Design of Optimal Vane Control for Ceiling Type Indoor Unit by PIV measurements

천장형 실내기의 기류 가시화를 통한 최적 제어 설계

  • 성재용 (LG전자, 디지털어플라이언스(연)) ;
  • 안광엽 (LG전자, 디지털어플라이언스(연)) ;
  • 이기섭 (LG전자, 디지털어플라이언스(연)) ;
  • 최호선 (LG전자, 디지털어플라이언스(연)) ;
  • 박승철 (한국산업기술대학교, 기계공학과) ;
  • 이인섭 (LG전자, 디지털어플라이언스(연))
  • Published : 2002.08.01

Abstract

A heating flow discharged from a 4-way ceiling type indoor unit has been investigated using a PIV(particle image velocimetry) system For the PIV measurements, an experimental model of 1/10 scale with a transparent room was devised by satisfying the Archimedes number, which is generally used in case that the forced convection has the similar magnitude as the natural convection. To optimize the heating flow, several vane angles and vane control algorithms of cross and right angle controls were considered. Regarding the vane angle, the experimental results show that it should be less than $30^{\circ}$ to avoid re-suction flows which decrease the performance of the air-conditioner. At the vane angle of $30^{\circ}$, applying open/close control gives nae to more uniform distribution of the heating flow than without control. Especially, the cross-control seems to be satisfactory for the thermal comfort.