A Flow Analysis of a Solution Pump for an Absorption Chiller (흡수식 냉동기용 용액펌프의 유동특성 해석)

  • Bae Wonyoung;Lee Kichoon;Hur Nahmkeon;Jeong Siyoung
    • Proceedings of the KSME Conference
    • /
    • 2002.08a
    • /
    • pp.569-572
    • /
    • 2002
  • In the present study, flow simulations of a solution pump fer an absorption chiller are performed. The results are compared to the experimental data. Since the cavitation is more likely to occur in a solution pump due to Its operation under vacuum condition, and the cavitation was not considered in the present computations, the computed and experimental results show large discrepancies. For more accurate performance prediction of a solution pump, a cavitation model is required in the flow simulation. Flows through an inducer are also studied to see the effect of design parameters on performance characteristics. It is shown from the results that, if not properly designed, recirculation legion may exist near the hub region of the Inducer, and the suction surface may experience higher pressure than the pressure surface of the inducer, which may deteriorate the performance.

  • PDF

Effect of S$iO_2$ Nano-sized particle on heat and mass transfer in ammonia-water absorption ($SiO_2$나노입자에 의한 암모니아-물 흡수용액의 열 및 물질전달 특성 연구)

  • 하종주;이찬호;김성현
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 2002.05a
    • /
    • pp.161-165
    • /
    • 2002
  • 인류가 직면한 환경 및 에너지 문제를 타개하기 위한 많은 연구 중 흡수식 열펌프는 환경친화적인 자연냉매를 사용하는 열구동 시스템으로 다시 주목을 받고 있다. 흡수식 열펌프의 구성요소 중 흡수기는 암모니아의 흡수에 의한 열 및 물질전달 현상이 동시에 일어나는 곳으로 암모니아-물 열펌프 시스템의 성능 향상을 위해 가장 중요한 부분이다.(중략)

  • PDF

Experimental Study on Compression/Absorption High-Temperature Hybrid Heat Pump with Natural Refrigerant Mixture (천연혼합냉매를 이용한 압축/흡수식 고온히트펌프의 실험적 연구)

  • Kim, Ji-Young;Park, Seong-Ryong;Baik, Young-Jin;Chang, Ki-Chang;Ra, Ho-Sang;Kim, Min-Sung;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.12
    • /
    • pp.1367-1373
    • /
    • 2011
  • This research concerns the development of a compression/absorption high-temperature hybrid heat pump that uses a natural refrigerant mixture. Heat pumps based on the compression/absorption cycle offer various advantages over conventional heat pumps based on the vapor compression cycle, such as large temperature glide, temperature lift, flexible operating range, and capacity control. In this study, a lab-scale prototype hybrid heat pump was constructed with a two-stage compressor, absorber, desorber, desuperheater, solution heat exchanger, solution pump, liquid/vapor separator, and rectifier as the main components. The hybrid heat pump system operated at 10-kW-class heating capacity producing hot water whose temperature was more than $90^{\circ}C$ when the heat source and sink temperatures were $50^{\circ}C$. Experiments with various $NH_3/H_2O$ mass fractions and compressor/pump circulation ratios were performed on the system. From the study, the system performance was optimized at a specific $NH_3$ concentration.

Experimental Study on Optimization of Absorber Configuration in Compression/Absorption Heat Pump with NH3/H2O Mixture (NH3/H2O 혼합냉매를 사용한 압축/흡수식 히트펌프 시스템의 흡수기 최적화에 관한 실험적 연구)

  • Kim, Ji-Young;Kim, Min-Sung;Baik, Young-Jin;Park, Seong-Ryong;Chang, Ki-Chang;Ra, Ho-Sang;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.3
    • /
    • pp.229-235
    • /
    • 2011
  • This research aims todevelopa compression/absorption hybrid heat pump system using an $NH_3/H_2O$ as working fluid.The heatpump cycle is based on a combination of compression and absorption cycles. The cycle consists of two-stage compressors, absorbers, a desorber, a desuperheater, solution heat exchangers, a solution pump, a rectifier, and a liquid/vapor separator. The compression/absorption hybrid heat pump was designed to produce hot water above $90^{\circ}C$ using high-temperature glide during a two-phase heat transfer. Distinct characteristics of the nonlinear temperature profile should be considered to maximize the performance of the absorber. In this study, the performance of the absorber was investigated depending on the capacity, shape, and arrangementof the plate heat exchangers with regard tothe concentration and distribution at the inlet of the absorber.

A New Energy Saving Process for Air Dehumidification : Analysis and Applications (공기제습의 새로운 에너지 절약과정의 해석과 응용)

  • 대한설비공학회
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.15 no.3
    • /
    • pp.254-263
    • /
    • 1986
  • 공기의 제습 운전에 많은 에너지가 소요되므로 고효율과 경비절감이 가능한 새로운 기술의 연구가 필요하게 되었다. 이 글에서는 공기-공기 열점프 시스템과 흡수시스템을 새로이 제안한 MIDA 과정과 비교한다. LiCl 수용액을 사용한 흡수식 제습과 열펌프 사이클을 조합한 MIDA시스템으로 공기온도가 일정하거나 상승하게 되었다. 열펌프사이클로서 열을 흡수기에서 진공으로 작동되는 용액 재생기로 전달한다.

