• Title/Summary/Keyword: 철탑설계

Search Result 69, Processing Time 0.026 seconds

Safety Evaluation Method of Transmission Tower Subjected to Special Load Case According to Broken Wires (전력선 단선으로 인한 이상시 송전철탑의 안전성 평가방법)

  • Jin, Seok Won;Kim, Jong Min;Park, Jong Sup;Kang, Young Jong
    • Journal of Korean Society of Steel Construction
    • /
    • v.20 no.1
    • /
    • pp.131-149
    • /
    • 2008
  • A transmission tower was designed according to general and special load cases based on KEPCO Design Specifications. The special load case such as unbalanced load a cording to some broken wires has not been considered significantly. Therefore, this paper presents investigations on the stability and safety of main post members subjected to unbalanced load and design wind load. In this study, all cases totally considered. From the finite element analyses using LUSAS program, the stresses on the tower subjected to unbalanced load and design wind load were very high in comparison to the allowable stresses of the steel post member that was used. Some of the post member had higher stresses than the yield stress of the steel member. This paper also shows an example to improve the capacity of the post members using increased cross-section members. Based on the analyses results, when investigating the safety of the transmission tower, one must consider thenew design philosophy including ultimate strength of the member and reliability of the special loading cases.

Design Procedure on the Environmental Effects of Compact Tower (컴팩트 타워 전기 환경장해 발생량에 따른 설계기법)

  • Lee, Won-Kyo;Park, Chan-Hyeong;Lee, Ho-Kwon
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.557-558
    • /
    • 2011
  • 전력수요의 지속적 증가에 따라 송전설비의 추가 건설이 필요하지만 건설여건의 악화에 따라 보다 더 최적화된 송전철탑의 도입이 요구되고 있다. 이러한 문제를 해결하기 위한 방법으로 절연암을 채용한 철탑 설계 방법 및 기존 154kV 송전철탑을 활용하여 345kV 전압을 송전 할 수 있는 방안이 검토되고 있다. 송전전압이 높아지면 주변에 여러 가지 환경장해(코로나 소음, 통신선 유도 장해)를 유발하는데 이 장해 발생량은 철탑의 절연간격, 전력선의 종류 및 도체 구성방식에 따라 달라 된다. 따라서 기존 154kV 송전선로를 이용하여 345kV 송전 전압으로 격상을 위해서는 필수적으로 환경장해 유발 요인을 분석이 필요하고 환경장해를 최소화 할 수 있는 설계 기법이 요구된다. 이에 따라 본 논문에서는 기존 154kV 송전철탑을 이용하여 345kV 전압을 송전 할 때 환경장해 기준치를 만족하는 설계기법을 제시하고자 한다.

  • PDF

A design of 150 meters high steel tower (150m 철탑의 설계 ( 2 ))

  • 이재숙
    • 전기의세계
    • /
    • v.17 no.4
    • /
    • pp.28-31
    • /
    • 1968
  • 본 철탑설계이서 느끼는 점은, 장차 우리나라에서 건설할 345KV 송전용철탑도 국내에서 설계가능함은 물론, 조합부재방식을 활용하면 소요강재도 대부분국산품을 충당할 수 있을 것이다. 그리고, 국내기술의 향상을 위해서는 기술자에게 연구하고, 설계할 수 있는 시간적여유등 여건향상이 절대로 필요하다는 것이다. 국내에서 사용하는 기기는 우리나라 기술자가 국산자재를 이용하는 방침하에서 설계하고 설계가 끝난다음 이것을 국내에서 가공 또는 제작해야 많은 와화도 절약할 수 있고, 생산비도 절하할 수 있고 국내산업의 유기적발전을 기대할 수 있는 것이다.

  • PDF

A Study on the Ultimate Load of Electric Transmission Tower Considering Member Strength and Joint Strength (부재 내력과 접합부 내력을 고려한 송전강관철탑의 극한하중 도출에 관한 연구)

  • Kim, Woo-Bum;Jeon, Bum-Jun;Suh, Yong-Pyo
    • Journal of Korean Society of Steel Construction
    • /
    • v.22 no.5
    • /
    • pp.435-443
    • /
    • 2010
  • The current design practice of an electric transmission tower is based on the allowable stress design. Design strengths of the electric transmission tower's compression member are determined by buckling the strength of the member itself without considering joint strength. There is a possibility of a joint failure prior to the buckling of a member. Therefore, in this study, joint strength is calculated for various member forces, and the shape of joint and database of strength were established. These data was compared with the member strength obtained from previous research studies based on an equivalent nonlinear analysis technique. Finally, practical evaluation and design method to distinguish failure mode in an electric transmission tower member is proposed.

