• Title/Summary/Keyword: 이온화식

Search Result 14, Processing Time 0.024 seconds

Knowledge State Analysis of Ionic Equation for Middle School Students (중학생들의 이온화식에 대한 지식상태분석)

  • Yoon, Heojeong;Lee, Yoonha;Kim, Youngshin
    • Journal of the Korean Chemical Society
    • /
    • v.59 no.6
    • /
    • pp.499-507
    • /
    • 2015
  • The purpose of this study is to investigate middle school students’ understanding of ionic equation. Two hundreds and nineteen middle school students were participated in the study. After six class hours of learning ‘electrolyte and ion’ unit, instrument was implemented to evaluate students’ understanding of ionic process and ability to write ionic equation. We analyzed the influence of characteristics of ionic compounds on correct answer rate. In addition, knowledge state of students required for writing ionic equation was analyzed. The results were as follows: First, ionic compounds tested were categorized into six groups. The correct answer rate was different depending on the characteristics of each group. Second, knowledge state required for writing ionic equation was structured. Based on results some suggestion were made to develope effective learning strategy for understanding ionic equation.

A Study on the Response Characteristics Depending on Service Life of Ionization Smoke Detector (이온화식연기감지기의 사용기간에 따른 응답특성 연구)

  • Baek, Won-Don;Kim, Shi-Kuk;Ok, Kyung-Jea;Lee, Chun-Ha;Jee, Seung-Wook
    • Fire Science and Engineering
    • /
    • v.22 no.4
    • /
    • pp.61-64
    • /
    • 2008
  • This paper studied on the response characteristics depending on service life of ionization smoke detector. The experimental samples used ionization smoke detectors (360 EA) for over 5 years which were influenced by environment set up with fire objects. The experimental method performed operate and non-operate test according to 'Type Approval and Technical Regulation of Detector (KOFEIS 0301)', for estimate the response characteristics of ionization smoke detector depending on service life. The results showed that their response characteristics were rapidly decreasing when the longer their using period. Accordingly, it is desirable that ionization smoke detector has to be changed for early fire detection when passed their service life.

A Study on Response Characteristics of ionization Smoke Detector Influenced by Air Stream (이온화식 연기감지기의 기류응답특성 연구)

  • 이복영;정길순;이병곤
    • Fire Science and Engineering
    • /
    • v.17 no.2
    • /
    • pp.6-9
    • /
    • 2003
  • Recently, forced ventilating air conditioning system has been widely used in modern buildings. However, It is obvious that this kind of system may affect on the response of fire detectors at real fire incidents, especially, on the ionization smoke detector, which is critically influenced by air stream. Therefore we studied to verify the response characteristics of air stream by ionization smoke detector for the design of facilities in practice. In this study, experiments were executed to examine the correlation between air velocity and the ionization detector's responses with var-ious air velocity and smoke densities in the simulated test room. As a result of experiments, ionization detector's operating time is in reverse proportion to air velocity. And the detector shows more sensitive reaction when the velocity of smoke stream increase over 60 cm/s. In addition, it was shown that ionization smoke detector is more sensitive to smoldering fires in paper than that in petro-chemicals.

LC/ESI/MS 와 기능성 화장품 관련 분석에의 응용

  • 이명희
    • Journal of the Society of Cosmetic Scientists of Korea
    • /
    • v.25 no.3
    • /
    • pp.23-46
    • /
    • 1999
  • LC/MS는 HPLC의 분리능과 질량분석기의 화합물의 확인 능력을 결합시킨 기기이다. 여기서 사용되는 이온화 방법은 GCJMS에서 사용되어지는 전자이온화법(electron ionization, EI)이나, 화학이온화법(chemical ionization, CI)은 부적당하기 때문에 최근 개발되어진 연성 이온화법의 대표적인 고속원자폭격식(Fast atom bombardment, FAB)이나 전기분무이온화식 (electrospray ionization, ESI) 등이 사용되고 있다. 이중 전기분무이온화법은 고속원자폭격법에서 사용되는 매트릭스를 사용하지 않기 때문에 매트릭스 이온의 부재로 인한 낮은 바탕 신호, 오래 지속되면서 안정된 초기 이온 전류, 샘플링의 용이성, HPLC와의 더 좋은 호환성 등의 장점을 제공한다. 이러한 전기분무이온화 방법은 극성이 매우 크거나 휘발성이 낮은 물질로 보통의 EI나 CI 이온화 방법으로 분석이 어려운 물질들을 분석할 수 있다. 또한 열에 불안정하거나 분자의 분자량이 다른 단백질 등의 분석도 가능하다. 이러한 LC/ESI/MS 방법을 이용하여 열에 불안정하고 극성이면서 분자량이 커서 GC/MS 펄의 분석이 어려운 기능성 화장품 원료로 주목받고 있고 생체에 존재하는 지질 성분으로 알려진 레시틴과 세라마이드의 분석이 가능함을 소개하고 분리와 동시에 그 분자량과 구조에 대한 정보를 빠르게 얻을 수 있음을 소개하였다.

  • PDF

Measurement of the Device Properties of a Ionization Smoke Detector to Improve Predictive Performance of the Fire Modeling (화재모델링 예측성능 개선을 위한 이온화식 연기감지기의 장치물성 측정)

  • Kim, Kyung-Hwa;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.27 no.4
    • /
    • pp.27-34
    • /
    • 2013
  • The high prediction performance of fire detector models is essentially needed to assure the reliability of fire and evacuation modeling in the process of PBD (Performance Based fire safety Design). The main objective of the present study is to measure input information in order to predict the accurate activation time of smoke detector into a Large Eddy Simulation (LES) fire model such as FDS (Fire Dynamics Simulator). To end this, FDE (Fire Detector Evaluator) which can measure the device properties of detector was developed, and the input information of Heskestad and Cleary's models was measured for a ionization smoke detector. In addition, the activation times of smoke detectors predicted using default values into FDS and measured values in the present study were systematically compared. As a result, the device properties of smoke detector examined in the present study showed a significant difference compared to the default values used into FDS, which resulted in the considerable difference of up to 15 minutes or more in terms of the activation time of smoke detector. The database (DB) on device properties of various smoke and heat detectors will be built to improve the reliability of PBD in future studies.