  • PDF

Fabrication of the Micro-pump using Stereolithography Technology (Stereolithography 기술을 이용한 마이크로 펌프 제작)

  • Lee, Young-Tae;Seo, Hee-Don
    • Journal of Sensor Science and Technology
    • /
    • v.10 no.4
    • /
    • pp.232-238
    • /
    • 2001
  • We fabricated micro-pump using stereolithography technology. The pump was fabricated using PZT for its drive and used non-movable valve of diffuser/nozzle concept. Size of the pump chamber is, $14mm{\psi}$, narrow hole of diffuser/nozzle is $0.5mm{\psi}$ and wide hole $1mm{\psi}$ and chamber depth is 1.2mm, respectively. We confirmed its operation at frequency 100Hz, supply voltage $90{\sim}250Vp-p$. As the result of the pump working measurement, when ethanol is used, the pressure head difference between inlet and outlet of the pump is about 53mm in the frequency of 100Hz, 200V of Vp-p.

  • PDF

Characteristics of Bubble Mode in the Cylindrical Absorber for Heat Pump System (열펌프 시스템에서 원통형 흡수기 내 기포모드의 특성)

  • 이기봉;전병희;이재철;박찬진;김성현
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 2000.11a
    • /
    • pp.199-204
    • /
    • 2000
  • 산업과 과학발달에 의해 더욱 물질적으로 풍요로워진 인류에게 에너지와 환경문제는 새로운 당면문제로 부각되고 있다. 특히 1992년 몬트리올 협정에서는 CFC 및 HCFC의 사용을 각각 1997과 2002년부터 전면 금지시키기로 하였고, 1997년에는 2008-2012년까지 전세계 온실가스 배출량을 5.2% 줄이는 것을 골자로 하는 교토 선언이 합의되었다. 이러한 상황을 타개하기 위한 많은 연구 중 흡수식 열펌프는 환경친화적인 자연냉매를 사용하는 열구동 시스템으로 다시 주목을 받고 있다. 특히 흡수식 열펌프의 구성요소 중 흡수에 의하여 고온의 열을 얻을 수 있는 흡수기에 효율적인 열·물질전달 모드를 적용함으로써 제품의 소형화와 에너지 손실 감소를 이루고 있다. 이에 본 연구에서는 새로운 흡수기 모드로 연구되고 있는 기포타입모드를 원통형 흡수기에 적용해 보고, 그 특성을 고찰해 보고자 하였다. 흡수기로 유입되는 ammonia gas와 용액을 cocurrnet 및 countercurrent로 흘려주었고, 높이에 따른 농도, 온도 및 압력을 측정·비교해 보았다.(중략)

  • PDF

Impact assesment of zooplankton by turbine of tidal power plant in Uldolmok waterway, Korea (울돌목 해역에서 조류발전 시설 터빈 가동에 따른 동물플랑크톤의 피해 영향)

