• Title/Summary/Keyword: 흡수식 시스템

Search Result 177, Processing Time 0.03 seconds

Thermodynamic Analysis of a Double-Effect Absorption Heating System Using Water-LiBr-LiSCN Solution with Solar Evaporator Heating (증발기 열원으로 태양열을 이용하며 LiSCN+LiBr 수용액을 사용하는 흡수식 2중효용 난방시스템의 열역학적 해석)

  • Won, Seung-Ho
    • Journal of the Korean Solar Energy Society
    • /
    • v.25 no.3
    • /
    • pp.27-35
    • /
    • 2005
  • In this paper, a thermodynamic analysis was performed to provide design data for a double-effect absorption heating system with water-LiBr-LiSCN mixture which utilizes solar energy as evaporator heat source. In addition, a comparative study of the water-LiBr-LiSCN mixture against the water-LiBr pair was conducted by a computer simulation. The computer simulation is based on mass, material and heat balance equations for each part of the system. Coefficients of performance and flow ratios for effects of different operating temperatures are investigated. It is found that the heating COP is higher for the water-LiBr-LiSCN mixture than for the water-LiBr pair, and FR is lower for the former.

Thermodynamic Analysis of Double-effect Absorption Heat Pump System with New Working Pairs (작동매체에 따른 2중효용 흡수식 시스템의 성능해석)

  • Won, S.H.;Lee, Y.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.3 no.4
    • /
    • pp.250-255
    • /
    • 1991
  • Performance analysis of double-effect absorption heat pump system has been done to find improved working pairs (or mixture) by computer simulation. Based on the thermodynamic analysis, the coefficient of performance and mass flow ratio are investigated to compare three aqueous solutions [LiCl-water, LiSCN-LiBr-water, LiCl-$CaCl_2$-$Zn(NO_3)_2$-water] which was developed for only cooling, with conventional LiBr-water solution. It is found that the performances of the new aqueous solutions are better than that of LiBr-water solution not only in cooling systems, but also in heating systems. Theoretical thermodynamic performance data can be used in heat recovery systems by basic design data.

  • PDF

Analysis of Thermodynamic Design Data for Heating of Double - Effect Solar Absorption System using LiBr - water and Ethylene Glycol Mixture (에틸렌글리콜 혼합액을 사용하고, 태양열을 보조열원으로 하는 이중효용 흡수식 시스템의 난방 특성해석)

  • Won, S.H.
    • Journal of the Korean Solar Energy Society
    • /
    • v.22 no.4
    • /
    • pp.51-61
    • /
    • 2002
  • Analysis of thermodynamic design data of double effect solar absorption heat pump system for heating has been done to find the property of Libr-water + ethylene Glycol mixture for working fluid by computer simulation. Derived thermodynamic design data. enthalpy based coefficient of performance and flow ratio for possible combinations of operating temperature for water - LiBr and Ethylene Glycol mixture (H2O: CHO ratio 10:1 by mole) by computer simulation. The obtained results, COP and mass flow ratio of the water-lithium bromide-ethylene glycol system, are compared with data for the water-Libr pair solution.

Solar Absorption Cooling System applicable to Educational Facilities (교육시설에 적용 가능한 태양열 흡수식 냉각 시스템)

  • Youn, Sung-Min;Paek, In-Su;Han, Young-Tae;Nam, Hyo-Gab
    • Journal of the Korean Institute of Educational Facilities
    • /
    • v.18 no.3
    • /
    • pp.35-41
    • /
    • 2011
  • Performance of a small-capacity solar absorption cooling system was investigated experimentally. Ten sets of evacuative-tube solar-heat collectors and a 5 kW single-stage absorption cooler were combined to produce a hybrid cooling system. The performance of the cooling system was measured using a tim-coil unit installed in a small plastic storage. It was found from the test on a sunny day of May that when the temperature of the hot water supplied from the solar collectors to the generator of the absorption cooler reached $60^{\circ}C$, the absorption cooler started cooling and the cold water temperature measured from the fan-coil unit reached $18^{\circ}C$. The COP, which is defined as the ratio of the cooling power to the total electrical power input was higher than 1.0.

  • PDF

Dynamic Analysis of an Ammonia-Water Absorption Chiller (암모니아-물 흡수식 냉각기의 동적 해석)

  • Kim Byong Joo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.10
    • /
    • pp.990-998
    • /
    • 2004
  • Dynamic behavior of an ammonia-water absorption system was investigated numerically. Thermal-hydraulic model for a single-effect 3 RT chiller was developed by applying transient conservation equations of total mass, $NH_3$ mass, energy and momentum to each component. Transient variations of system properties and transport variables were analysed during start-up operation. Numerical analyses were performed to quantify the effects of bulk concentration and charging ratio on the system performance in terms of cooling capacity, coefficient of performance, and time constant of system. For an absorption chiller considered in the present study, optimum charging ratio and bulk concentration were to found to exist, which resulted in the maximum cooling capacity and COP. The time constant increased as the charging ratio increased, but decreased with the increase of bulk concentration.

