• Title/Summary/Keyword: 휜-관

Search Result 74, Processing Time 0.02 seconds

A Study on Beat Transfer Characteristics in the Air Side of Large-scaled Heat Exchanger (확대모형 열교환기를 이용한 공기측 열전달 성능에 관한 연구)

  • Byun Ju-Suk;Lee Jinho;Hong Man-Gi;Jeon Chang-Duk
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.29 no.9 s.240
    • /
    • pp.1032-1041
    • /
    • 2005
  • This study is performed to investigate the heat transfer characteristics of heat exchanger according to the arrangement of fins as well as fin configuration by using the four times enlarged model. Friction factor, Colburn j factor and goodness factors are compared to each other to estimate performance of each case for 4 different kinds of fins, which are plain, single side slit, double side slit and louver fin. Results show that heat transfer would be altered by fin arrangement and that friction loss is more affected by fin configurations than by the fin arrangements. In particular, heat transfer depends more on the shape of front row than that of rear row. The heat transfer rate of combined fin arrangement increases a lot more under the same pressure drop than that of conventional fin arrangement. This indicates that the heat exchanger of higher efficiency would be designed by the proper combination of fins, of different shapes.

Flow and heat transfer analysis for the performance improvement of cross-flow fin-tube heat exchangers (에어컨 실외기용 휜-관 직교형 열교환기의 열, 유동 해석 및 휜 성능 개선을 위한 연구)

  • An C. S.;Choi D. H.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2004.03a
    • /
    • pp.183-189
    • /
    • 2004
  • The flow and the heat transfer about the cross-flow fin-tube heat exchanger in an out-door unit of a heat pump system has been numerically Investigated. Using the general purpose analysis code, FLUENT, the Navier-Stokes equations and the energy equation are solved for the three dimensional computation domain that encompasses multiple rows of the fin-tube. The temperature on the fin and tube surface is assumed constant but compensated later through the fin efficiency when predicting the heat-transfer rate. The contact resistance is also taken into consideration. The flow and temperature fields for a wide range of inlet velocity and fin-tube arrangements are examined and the results are presented in the paper. The details of the flow are very well captured and the heat transfer rate for a range of inlet velocity is in excellent agreement with the measured data. The flow solution provides the effective permeability and the inertial resistance factor of the heat exchanger if the exchanger were to be approximated by the porous medium. This information is essential in carrying out the global flow field calculation which, in turn, provides the inlet velocity lot the microscopic temperature-field calculation of the heat exchanger unit.

  • PDF

A Numerical Analysis of Convective Heat Transfer in Air Flow Channels of a Plate Fin-tube Matrix for Heat Pipe Heat Sinks (히트파이프 히트싱크에서 평판 휜-관으로 구성된 공기유동 냉각채널의 대류 열전달 특성에 관한 수치해석)

  • Kim Sung-Hoon;Shin Hyun-Myung;Kim Chul-Ju
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.8
    • /
    • pp.862-869
    • /
    • 2005
  • A study on convective cooling characteristics has been done in the channels with heat pipes and associated Plane fins Analysis with FLUENT V5.0 lies its Purpose on the possible enhancement of heat transfer capability between an existing three in-line arrayed heatpipes and an extending four in-line arrayed heatpipes with increasing channel width. Numerical analysis is limited to the laminar flow in an isolated flow channel by employing cyclic boundary conditions for calculation purposes. Friction factors for three and four in-line arrayed heatpipes are compared with experimental results. In addition, temperature behavior at the plate fin for the three in-line arrayed heatpipes is compared with experiment. Friction factors and overall channel heat transfer coefficients (and/or Nusselt numbers) are presented as a function of Reynolds number. An increase of number of heatpipes and channel width reults in a decrease of the friction factor and doesn't not result in an increase of heat transfer performance. However. considering the 25$\%$ increase of heat load accompanies with maximum 8$^{\circ}C$ rise of average temperature of heat pipes, the four in-line array with the increase of channel width of heat pipe heat sink can be considered appropriate.

Characteristic of air-side sensible heat transfer and pressure drop on the corrugate fin tube heat exchangers (Corrugate 휜-관 현열 열교환기의 구조에 따른 공기측 열전달 및 압력손실 특성)

  • Ryu, Joon-Il;Jeon, Chang-Duk;Lee, Jin-Ho;Nam, Leem-Woo
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.216-221
    • /
    • 2007
  • An experiment was carried out to investigate the effect of a coolant circuit arrangement on the heat transfer and air pressure drop of a fin-tube sensible heat exchanger with the corrugated fin surface. The air inlet temperature was set to $23^{\circ}C$,the relative humidity to 50% and the air inlet flow rate to 20, 22, $25m^3/min$, respectively. while the coolant temperature was set to $7^{\circ}C$, and the coolant mass flow rate to 10, 16, 22kg/min, respectively. Experiment showed that the exchanger having a diameter of 12.7mm with parallel circuit does better performance in sensible heat transfer and air pressure drop than those three of diameter of 12.7mm with a series circuit and that with diameter of 15.88mm with a parallel circuit.

