Browse > Article
http://dx.doi.org/10.15683/kosdi.2020.12.31.712

Seismic Performance Evaluation of Seismic Isolation Device with Double Slip Friction Surface  

Son, Su-Won (Seismic Simulation Test Center, Pusan National University)
Kwon, Jeong-Ho (Korea Society of Disaster Information)
Kim, Jung-Gon (Disaster Management Research Center)
Jung, Yong-Gyu (JKRST Co. Ltd.)
Hwang, Eun-Dong (JKRST Co. Ltd.)
Publication Information
Journal of the Society of Disaster Information / v.16, no.4, 2020 , pp. 712-722 More about this Journal
Abstract
Purpose: The damage from earthquakes with a magnitude of 5.0 or greater Korea has increased in South Korea. When a earthquake occurs, internal facilities and electric equipment besides urban structures will be damaged. Thus, in this paper, an earthquake-induced seismic isolation device with double slip fiction surfaces which can reduce the damage of electric power equipment such as distribution panel and then the seismic performance was evaluated. Method: To evaluate the seismic performance shaking table test was performed, a seismic performance comparison was performed according to the presence or absence of a seismic isolation device. The attenuation effect of the seismic isolation device are analyzed by comparing response acceleration and displacement for different frequencies and acceleration levels. Result: As a result of the test, the acceleration amplification was up to 42% less than when the seismic isolation device was installed in comparison to the other case without the seismic device. This is believed that the amplification energy has reduced because the displacement between the double slip friction surfaces of the seismic device play a role in dissipating the seismic energy. Conclusion: The seismic device with double slip friction surfaces has a greater earthquake attenuation effect in strong earthquakes than in weak ones, so the greater the frequency, the better the earthquake attenuation effect. Therefore, it is judged that earthquake energy can be decreased by applying to electric equipment such as distribution panels.
Keywords
Double Slip Friction Surface; Seismic Isolation Device; Seismic Performance Evaluation; Shaking Table Test; Distribution Panel;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Kim, Y.-J., Huh, Y.-C., Kim, B.-H. (2000). "A study on the characteristics of friction pendulum isolation bearings." Proceedings of EESK Conference-Fall 2000, pp.407-414.
2 Korea Meteorological Administration (2019). 2019 Annual Report of Earthquakes.
3 Hwang, J.S., Joo, S.J., Kim, Y.S., Kurabayashi (2001). "Dynamic characteristics and isolation performance of isolation table system." Journal of the Earthquake Engineering Society of Korea, Vol. 5, No.4, pp. 67-74.
4 Jang, J.-B. Kim, J.-K., Hwang, K.-M., Ham, K.-W., Park, J.-W., Lee, C.-W. (2008). "Experimental study of friction pendulum system to improve the seismic capacity of transformer." Journal of the Earthquake Engineering Society of Korea, Vol. 12, No. 2, pp.1-8.   DOI
5 Kim, J.G. (2016). Performance Evaluation of Viscoelastic Dampers Using a Shake Table Experiment. Ph.D Thesis, Gyeongsang National University.
6 Son, S.W. (2018). Evaluation of Seismic Performance of Geotechnical Seismic Foundation Isolation System. Ph.D Thesis, Pusan National University.
7 Takahashi, Y., Onuki, M., Goda, Y., Haino, H., Tanaka, K., Koizumi, T., Sugiyama, H. (2016). "Development of sliding isolation system with multi-frictional plates and horizontal bidirectional behavior" Journal of Structural Engineering, Vol. 62A, pp. 374-383.