• Title/Summary/Keyword: 천장형 실내기

Search Result 6, Processing Time 0.024 seconds

실내공기질 향상을 위한 환경친화형 바닥공조시스템

  • 조동우
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.33 no.8
    • /
    • pp.32-40
    • /
    • 2004
  • 바닥공조시스템(underfloor air distribution system)은 건물 내에서 공기흐름을 바닥을 통해 조절하는 방식으로 전통적인 천장공조 방식을 대체할 새로운 시스템으로 평가받고 있다. 일반적으로 바닥 공조시스템은 공조기 등에서 송풍되는 공조공기가 억세스 플로어 하부의 바닥공간으로 전달되고 바닥급기구를 통해 실내로 송풍되는 구조를 이루고 있다. 바닥공조시스템의 이점은 전통적인 천장공조 방식에 비해 실내공기의 질(IAQ)이 향상되며 에너지의 절감이 가능하다는 점을 들 수 있다. (중략)

  • PDF

Optimal Flow Control of Ceiling Type Indoor Unit by PIV Measurements (PIV 유동 계측을 통한 천장형 실내기의 최적 제어 설계)

  • Sung, Jae-Yong;An, Kwang-Hyup;Lee, Gi-Seop;Choi, Ho-Seon;Lee, In-Seop
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.27 no.8
    • /
    • pp.1042-1050
    • /
    • 2003
  • A heating flow discharged from a 4-way ceiling type indoor unit has been investigated to determine the design parameters for the optimal flow control. The flow was measured by a PIV(particle image velocimetry) system and an experimental model of 1/10 scale with a transparent room was devised by satisfying the Archimedes number. This similarity is generally used in cases where the forced convection has similar magnitude of the natural convection. To optimize the heating flow, several vane angles and vane control algorithms of cross and right angle controls were considered. Regarding the vane angle, experimental results show that 30$^{\circ}$is an optimal angle to avoid re-suction flows without significant increase in flow noise. Temperature distribution measured in the environmental chamber ensures the increased thermal comfort when compared to the case, 60$^{\circ}$angle. At the optimal angle, applying open/close control gives rise to more uniform distribution of the heating flow than without control. Especially, the cross-control seems to be satisfactory for thermal comfort.

Design of Optimal Vane Control for Ceiling Type Indoor Unit by PIV measurements (천장형 실내기의 기류 가시화를 통한 최적 제어 설계)

  • Sung Jaeyong;An Kwang Hyup;Lee Gi Seop;Choi Ho Seon;Park Seung-Chul;Lee In-Seop
    • Proceedings of the KSME Conference
    • /
    • 2002.08a
    • /
    • pp.533-536
    • /
    • 2002
  • A heating flow discharged from a 4-way ceiling type indoor unit has been investigated using a PIV(particle image velocimetry) system For the PIV measurements, an experimental model of 1/10 scale with a transparent room was devised by satisfying the Archimedes number, which is generally used in case that the forced convection has the similar magnitude as the natural convection. To optimize the heating flow, several vane angles and vane control algorithms of cross and right angle controls were considered. Regarding the vane angle, the experimental results show that it should be less than $30^{\circ}$ to avoid re-suction flows which decrease the performance of the air-conditioner. At the vane angle of $30^{\circ}$, applying open/close control gives nae to more uniform distribution of the heating flow than without control. Especially, the cross-control seems to be satisfactory for the thermal comfort.

  • PDF

A Study on the Improvement of Indoor Thermal and Air Environment Made by Ceiling Cassette Type Cooling and Heating Unit in Classrooms (천장 카세트형 냉·난방기에 의해 형성되는 학교 교실의 실내 열환경 및 공기환경의 개선에 대한 연구)

  • Chang, Hyun-Jae;Lee, Ha-Young
    • Journal of the Korean Solar Energy Society
    • /
    • v.32 no.6
    • /
    • pp.141-148
    • /
    • 2012
  • Ceiling cassette type air conditioner has been a main stream as a heating/cooling system recently in school, Korea. In this study, indoor thermal environments made by ceiling cassette type air conditioner were investigated by CFD simulation. Concentrations of $CO_2$ were investigated by a field measurement. Indoor thermal environment with the velocity inlet angle of $45^{\circ}$ from the ceiling in heating season was very ununiform so that thermal area was divided into two parts those the one is window side which is cold, and the other is corridor side which is hot. In cooling season under the same condition, there are areas too hot or too cold. If the velocity inlet angle is set in $30^{\circ}$ from the ceiling, indoor thermal environments was improved greatly in cooling season and heating season, too. Also, from the field measurement of $CO_2$ concentrations, it was suggested to install ventilators with proper air volume considered the number of class students.

Implementation of portable WiFi extender using Raspberry Pi (라즈베리파이를 이용한 이동형 와이파이 확장기 구현)

  • Jung, Bokrae
    • Journal of Industrial Convergence
    • /
    • v.20 no.1
    • /
    • pp.63-68
    • /
    • 2022
  • In schools and corporate buildings, public WiFi Access Points are installed on the ceilings of hallways. In the case of an architectural structure in which a WiFi signal enters through a steel door made of a material with high signal attenuation, Internet connection is frequently cut off or fails when the door is closed. To solve this problem, our research implements an economical and portable WiFi extender using a Raspberry Pi and an auxiliary battery. Commercially available WiFi extenders have limitations in the location where the power plug is located, and WiFi extension using the WiFi hotspot function of an Android smartphone is possible only in some high-end models. However, because the proposed device can be installed at the position where the Wi-Fi reception signal is the best inside the door, the WiFi range can be extended while minimizing the possibility of damage to the original signal. Experimental results show that it is possible to eliminate the shadows of radio waves and to provide Internet services in the office when the door is closed, to the extent that web browsing and real-time video streaming for 720p are possible.

A method of wall absorption treatment for enhancing the speech intelligibility at a directional microphone array in a room (실내 공간 내 지향성 마이크 어레이에서의 음성 명료도 개선을 위한 벽면 흡음 처리 방법)

  • Ko, Byeong-Yun;Ih, Jeong-Guon;Cho, Wan-Ho
    • The Journal of the Acoustical Society of Korea
    • /
    • v.40 no.6
    • /
    • pp.649-659
    • /
    • 2021
  • Wall absorption treatment effectively reduces reverberation, but requires a large area for a live room and each wall absorption affects speech intelligibility differently. In this study, we try to find the most effective wall for the absorption treatment using the beamforming array microphone in terms of speech intelligibility. The absorption importance factor is defined by using the collision number of reflected sounds on each wall. It allows estimating how much the speech signal will be enhanced by the absorption treatment. A cuboid room with a size of 107 m3 and a reverberation time of 1.1 s is selected for the simulation. When a Helmholtz-type absorption is treated on the wall with the most significant importance factor, the modified clarity for 500 and 1k Hz is improved by 5.1 dB and 4.8 dB respectively, and the speech transmission index is enhanced by 0.06. The difference in results between the proposed method and commercial simulation code is less than a Just-Noticeable Difference (JND). The absorption treatment on the wall with the most significant importance factor shows improvement greater than the wall with the largest area, and its difference is larger than a JND value.