• 제목/요약/키워드: 온돌 시스템

검색결과 77건 처리시간 0.025초

공동주택의 한국형 온돌시스템 적용에 관한 연구 (A Study on the Korean Ondol-System Application in Apartment Houses)

  • 안민희;최창호;유기형;조동우
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.860-865
    • /
    • 2006
  • The traditional Korean Ondol System that is a radiant floor heating system was made as warm floor and cool indoor temperature. Nowaday, Ondol is developed as the hydronic floor heating system. But unbalance of floor temperature and indoor temperature is occurred bocause strengthen thermal insulation and airtightness in building changes thermal performance. To solve these problems, we examine actual indoor environment of heating system methods in existing apartments and present the new method of floor heating system. The existing heating system made definite indoor temperatures but floor temperatures that is $22^{\circ}C-26^{\circ}C$ was maintained. To solve these problems, we adopted the differential heating system which made warm area and cool area. A differential heating system was made different pitches of heating pipe in single zone and ratio of warm area to cool area is 1 to 2. As a result of experiments, warm area temperature is $40.7^{\circ}C$, cool area temperature is $36.1^{\circ}C$. A difference of temperature between both area is 4K. A distribution of indoor vertical temperature is similar to both warm area and cool area.

  • PDF

축열식 전기온돌 공급시간자동제어시스템 (Development of Automatic Control System for Midnight Electric Ondol)

  • 박석인;정봉만;유승원
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.369-371
    • /
    • 2002
  • 기저부하조성 및 부하율 망상을 위한 심야 전력요금제도의 정착으로 최근 심야전력축열기기의 보급이 활성화되고 있다. 그러나 모든 심야전력축열기기들이 심야요금개시시간대인 22:00경에 동시에 가동됨에 따라 23:00경에 심야전력 부하가 최대에 이르러 전력피크가 발생하여 한전의 수요관리에 어려움을 주고 있다. 따라서 이 피크 부하를 심야전력 공급시간대의 저부하 시간대로 분산시킬 수 있는 심야전력기기 공급시간제어장치가 필요하게 되었으며, 이미 축열식전기보일러와 축열식 전기온수기에는 개발 보급되고 있는 실정이다. 이 논문에서는 다른 심야전력축열기기와는 달리 자연방열의 바닥축열난방방식인 축열식전기온돌의 공급시간자동제어장치 알고리즘을 실증실험을 통해서 검증하였다.

  • PDF

인공신경망 모델을 이용한 온돌시스템의 최적 제어에 관한 연구 (A Study on the Optimal Control of Ondol System Using Artificial Neural Network)

  • 양인호;이진영;김광우
    • 설비공학논문집
    • /
    • 제12권7호
    • /
    • pp.680-687
    • /
    • 2000
  • The objective of this study is to improve the control performance of Ondol system which causes overheating and underheating with 2-position on/off control. For this, a predictive control that determines the suitable on/off positions using Artificial Neural Network(ANN) model was proposed Dynamic analyses using computer simulation show that the neural network used in the predictive control is adapted to each room whose loads variation and thermal characteristics are different. To examine the applicability of this predictive control with ANN it was compared with 2-position on/off control through experiments.

  • PDF

2차원(次元) 온돌 상난방(床煖房)시스템의 연도내 열유동(熱流動) 및 열전달(熱傳達) 수치해석(數値解析) (Numerical Analysis of Heat Flow and Heat Transfer in Flue Channel of Two-Dimensional Ondol Panel Heating System)

  • 김영득;민만기;이상혁;김원갑
    • 설비공학논문집
    • /
    • 제6권4호
    • /
    • pp.337-343
    • /
    • 1994
  • Numerical analysis was applied to a simplified two-dimensional Ondol heating model which consists of heating space on the top of it along with radiant and convective heating floor panel, flue channel in the midway and rectangular underground soil region at the bottom. These three components constitute a system thermally coupled at the top and bottom interfaces of the flue channel. Investigated in the present paper are effects with variations of the Reynolds numbers of 100, 200, and 300, Grashof numbers of $0.1{\times}10^6$ and $0.3{\times}10^6$ and aspect ratios of 15 and 20 on the heat transfer and fluid flow characteristics of two-dimensional Ondol heating model by computer simulation.

  • PDF

심야전력 부하평준화를 위한 심야전기온돌 통전제어시스템 개발 (Development of Electric Ondol Automatic Control System for Midnight Load Levelling)

  • 박석인;정봉만;유승원;한승호;권성철;고기중
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 전력전자학술대회 논문집
    • /
    • pp.719-722
    • /
    • 2002
  • 기저부하조성 및 부하율 향상을 위한 심야전력요금제도의 정착으로 최근 심야전력축열기기의 보급이 활성화되고 있다. 그러나 모든 심야전력축열기기들이 심야요금개시시간대인 2f시경에 동시에 가동됨에 따라 23시경에 심야전력 부하가 최대에 이르러 전력피크가 발생하여 한전의 수요관리에 큰 어려움을 주고 있다 따라서 이 피크 부하를 심야전력 공급시간대의 저 부하시간대로 분산시킬 수 있는 심야전력기기 공급시간을 제어하는 통전제어장치가 필요하게 되었으며, 이미 축열식전기보일러와 축열식전기온수기에는 개발 보급되고 있는 실정이다. 이 논문에서는 다른 심야전력축열기기와는 달리 자연방열의 바닥축열난방방식인 축열식전기온돌의 통전제어장치 알고리즘을 실증실험을 통해서 검증하였다.

  • PDF

온돌 실내공간의 온도제어 (Temperature Control of Ondol Indoor-Space)

  • 신찬배;이재원;사종엽;이상천;조성환;서항석
    • 설비공학논문집
    • /
    • 제7권3호
    • /
    • pp.538-545
    • /
    • 1995
  • The heat transfer model of ondol heating system is derived in the linear form. The step responses of On-Off controller, PID controller and Position type fuzzy controllers are compared in the sense of several aspects : variation of temperature feedback variable, variation of supplied heat quantity by the boiler, variation of flow rate, variation of thickness of the base, variation of the outdoor temperature.