• Title/Summary/Keyword: 이중 슬립마찰면

Search Result 1, Processing Time 0.015 seconds

Seismic Performance Evaluation of Seismic Isolation Device with Double Slip Friction Surface (이중 슬립마찰면을 이용한 면진장치의 면진성능평가)

  • Son, Su-Won;Kwon, Jeong-Ho;Kim, Jung-Gon;Jung, Yong-Gyu;Hwang, Eun-Dong
    • Journal of the Society of Disaster Information
    • /
    • v.16 no.4
    • /
    • pp.712-722
    • /
    • 2020
  • Purpose: The damage from earthquakes with a magnitude of 5.0 or greater Korea has increased in South Korea. When a earthquake occurs, internal facilities and electric equipment besides urban structures will be damaged. Thus, in this paper, an earthquake-induced seismic isolation device with double slip fiction surfaces which can reduce the damage of electric power equipment such as distribution panel and then the seismic performance was evaluated. Method: To evaluate the seismic performance shaking table test was performed, a seismic performance comparison was performed according to the presence or absence of a seismic isolation device. The attenuation effect of the seismic isolation device are analyzed by comparing response acceleration and displacement for different frequencies and acceleration levels. Result: As a result of the test, the acceleration amplification was up to 42% less than when the seismic isolation device was installed in comparison to the other case without the seismic device. This is believed that the amplification energy has reduced because the displacement between the double slip friction surfaces of the seismic device play a role in dissipating the seismic energy. Conclusion: The seismic device with double slip friction surfaces has a greater earthquake attenuation effect in strong earthquakes than in weak ones, so the greater the frequency, the better the earthquake attenuation effect. Therefore, it is judged that earthquake energy can be decreased by applying to electric equipment such as distribution panels.