Ion Permeability, Dehydration and Relaxation Times of Hydrated Ions Through Membranes (반투막을 통한 수화된 이온의 투과속도 탈수화율 및 완화시간에 관한 연구)

  • Kim Mu Shik;Lee Hai Bang;Kim Sung Wan;Joseph D. Andrade
    • Journal of the Korean Chemical Society
    • /
    • v.20 no.6
    • /
    • pp.448-452
    • /
    • 1976
  • A simplified statistical mechanical method was developed for the calculation of the dehydration fraction, activation free energy of dehydration, and the relaxation times of hydrated ions. The model used includes the equilibrium constant between hydrated and dehydrated water, a water-ion interaction potential energy term, and a mixing factor for the species present. The agreement between theory and experiment is good. The pressure dependence of ion dehydration is also discussed.

  • PDF

A Study on the Reliability Test for Smoke Detection Chamber of Smoke Detector (연기감지기의 연기감지 챔버와 신뢰성 시험에 관한 연구)

  • Hong, Sung-Ho;Choi, Moon-Soo;Park, Sang-Tae;Baek, Dong-Hyun
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2012.04a
    • /
    • pp.389-392
    • /
    • 2012
  • 연기감지기는 이온전류의 변화량을 감지하는 이온화식 연기감지기와 발광부와 수광부로 이루어진 챔버내에 연기에 의한 광량의 변화를 감지하는 광전식 연기감지기로 구분된다. 국내에서는 광전식 연기감지기가 더 많이 사용되고 있는데 이러한 광전식 연기감지기의 챔버내에 이물질이 침입하게 되면 비화재보를 발생시키게 된다. 본 논문은 연기감지기의 연기감지 챔버에 대한 비화재보를 감소시키기 위한 신뢰성 시험에 대하여 논한 연구이다. 광전식 연기감지기의 신뢰성을 검증하는 방법으로는 먼지에 대한 신뢰성을 검증하는 가연물 종류에 따른 연기감지 신뢰성 시험이나 분진시험이 적합한 것으로 판단되며, 이러한 시험의 반복을 통하여 광전식 연기감지기의 신뢰성을 검증하는 것이 필요한 것으로 사료된다.

  • PDF

CCTV를 이용한 디지털 비디오 연기감지 방식

  • Lee, Sang-Hyeon
    • 방재와보험
    • /
    • s.107
    • /
    • pp.38-44
    • /
    • 2005
  • 기존 화재감지 기술이 점차적으로 발전되어 가고 있지만, 이러한 기존 기술과 다른 자동식 연기감지 방식이 혁신적으로 변화하고 있다. 이런한 혁신기술로 인하여 성장기의 화재를 감지하고 감지기에서 데이터를 분석하고, 화재와 관련된 데이터를 소방관계자에게 전송하는 방법이 계속 변화하고 있다. 기존 화재감지 방식의 예는 여러 가지 감열소자(열감지기), 광전식, 이온화식, 공기흡입형(연기감지기), 자외선.적외선(불꽃감지기)감지 방식이다. 감지기에서 데이터 분석의 형태로 연기농도를 표시하는 방법 등이 있다. 화재조건을 전송하는 방법은 특정한 구성요소(발신기, 감지기 등)의 위치(어드레스), LCD, CRT 그래픽 표시장치에서 많은 발전이 있었다. 이러한 혁신 기술은 화재경보 설비 판매시장, 설치방법, 기술기준의 변화에 많은 영향을 미치고 있다. 최근 개발된 디지털 비디오 연기감지 방식은 자동화재 감지 방식에 있어서 새롭고 급진적인 변화를 요구하고 있다.

  • PDF

A Study on the Reliability Test for Smoke Detection Chamber of Smoke Detector (화재감지기 신뢰성 검증방법에 관한 연구)

  • Hong, Sung-Ho;Choi, Moon-Soo;Park, Sang-Tae;Yoo, Song-Hyun;Yoo, Sang-Pil
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2013.04a
    • /
    • pp.150-151
    • /
    • 2013
  • 화재감지기는 연기감지기는 이온전류의 변화량을 감지하는 이온화식 연기감지기와 발광부와 수광부로 이루어진 챔버내에 연기에 의한 광량의 변화를 감지하는 광전식 연기감지기로 구분된다. 국내에서는 광전식 연기감지기가 더 많이 사용되고 있는데 이러한 광전식 연기감지기의 챔버내에 이물질이 침입하게 되면 비화재보를 발생시키게 된다. 본 논문은 연기감지기의 연기감지 챔버에 대한 비화재보를 감소시키기 위한 신뢰성 시험에 대하여 논한 연구이다. 본 연구에서는 광전식 연기감지기의 신뢰성을 검증하는 방법으로 UL 268 등에 규정되어 있는 먼지, 즉, 분진에 대한 신뢰성을 검증방법을 제시하였다. 먼지에 대한 신뢰성 검증을 보다 적절하게 하기 위하여 분진챔버로 분진을 반복적으로 폭로됨에 따른 감도성능 변화를 분석하는 방법이 필요할 것으로 사료된다.