been developed with special consideration of picking up lower frequency and spatial components without any distortion. So finally the electric field measuring system has the frequency bandwidth of 7[Hz] to 2.7[MHz] and the response sensitivity of 0.094[mV/V/m]. A brief description of design rules of the measuring system and measurement procedures is introduced. The actual survey near 154 and 345[kV] overhead transmission lines and power subststions was carried out and analyzed. It may be inferred from these results that the electric field intensity exeeds 7[kV/m] only in very few cases particularly at the substations so that the field measurements meet almost limits or guidelines that various authorized international institutes recommend.

  • PDF

345kV 송전선로 철탑이 인근에 매설된 가스배관에 미치는 영향 (The Influence on GAS pipelines Buried in nearby Tower of 345kV Transmission Line)

  • 이현구;하태현;배정효;김대경
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 A
    • /
    • pp.349-351
    • /
    • 2001
  • Because of the continuous growth of energy consumption and also the tendency to site power lines and pipelines along the same route, the close proximity of power lines and buried metallic pipelines has become more and more frequent. Therefore there has been and still is a growing concern about possible hazards resulting from the influence of power lines on metallic pipelines. When a ground fault occurs in an electrical installation the current flowing through the earthing electrode produces a potential rise of the electrode and of the neighbouring soil with regard to a remote earth. This paper analyzes the effects of ground faults when the current will flow into the soil from the foot of 345kV transmission line tower.

  • PDF