Experimental Study on Optimization of Absorber Configuration in Compression/Absorption Heat Pump with NH3/H2O Mixture (NH3/H2O 혼합냉매를 사용한 압축/흡수식 히트펌프 시스템의 흡수기 최적화에 관한 실험적 연구)

  • Kim, Ji-Young;Kim, Min-Sung;Baik, Young-Jin;Park, Seong-Ryong;Chang, Ki-Chang;Ra, Ho-Sang;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.3
    • /
    • pp.229-235
    • /
    • 2011
  • This research aims todevelopa compression/absorption hybrid heat pump system using an $NH_3/H_2O$ as working fluid.The heatpump cycle is based on a combination of compression and absorption cycles. The cycle consists of two-stage compressors, absorbers, a desorber, a desuperheater, solution heat exchangers, a solution pump, a rectifier, and a liquid/vapor separator. The compression/absorption hybrid heat pump was designed to produce hot water above $90^{\circ}C$ using high-temperature glide during a two-phase heat transfer. Distinct characteristics of the nonlinear temperature profile should be considered to maximize the performance of the absorber. In this study, the performance of the absorber was investigated depending on the capacity, shape, and arrangementof the plate heat exchangers with regard tothe concentration and distribution at the inlet of the absorber.

An Economic Analysis of Ice Thermal Storage and Absorption Chiller-Heater Systems (빙축열 시스템과 흡수식 냉온수기 공조 방식의 경제성 분석)

  • Lim, Hyun-Woo;Kim, Young-Il;Kim, Kang-San;Kang, Yong-Tae
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.218-223
    • /
    • 2009
  • Cost related to building equipment accounts for about 85% of the life cycle cost of buildings. Therefore proper selection of air-conditioning system is important for reducing the overall cost of buildings. In this study, large capacity ice thermal storage and absorption chiller-heater for air-conditioning a building with a floor area of $9,900\;m^2$ are compared economically. For easy input and analysis, an Ms Excel VBA program has been developed. To consider all the factors of initial and operation costs effectively, an annual equal payment method is proposed. Under the assumptions made in this study, overall cost of an absorption chiller-heater is less than that of an ice thermal storage, but this is not absolute and different outcome may result if different assumptions are made. This study is useful for those who are interested in choosing an economical air-conditioning system for large-size buildings with simple calculations.

  • PDF

Comparison Between Two Solar Absorption Cooling System Using Single Effect and Single Effect/Double Lift Cycle (일중효용 사이클과 일중효용/2단승온 사이클을 이용한 태양열 흡수식 냉방시스템의 비교)

  • 정시영;이상수;조광운;백남춘
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.3
    • /
    • pp.267-276
    • /
    • 2000
  • A numerical study has been carried out to find out the optimal design condition of a solar absorption cooling system. The system was composed of solar collectors and an absorption chiller with LiBr/water The System performance with commercial single effect(SE) cycle and a new single effect/double lift(SE/DL) cycle utilizing low temperature hot water was calculated and compared. It was found that the required solar collector area grew exponentially as the overall heat loss coefficient of solar collectors increased. For instance, the required area for cooling capacity of 1 USRT was $17m^2$ if heat loss coefficient was 4 W/$m^2\;cdot\;K$. If heat loss coefficient was doubled($8\;W/m^2\;cdot\;$K), the required collector area was increased by 6 times($100m^2$) .It was also found that the SE-cycle as the heat loss coefficient of solar collectors increased. Generally, a SE/DL-cycle seems to be more advantageous than a SE-cycle if loss coefficient of solar collector is greater than 4 W/$m^2\;cdot\;K$.

  • PDF

20주년 맞은 SK텔레콤 신가치경영으로 초일류기업 선언 에너지 절감노력도 한 몫

  • 에너지절약전문기업협회
    • The Magazine for Energy Service Companies
    • /
    • s.30
    • /
    • pp.14-17
    • /
    • 2004
  • 시설경비 절감과 국가에너지 절약사업에 일조하기 위해 최근 5년 전부터 에너지절약프로그램을 적극적으로 시행하고 있는 SK텔레콤은 오는 12월에 준공할 예정인 대전 둔산지점 신사옥과 10월 준공예정인 을지로 신사옥 본사에 자사에서는 최초로 ESCO사업을 활용한 에너지 절약설비를 설치했다. 대전 둔산 지점은 ESCO자금 7억2천5백만원으로 빙축열냉방시스템을 설치하고 본사에는 29억8천6백만원을 투입해 흡수식 냉동기, 빙축열시스템을 설치한 것. 이 설비로 인해 각각 연간 약 1억원과 4억원의 에너지절감효과를 기대하고 있다. 부분축열방식을 도입한 대전 둔산지점을 찾았다.

  • PDF