• 제목/요약/키워드: 제습로터

검색결과 29건 처리시간 0.022초

재생 면적비가 가정용 소형 제습로터의 성능에 미치는 영향에 관한 실험적 연구 (An Experimental Study of the Effect of Regeneration Area Ratio on the Performance of Small-Sized Dehumidification Rotor for Residential Usage)

  • 김내현
    • 설비공학논문집
    • /
    • 제27권5호
    • /
    • pp.277-282
    • /
    • 2015
  • During hot and humid weather, air-conditioners consume a large amount of electricity due to the large amount of latent heat. Simultaneous usage of a dehumidifier may reduce latent heat and reduce electricity consumption. In this study, dehumidification performance was measured for a small-sized dehumidification rotor made of inorganic fiber impregnated with metallic silicate within a constant temperature and humidity chamber. Regeneration to dehumidification depends on ratio, rotor speed, room temperature, regeneration temperature, room relative humidity and frontal velocity to the rotor. Results demonstrate an optimum area ratio (1/2), rotor speed (1.0 rpm), and regeneration temperature ($100^{\circ}C$) to achieve a dehumidification rate of 0.0581 kg/s. As the area ratio increases, the optimum rotation speed and the optimum regeneration temperature also increase. Above the optimum rotor speed, incomplete regeneration reduces dehumidification. Above the optimum regeneration temperature, increased temperature variation between regeneration and dehumidification reduces dehumidification. Dehumidification rate also increases with an increase of relative humidity, dehumidification temperature and flow velocity into the rotor.

제습냉방시스템에서 요소성능이 시스템성능에 미치는 영향 (Effects of Individual Components on the System Performance in a Desiccant Cooling System)

  • 장영수;이대영
    • 설비공학논문집
    • /
    • 제19권10호
    • /
    • pp.687-694
    • /
    • 2007
  • Cycle simulation is peformed for two types of the desiccant cooling system incorporating a regenerative evaporative cooler. The cooling capacity and COP are evaluated at various effectiveness values of the regenerative evaporative cooler, the desiccant rotor and the sensible heat exchanger. As either of the effectiveness of the regenerative evaporative cooler or the humidity effectiveness of the desiccant rotor increases, both the cooling capacity and COP increase, but the enthalpy leak ratio gives the opposite effect on the system performance. It is found that COP of cycle A mainly depends on the humidity effectiveness of the desiccant rotor, while for cycle B enthalpy leak ratio of desiccant rotor has the major impact on COP. The effect of the sensible heat exchanger on the cooling capacity is small about 1/10 compared with those of other components.

외기조건에 따른 제습냉방시스템의 성능 특성 (Performance Characteristics of the Desiccant Cooling System in Various Outdoor and Load Conditions)

  • 이대영;장영수
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.623-628
    • /
    • 2009
  • Desiccant based air conditioning system offers a promising alternative to conventional one using vapour compression refrigeration for energy saving and greenhouse gas reduction. It is a heat driven cycle which has high potential for the use of low grade heat source such as the waste heat from the cogeneration plant or the solar thermal energy. In this study, the cooling performance of a desiccant cooling system incorporating a regenerative evaporative cooler was characterized in various operation conditions through numerical simulation. The cooling capacity and COP were evaluated at various outdoor conditions, regeneration temperatures, and supply flow rates. Based on the performance characteristics, the optimal control scheme was discussed to minimize the cooling cost at part load condition.

  • PDF

재생 입구 직접증발냉각기 적용이 제습냉방시스템 성능에 미치는 영향 (Effects of performance analysis of a desiccant cooling system with a direct evaporative cooler in the regeneration process)

  • 다쉬울찌우타스;오명도
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.633-638
    • /
    • 2009
  • In this study the performance analysis and cooling capacity of desiccant cooling system incorporating regenerative cooler and direct evaporative cooler in the regeneration air inlet were investigated on the condition of low regeneration temperature and time rotation 180s and area ratio of regeneration to dehumidification section 0.7. The cooling capacity and COP are evaluated at various effectiveness values of the direct evaporative cooler or the regenerative evaporative cooler. As either of effectiveness of the regenerative and direct evaporative coolers of desiccant cooling system increases, both the cooling capacity and COP increase, but effectiveness value of regenerative cooler gives the opposite effect on the system performance. It is found that effectiveness of regenerative cooler less than 0.7 shows the optimum cooling capacity.

  • PDF

고분자 제습로터의 저온재생 성능시험 (Performance Test of Low Temperature Regeneration Polymeric Desiccant Rotor)

  • 이진교;이대영;오명도
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.629-632
    • /
    • 2009
  • The polymeric desiccant rotor is made from the super absorbent polymer by ion modification. The moisture sorption capacity of the super desiccant polymer(SDP) is 4 to 5 times larger than those of common desiccant meterials such as silica gel or zeolite. It is also known that SDP can be regenerated even at the relatively low temperature. To fabricate the desiccant rotor, firstly the SDP was laminated by coating the SDP on polyethylene sheet. Then corrugated and rolled up into a rotor. The diameter, the depth, the dimensions of the corrugated channel, etc. were pre-determined from numerical simulation on the heat and mass transfer in the desiccant rotor. The dehumidification performance was tested in a climate chamber. The relevant tests were carried out at the process air inlet temperature of $32^{\circ}C$, the regeneration air inlet temperature of $60^{\circ}C$ and the inlet dew-point temperature of both the process air and the regeneration air of $18.5^{\circ}C$, when the rotation period is long, the moisture sorption is not effective. In the desiccant rotor developed in this study, the optimum rotation period is found about 350s at the regeneration temperature of $60^{\circ}C$. It was found from further experiments that the optimum rotation tends to decreases as the regeneration temperature increases. Meanwhile, the outlet temperature of the process air deceases monotonically as the rotation period increases.