Development of Nonlinear Analysis Technic to Determine the Ultimate Load in Electric Transmission Tower (송전철탑의 극한하중 도출을 위한 비선형해석 기법)

  • Kim, Woo Bum;Choi, Byong Jeong;Ahn, Jin Kyu
    • Journal of Korean Society of Steel Construction
    • /
    • v.20 no.3
    • /
    • pp.389-398
    • /
    • 2008
  • The current design practice of electric transmission tower is based on the allowable stress design. However, it is difficult to find the cause behind a transmission tower's collapse by the above design approach as the collapse is caused by large secondary deformations based on and geometrical nonlinear behavior.influence factor for the nonlinear behavior is mainly residual stress, initial imperfection and end restraints on members. In this study, the necessity of the nonlinear analysis is examined through the comparison between elastic ana the nonlinear analysis, a new analytical method (equivalent nonlinear analysis technique) is proposed. To confirm the reliability of the proposed method, the computed ultimate load of the transmission tower using the method was compared with that of the nonlinear finite element analysis. Effects of parameters, such as compressive force and the slenderness ratio of the brace member on the main post member, were investigated. The effective member length according to influential parameters was formulated in table form for practical purposes.

Study on the compact design for steel tower (컴팩트형 철탑 설계에 관한 연구)

  • Lee, W.K.;Park, J.H.;Choi, I.H.;Lee, D.I.;Song, H.J.;Byun, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.711-712
    • /
    • 2007
  • 전력수요의 지속적 증가에 따라 송전설비의 추가적인 건설은 불가피하지만 토지구입비 증대 및 님비현상 등에 따른 토지구입난 등의 건설여건의 악화에 따라 보다 더 최적화 된 송전철탑의 도입이 요구되고 있다. 고분자소재 및 성형기술의 발달로 금속의 기계적 강도를 능가하는 절연성능을 가진 고분자 복합재료의 제작이 가능하게 되면서 큰 기계적 강도가 요구되는 철탑의 암(arm)을 고강도 FRP(Fiber glass Reinforced Plastics)를 적용한 암 절연물(braced post insulator)로 대체하려는 시도가 진행되고 있다. 본 논문은 기존의 철탑에서 도체를 지지하고 고전압이 인가된 도체의 공간적 절연 유지를 위하여 사용되던 무거운 금속 암과 애자련 대신 중심부분을 전기적 특성과 내환경성이 우수한 암 절연물을 사용한 154kV급 철탑 설계 방법과 컴팩트화 방법에 대해 제시하고자 한다.

  • PDF

765kV 심형기초 철탑의 정상 접지저항

  • 한국전력기술인협회
    • Electric Engineers Magazine
    • /
    • v.195 no.11
    • /
    • pp.30-34
    • /
    • 1998
  • 가공송전선의 접지는 주로 내뢰설계에 그 목적이 있지만 전력계통의 안정도, 전력계통의 고장검출과 철탑주변의 접촉전압 및 보폭전압에도 영향을 미치고 있는 것이 사실이다. 특히 전력계통에서 지락사고가 발생할 경우 지락전류가 송전철탑에 시설되어 있는 가공지선과 대지로 분류하는 정도에 따라 지락지점에서의 대지전위 상승이 크게 좌우된다.

  • PDF

Reliability-Based Wind-Resistant Design Criteria of Transmission Towers (신뢰성에 기초한 송전철탑의 내풍설계기준)

  • Cho, Hyo Nam;Shin, Jae Chul;Lee, Seung Jae
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.14 no.5
    • /
    • pp.1043-1053
    • /
    • 1994
  • This study suggests a practical but rational approach for the development of reliability-based LRFD criteria for transmission towers under wind and ice loadings in Korea. Based on available statistical data on wind speed and icing on transmission lines in Korea, the design wind and ice loads are obtained by Monte Carlo Simulations. In the study, the AFOSM reliability method and an Importance Sampling Technique are used for the element and system reliability evaluation of actual transmission towers. Based on the selected target reliabilities, a set of load and resistance factors for the LRFD criteria are calibrated using the AFOSM and the code optimization technique.

  • PDF