  • PDF

Comparison of Condenser Characteristics using R134a and R22 under the Same Inlet Temperature Condition (동일한 유입온도조건에서 R134a와 R22 적용 응축기의 특성비교)

  • Kang, Shin-Hyung;Byun, Ju-Suk;Kim, Chang-Duk
    • Journal of Energy Engineering
    • /
    • v.15 no.3 s.47
    • /
    • pp.166-173
    • /
    • 2006
  • R134a is considered as an alternative refrigerant to R22 for air conditioners. An experimental investigation was made to study the characteristics of the heat transfer and pressure drop for R134a flowing in a fin-and-tube heat exchanger used for commercial air-conditioning units. Experiments were carried out under the conditions of inlet refrigerant temperature of $60^{\circ}C$ and refrigerant mass fluxes of $150,\;200,\;and\;250\;kg/m^{2}s$. The inlet air has dry bulb temperature or $35^{\circ}C$, relative humidity of 40% and air velocity varying from 0.68 to 1.6 m/s. Experiments show that air velocity decreased by 5.9% is needed for R134a than that of R22 while pressure drop for R134a was $18.1{\sim}20.4%$ higher than that of R22 for the degree of subcooling $5^{\circ}C$. The results are useful in designing more compact and effective condensers for various refrigeration and air conditioning systems using refrigerant R134a.

Experimental study of heat transfer and pressure drop characteristics for flow of water inside circular smooth and micro-fin tubes (평활관 및 미세휜관 내에서의 물을 이용한 열전달 및 압력강하 특성에 관한 실험)

  • Park, H.B.;You, S.M.;Youn, B.;Yoo, K.C.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.4
    • /
    • pp.454-461
    • /
    • 1997
  • Heat transfer and pressure drop for single phase flow of water in circular smooth and micro-fin tubes are measured. Copper tubes of 9.52 and 7mm outer diameter were used. The internal roughness in micro-fin tubes was formed by spiral grooves having $25^{\circ}$ helx angle, 0. 12mm fin height and 0.454mm pitch in 9.52mm tubes; $18^{\circ}$ helix angle, 0.15mm fin height and 0.322mm pitch in 7mm tubes. The measured friction factor and heat transfer coefficient are compared with relevant previous works, and the correlations for micro-fin tube are developed.

  • PDF

An Experimental Investigation on the Airside Performance of Fin-and-Tube Heat Exchangers Having Sinusoidal Wave Fins (사인 웨이브 휜-관 열교환기의 공기측 성능에 관한 실험연구)

  • Kim, Nae-Hyun;Cho, Jin-Pyo;Yoon, Baek
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.4
    • /
    • pp.355-367
    • /
    • 2004
  • The heat transfer and friction characteristics of the heat exchangers having sinusoidal wave fins were experimentally investigated. Twenty-nine samples having different waffle heights (1.5 mm and 2.0 m), fin pitches (1.3mm to 1.7mm) and tube rows (one to three) were tested. Focus was given to the effect of the waffle configuration (herringbone or sinusoidal) on the heat transfer and friction characteristics. Results show that the sinusoidal wave geometry provides higher heat transfer coefficients and friction factors than the herringbone wave geometry, and the difference increases as the number of row increases. The i/f ratios of the herringbone wave geometry, however, are larger than those of the sinusoidal wave geometry. Compared to the herringbone wave geometry, the sinusoidal wave geometry yielded a weak row effect, which suggests a superior heat transfer performance at the fully developed flow region. Possible explanation is provided considering the flow characteristics in wavy channels. Within the present geometric range, the effect of the waffle height on the heat transfer coefficient was not prominent. The effect of the fin pitch was also negligible. Existing correlations highly overpredicted both the heat transfer coefficients and friction factors. A new correlation was developed using the present data.

Performance Characteristics of Vehicle Air Conditioning System Using Internal Heat Exchanger with Inner Fin (휜 타입 내부열교환기 적용에 따른 차량용 냉방시스템 성능 특성)

  • Kim, Sung Chul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.14 no.1
    • /
    • pp.69-73
    • /
    • 2013
  • Internal heat exchanger (IHX) apparatus using the temperature difference between high and low pressure lines in vehicle air conditioning system is a good method to enhance the cooling performance. In this study, we designed various double-pipe internal heat exchangers which have inner fins between the internal pipe and external pipe. We also measured the performance characteristic (pressure drop, cooling capacity, compressor work and coefficient of performance (COP)) of the modified internal heat exchangers that had the change of the fin height and the inside shape of the internal pipe. This experimental results indicated that the liner and serration type internal heat exchanger was the best cooling performance. In addition, the air conditioning system with the liner and serration type internal heat exchanger showed the improved performances of about 6.4% and 9.2%, respectively, for the cooling capacity and COP.