• Title/Summary/Keyword: 피난 유도

Search Result 117, Processing Time 0.023 seconds

Analysis of Safety Management Operations of Fire Risk Factors in Small-Scale Construction Sites (소규모 건설현장 화재 위험요인 안전관리 운영실태 분석)

  • Moon, Pil-Jae;Kong, Ha-Sung
    • The Journal of the Convergence on Culture Technology
    • /
    • v.8 no.6
    • /
    • pp.775-785
    • /
    • 2022
  • By analyzing the operation status of fire safety management of small construction site workers, deriving problems, and suggesting improvement measures, this study was conducted to present practical basic data for their efficient use in the future, and the following conclusions were drawn. First, it was analyzed that small construction site workers are elderly in the age group of construction workers, have short construction skills, most of the jobs are working in the construction industry, and the employment type is non-regular workers. Second, the fire safety management improvement plan of small construction site workers is systematized, fire safety manager is deployed to manage fire risk, fire escape routes and emergency warning facilities are provided to inform all workers at the construction site. In addition, measures to reduce industrial accidents are needed through realistic evacuation training, fire VR training, and interesting educational programs.

Examination for Methodology of Design of Emergency Lightings by Using Space Syntax Theory (공간구문론을 이용한 지하공간 비상유도등의 효율적인 위치선정 방법론 검토)

  • Won, Seul-Ki;Kim, Young-Uk;Choi, An-Seop
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.10
    • /
    • pp.1-9
    • /
    • 2006
  • The emergency lighting plan for underground space should be done with consideration of characteristics of the space. In terms of utilizing the Depthmap program from the Space Syntax theory, it is possible to analyze space quantitatively. Integration and intelligibility are major induces of this theory and we can use them as emergency lighting design parameters. For this study, human behaviors and survivor's evacuation routes in fire emergencies are analyzed through literature review. Based on those results, this study suggests the methodology of emergency lighting plan in underground space.

A Study on Disaster Prevention Improved Performance by Utilizing Directional Speakers (지향성스피커를 활용한 방재성능 향상에 관한 연구)

  • Kang, Shinwook;Jeon, Gaehyun;Kim, Teahwan
    • Journal of the Society of Disaster Information
    • /
    • v.12 no.3
    • /
    • pp.235-241
    • /
    • 2016
  • Recently our country was entering a high-tech society with social and economic development. However, the individual's ability to respond to disasters is lowered by the increase in complexity society. Accurate situation assessment and disaster response by a margin of personal information that can identify when a disaster has been difficult. Until now, by leveraging Standard speaker was the emergency alert broadcast. However, it was difficult to have regular speakers reverberation, a distinct attenuation of sound by listening to the sound, etc. due to the reflection of sound. By using a directional speaker that is characteristic of the sound attenuation of sound is straight to solve this problem and obtain feedback on measures that can effectively provide the oocytes to a valid information on a disaster situation and the evacuation.

Research of Regional Disaster Prevention Evaluation(2): In the case of kangwon-do (지역방재력 평가에 관한 연구(2): 강원도를 중심으로)

  • Kim, Kyoung-Nam;Kwon, Gun-Ju;Baek, Min-Ho
    • Journal of the Korean Society of Hazard Mitigation
    • /
    • v.9 no.1
    • /
    • pp.81-89
    • /
    • 2009
  • Until now, Korea carried out disaster management under the perception that the central government or the local government bodies are totally responsible. However as the size of disasters become larger, the capacity of the public disaster management did not live up to the expectations. To analyze this issue, this research conducted interviews on disaster response readiness by "individual resident-residents cooperation-public/private collaboration" according to each preparedness-response-recovery stage, as resident representatives (Head of Ri, Head of Tong) as subjects. Based on the interviews, surveys were conducted to deduct the necessary factors needed for the general residents to exhibit disaster prevention capabilities. The surveys consist of 6 factors-risk perception, evacuation inductively, individual evacuation response, disaster prevention system, lookout & precaution, information communication.

Analysis of the Causes of Casualties of Jecheon Sports Center Fire - Focus on an Initial Response and Management - (제천 스포츠센터 화재의 다수 사상자 발생원인 분석 -초기대응과 관리적인 측면을 중심으로-)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.32 no.5
    • /
    • pp.57-66
    • /
    • 2018
  • A sports center fire in Jecheon that caused 29 deaths and 40 injuries was analyzed based on initial response and management in order to investigate the causes of the casualties. The aspects of initial response included delay of reporting 119, not being guided to the exit for the body scrubber on the $2^{nd}$ floor for escape, opening the fire doors of the exits on the $1^{st}$ floor and $3^{rd}$ floor, not closing the fire door of the main stairs on the $3^{rd}$ floor, and not doing an emergency broadcast. The management aspects included closing the alarm valve of the sprinkler system on the $1^{st}$ floor, starting-stop of the fire pump controller, neglecting leakage of water and electricity between the false ceiling and ceiling in the parking lot, hiding the exit light in the ladies bathroom lounge on the $2^{nd}$ floor and piling up things in the exit, neglecting the button of an automatic door on the $2^{nd}$ floor, conventional fire safety management, insufficient inspection of fire equipment, and not working fire shutters and smoke exhaust windows.