  • PDF

재생입구 직접증발냉각기 적용이 제습냉방시스템 성능에 미치는 영향 (Effects of Performance Analysis of a Desiccant Cooling System with a Direct Evaporative Cooler in the Inlet of Regeneration Process)

  • 다쉬 울찌우타스;성상철;오명도;이대영
    • 설비공학논문집
    • /
    • 제22권5호
    • /
    • pp.328-335
    • /
    • 2010
  • The purpose of this study is to make an analysis of influence on the cooling capacity and COP of a desiccant cooling system with a regenerative evaporative cooler when a direct evaporative cooler was applied to the inlet of regeneration process of this system. We used cycle simulation in order to analyze the performance of this system. From the cycle simulation, we knew that the optimal rotation time of desiccant rotor was between 160s and 220s and hardly ever affected cooling capacity of desiccant cooling system when this system was operated at the outdoor air condition of $35^{\circ}$ and 40% RH and low regeneration temperature of $60^{\circ}$. Also there was optimal area ratio of regeneration to dehumidification between 0.7 and 1.0. Our results showed that it had a small effect on the system’s cooling capacity to install direct evaporative cooler at the inlet of regeneration process.

지역난방에 연계된 하이브리드 제습냉방시스템의 주거환경에서의 성능 분석 (Characteristic Analysis of Hybrid Desiccant Cooling System for District Heating in Residential Environment)

  • 안준;김재율;강병하
    • 대한기계학회논문집B
    • /
    • 제38권7호
    • /
    • pp.571-579
    • /
    • 2014
  • 하절기 에너지 이용의 합리화를 위해서는 소형 열병합 발전의 설비이용률을 높일 수 있는 지역냉방의 보급이 확대되어야 한다. 지역냉방에는 흡수식 냉동기와 제습냉방기 있는데 상대적으로 낮은 열원을 사용할 수 있어 지역난방에 연계할 수 있는 제습냉방이 공동주택용으로 각광을 받고 있다. 본 논문에서는 고체제습제를 이용며 현열로터 대신에 히트펌프를 사용한 하이브리드 제습냉방 시스템의 주거환경에서의 성능 특성을 분석하였다. 실내공급공기, 실내리턴공기, 실외흡입공기, 재생열량, 소비전력을 측정하여 인터넷을 이용한 모니터링을 통하여 데이터를 분석하였다. 전체에너지는 외기온도가 증가할수록 감소하였고 냉방능력은 외기온도가 증가할수록 증가하고, 외기습도가 감소할수록 증가하는 경향을 보였다. 성능계수는 냉방능력과 유사한 경향을 보이는 것으로 분석되었다.

열회수 냉각 제습기의 이론적 해석 (Theoretical Analysis of a Recuperative Refrigeration Dehumidifier)

  • 김동선
    • 설비공학논문집
    • /
    • 제26권1호
    • /
    • pp.48-54
    • /
    • 2014
  • A refrigeration dehumidifier with a recuperative heat exchanger is theoretically analyzed. The recuperative heat exchanger is located between the two air streams from and to the dehumidifying coil, and reduces the sensible heat load in dehumidification process. A simple model is developed to predict performance of the dehumidifier. The model predicts that the recuperative heat exchanger is effective especially in the low humidity condition, where the sensible heat load is relatively large. It is predicted that, by adopting a recuperative heat exchanger, a maximum 30~110% increase in COP is possible for indoor air at $27^{\circ}C$, and 40~60% relative humidity.

하이브리드 제습냉방시스템의 성능평가 연구 (A Study on the Performance Evaluation of a Hybrid Desiccant Cooling System)

  • 황원백;김용찬;이대영
    • 설비공학논문집
    • /
    • 제24권2호
    • /
    • pp.121-128
    • /
    • 2012
  • Improvement in the energy efficiency has been studied of the desiccant cooling system by applying a vapor compression type heat pump to modify the system into a hybrid system. The cycle simulation was performed and the results were compared between a reference desiccant cooling system composed of a desiccant rotor, a sensible rotor and a regenerative evaporative cooler, and a hybrid desiccant cooling system with the sensible rotor being replaced by a heat pump. Though the electric consumption increases as much as the compressor power consumption, the total cooling capacity increases and the thermal energy input decreases by the addition of the heat pump. Therefore, the total energy efficiency can be improved if the increase in the electric consumption can be compensated with the increase in the cooling capacity and the decrease in the thermal energy input. The results showed that the total energy efficiency is optimized at a certain heat pump capacity. When the heat from the CHP plant is used for the thermal energy input, the energy consumption of the hybrid system is reduced by 20~30% compared with the reference system when the heat pump shares 30~40% of the total cooling capacity.