반밀폐공간 내 점화원의 위치가 수소-공기 혼합물 벤트폭연에 미치는 영향 (Effect of Ignition Location on a Vented Deflagration of Hydrogen-air Mixtures in Semi-confined Space)

  • 윤웅기;박병직;황인주;김우경;김양균
    • 한국수소및신에너지학회논문집
    • /
    • 제35권4호
    • /
    • pp.415-427
    • /
    • 2024
  • Explosion experiments were conducted using a rectangular concrete structure filled with hydrogen-air mixture (29.0%). In addition, the effect of ignition location on explosion was investigated. The impact on overpressure and flame was increased with the increasing distance of the ignition source from the vent. Importantly, depending on the ignition location the incident pressure was up to 24.4 times higher, while the reflected pressure was 8.7 times higher. Additionally, a maximum external overpressure of 30.01 kPa was measured at a distance of 2.4 m from the vent, predicting damage to humans at the injury level (1% fatality probability). Whereas, no significant damage would occur at a distance of 7.4 m or more from the vent.