Analysis of the Working Conditions of Fire Protection Systems in the Goyang Bus Terminal Building Fire (고양종합터미널화재 시 소방시설의 작동실태 분석)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.32 no.3
    • /
    • pp.95-107
    • /
    • 2018
  • This study analyzed the working conditions of the fire protection system in the Goyang Bus Terminal fire based on the fire investigation results. The results were as follows. First, extinguishing using an indoor fire hydrant was not attempted immediately after the fire burned the ceiling urethane foam. Second, a sprinkler alarm valve was turn off and did not work in the repair work space of the 1st basement. On the other hand, the sprinklers in the $2^{nd}$ basement, $1^{st}$ floor, $2^{nd}$ floor, and $3^{rd}$ floor worked and prevented the fire from moving to stories other than the $1^{st}$ basement. Third, although an exit light worked normally, it was not installed in the exit from the waiting room in the $2^{nd}$ floor to the bus stop. This resulted in many casualties. Fourth, although a fire receiver sent an electrical signal to the fan controller of the smoke control system, it was treated manually in the fan controller and the fan in the $2^{nd}$ floor did not work.

The present state of acoustic barrier-free in Japan (음향분야에서의 배리어 프리(barrier-free)의 현황 -일본 사례를 중심으로-)

  • Ryu, Jong-Gwan;Hiroshi, Sato;Kenji, Kurakata
    • Proceedings of the Korean Society for Emotion and Sensibility Conference
    • /
    • 2009.05a
    • /
    • pp.83-86
    • /
    • 2009
  • 음 배리어 프리(acoustic barrier-free)는 '음과 관련하여 장애인과 고령자의 생활에 불편을 주는 장벽을 제거하는 방안'이라고 정의 된다. 음 배리어프리는 건축, 도시 공간 및 교통 수단에서의 시각 또는 청각약자를 위한 안내, 유도, 경보 및 피난 시설에 대한 설계와 관련된다. 또한 보청기 등의 청각지원기기, 전자기기 등의 신호음 및 안내음과 음성 전송 장치와 같은 제품 디자인에도 음 배리어프리 개념은 요구된다. 본고에는 일본사례를 중심으로 음 배리어프리의 현황을 소개하고자 한다.

  • PDF

Evacuation System for Boarding an Elevator in Disaster (재난 발생 시 승강기 탑승인원을 위한 피난 유도 시스템)

  • Kim, Hyung-O;Kim, Junwoo;Park, Gooman;Cha, Jaesang
    • Journal of Satellite, Information and Communications
    • /
    • v.10 no.4
    • /
    • pp.28-31
    • /
    • 2015
  • The elevator is extreme important due to the large size of the building and public facilities. In particular, it occurs bottleneck phenomenon in a elevator in case of using a theater. So, in this paper, we suggests technology of removing the traffics of visitors' movement and increase the efficiency of the use of elevator. Configuration of the proposed technique is divided parts of the processing unit, the movement route of the mobile cover to help viewers to create a route to collect sensor and the sensed data to detect state and a waiting elevator. This was the design and verification of technical performance and implementation.

기능성과 경제성을 겸비한 세종지하차도 설계

  • Jo, Seong-Tae;Song, Guk-Hwan;Lee, Hui-Geon
    • 한국도로학회지:도로
    • /
    • v.10 no.2
    • /
    • pp.58-67
    • /
    • 2008
  • 교통량이 많은 도심지내 장대 지하차도 건설은 교통정체 해소에 기여를 하지만 초기 공사비가 많이 소요되는 단점이 있다. 또한, 화재등 유고시 이용자의 안전을 최우선으로 고려되어야 한다. 즉, 장대 지하차도 건설에 있어서 경제성과 안전성이 함께 만족할 수 있는 건설 방안이 필요하다. 세종지하차도는 이러한 문제점을 극복하고자 다음과 같이 지하차도의 환기방식 및 단면, 포장형식, 사고 예방 및 발생시를 대비한 종합방재시스템을 구축하였다. $\cdot$환기방식은 종류식 환기방식의 경제성과 횡류식 환기방식의 제연성능을 겸비할 수 있는 조합형 환기방식과 Duct Arch 단면을 적용하여 공사비 절감 및 운영시 유지관리비를 획기적으로 절감하였다. $\cdot$지하차도 포장형식은 화재시 내화성이 우수하며 유독가스 발생이 없는 HPC(고성능 콘크리트 포장) 포장을 적용하여 이용자의 안전을 최우선으로 고려하였고 일반 아스팔트 포장 및 배수성 아스팔트 포장에 비해 우수한 성능과 공용수명을 가진 공법을 적용함으로서 유지보수비용의 절감을 가능하게 하였다. 또한, 콘크리트포장의 단점인 소음발생을 최소화하기 위해 타이닝과 그루빙을 적용하였다. $\cdot$지하차도내 화재 등 유고시 신속한 대피가 가능하도록 피난 연락문 간격을 167m 간격으로 설치하고 비상탈출계단 6개소를 확보하였다. 또한 노약자 및 환자의 지하차도 외부로 대피를 돕기 위해 비상엘리베이터 3개소를 설치하는 등 사고발생 시 종합적으로 대처할 수 있는 시스템을 마련하여 적용하였다.

  • PDF

Development of M2M-based Underground Space (subway) Disaster Response Network and EL Display Integrated Board (M2M기반 지하공간(지하철) 재난대응 네트워크 및 EL 디스플레이 통합 보드 개발)

  • Park, Miyun;Kwon, Segon;Park, EunChurn;Lee, Jeonhun
    • Journal of the Society of Disaster Information
    • /
    • v.13 no.4
    • /
    • pp.422-441
    • /
    • 2017
  • Notifying emergency evacuation methods, accurate disaster location and evacuation route guidance can be very active alternatives to quickly minimize evacuation and casualties in disaster situation in the development of subway disaster prevention detection system that detects the disaster signs at the subway station early on the basis of Internet of things and leads passengers to evacuate. It's not easy to ensure perfect functioning of fire fighting facilities and equipments due to underground space structure with narrow exits. Therefore, we developed disaster provision EL Display integrated board that can induce the most efficient evacuation and the field experiment was conducted to examine the practical application in this study. Especially the applicability was verified by field application test because there is no case in which EL panels are used to evacuate disasters.