  • Yoo Jeong-kyu;Nam Eun-jung;Myung Chul-soo
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2005.06a
    • /
    • pp.507-511
    • /
    • 2005
  • 울돌목은 조류발전의 세계적인 최적지로 꼽히고 있으며 서해와 남해의 점이 지대로서 조류에 의해 해양 생물 군집의 대량 이동이 빈번한 곳이라 할 수 있다. 조류 발전 시설인 터빈의 가동은 물리적인 충격에 의해 해양 생물의 생태-생리 반응에 영향을 미칠 가능성이 있다. 네트를 이용한 1차 조사에서 터빈 가동에 의한 동물플랑크톤의 순 사망률은 $44.3\%$로 나타났다. 1차 조사 이 후 다이아프램 펌프를 이용한 조사 결과 중 출현 개체수가 높았던 조사에서 전체 동물플랑크톤의 순 사망률은 각각 $7.3\%,\;5.8\%$를 나타내었고, 요각류는 각각 $4.4\%,\;5.2\%$를 나타냈다. 물리적인 충격을 인위적으로 가한 실험에서 스트레스를 받은 요각류 Acartia hongi의 알 생산은 스트레스를 받지 않은 것보다 $1.8\~2.3$배 낮은 경향을 보였다. 본 조사에서 동물플랑크톤이 낮은 사망률을 보골 이유는 작은 크기의 생물이 우점하였기 때문이며 조사 결과에서 몸체가 비교적 단단하고 크기가 작은 요각류는 상대적으로 약한 부유유생보다 높은 생존율을 보였다. 울돌목 조사 해역에서 출현한 동물플랑크톤은 크기가 작아 터빈의 물리적인 충격에 의한 사망률은 낮을 수 있으나 순간적으로 강한 스트레스를 받는다면 재생산을 포함한 생리활동이 저하될 수 있음을 보였다. 네트 및 펌프를 이용한 조사 결과에서 네트에 의한 채집은 터빈의 영향뿐만 아니라 빠른 유속으로 인하여 네트가 받는 압력에 의해 생물체가 손상되는 양상이 높아 사망률이 높았던 것으로 보인다. 그러나 다이아프램 펌프는 생물 채집 시 오류를 최소화하는 장점은 있으나 채집의 장시간에 비해 매우 적은 생물량이 채집되는 단점을 보였다TEX>$96.5\%$에 미달하는 문제는 식물성 원료유로 제조한 고순도 바이오디젤과 혼합 사용하거나 감압 증류 공정을 통해 고농도의 폐식용유 바이오디젤을 제조하여 해결 가능하다. 대전시 신성동 소재의 음식점에서 수거한 폐식용유를 원료로 하여 생산한 바이오디젤의 차량 배출가스 실증 테스트 결과 경유 차량의 주 오염물질인 PM과 Soot 및 기타 오염물질의 배출량은 감소하였으나 NOx의 배출량은 약간 증가하는 것으로 나타났다구와 이해를 바탕으로 보존대책이 마련되어야 한다.되었다. 이런 모든 시편들을 각 탈염방법에 따라 탈염처리한 후 XRD와 SEM-EDS으로 분석한 결과 인철광과 침철광은 어떠한 변화도 보이지 않았고, 다만 적금광으로 동정된 시편만이 잔존하지 않았다. 철기 제작별 $Cl^-$ 이온 추출량과 탈염효과에 대한 비교 실험은 이온 크로마토그래피 분석 결과와 마찬가지로 단조 철제유물이 주조 철제보다 $Cl^-$ 이온을 많이 가지고 있었으며, 탈염 처리 후에는 $Cl^-$ 이온은 전혀 발견되지 않았다. 이상의 결과 $K_2CO_3$와 Sodium 용액은 탈염처리에서 가장 적합한 탈염처리 용액으로 알수가 있었으며 특히 어떠한 탈염 용액으로 유물을 처리한다 해도 철제유물에 생성된 부식물은 제거되지 않는다는 것을 알게 되었다. 따라서 보존처리자는 유물 표면의 부식 상태만을 보고 처리하기 보다는 철기제작물로 고려하여 처리하는 것이 필요하다. 또한 금속에 부식을 야기시키는 $Cl^-$ 이온과 부식물을 완전하게 제거하여 탈염처리를 하는 것이 유물 부식을 최대한 지연시킬 수 있는 것이라 생각된다.TEX>$88\%$)였다.(P=0.063). 결론: 본

  • PDF

Study on Scale Control of Hard Water using High Voltage Impulse Generation (고전압 임펄스를 이용한 용수의 스케일 발생 제어에 관한 연구)

  • Jung, Jae-hwan;Kim, Chul-ho;Lee, June-Ho;Kim, Tae-hui;Jang, In-soung
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.1167-1168
    • /
    • 2015
  • 본 연구는 고전압 임펄스를 이용하여 용수의 스케일 발생 제어가 가능한 조건을 찾는 것을 목표로 하고 있으며 약 100[ppm]의 농도를 갖는 용액을 1[L]제조하여 임펄스 전압 5[kV], 8[kV], 12[kV]를 4시간동안 인가한 회분식 조건의 실험으로써 임펄스 전압의 크기가 증가함에 따라 칼슘이온의 제거율이 8.7[%], 15.6[%], 16.3[%]로 나타났다. 또한 임펄스전압 20[kV]를 20시간동안 인가한 조건에서 칼슘이온 제거율이 약 50[%]에 도달하였다. 연속식 실험은 회분식 실험과 달리 투입과 배출을 중단 없이 연속적으로 용액을 순환시키는 실험으로써 임펄스 전압이 인가되는 반응기가 수용한 용액에 체류 시간에 따라 칼슘제거율을 비교하였다. 일정시간이 되면 배출되는 용액의 칼슘제거율을 측정 하였다. 정량펌프와 정량호스를 이용하여 유량을 8.33[mL/min]으로 조절한 후 임펄스전압 12[kV]를 20시간 인가한 결과 임펄스 전압이 인가되는 반응기내에서 제조된 용액이 체류되는 시간 이후 칼슘제거율이 체류시간에 따라 포화(Saturation)되는 경향을 보였다.

  • PDF

An Experimental Study on Absorber with Spiral Tube in Absorption Heat Pump (흡수열펌프에서 나선형 관이 설치된 흡수기의 실험적 연구)

  • Min, Byong-Hun
    • Applied Chemistry for Engineering
    • /
    • v.21 no.1
    • /
    • pp.71-75
    • /
    • 2010
  • The efficient performance of absorber is of great importance for the absorption heat pump cycle. The experimental study of absorber with spiral tube of tangential feeding of liquid phase has been investigated using methanol-glycerine as a working fluid. The effect of change in absorber operating conditions was analyzed to improve the performance. The increase in solution flow rate and cooling flow rate positively affects the absorber performance while an increse in the solution concentration negatively affects the absorber performance. The results showed that mass absorption flux was in the range of $0.2{\sim}0.6kgm^{-2}sec^{-1}$, the solution heat transfer coefficient between 1.6 and $4.2kwm^{-2}K^{-1}$, the absorber thermal load from 0.9 to 1.5kw and the mass transfer coefficient from 0.9 to 1.7 m/sec.