난방시 가압식 바닥취출 공조방식의 실내온열환경 평가 (An Estimation on Indoor Thermal Environment by Pressurized Plenum Under Floor Air Conditioning System in Heating)

  • 최은훈;이용호;권영철;황정하
    • 한국태양에너지학회 논문집
    • /
    • 제30권4호
    • /
    • pp.92-99
    • /
    • 2010
  • The purpose of this study is to apply pressurized plenum under floor air conditioning system to office areas to understand characteristics of indoor thermal environment based on forms of diffusers. For doing this, the author conducted experiment of module measurement, and based on the results, analyzed indoor temperature distribution and velocity distribution based on direction of diffusion by using Computational Fluid Dynamics(CFD), and estimated the Predicted Mean Vote(PMV) of residents based on forms of diffusers to present the optimal air conditioning of the pressurized plenum under floor air conditioning system in heating. The results of this study are as follows. First, as for forms of diffusers, distributed diffusers rather than conical and grill diffusers were favorable in maintaining $24^{\circ}C$, the established temperature in heating, were active in velocity flowing, and were wide in a radius of diffusion. Second, as for position of pressurizing, the difference between upper and lower temperature was wider in center, lateral, and dispersed pressurizing (in order). As for velocity distribution, the velocity was more increased in lateral, center, and dispersed pressurizing(in order), indicating that dispersed pressurizing maintained uniform thermal environment. Third, as for diffusion direction, mixed direction showed less difference between upper and lower temperature and the difference in velocity between center and lateral part was 0.01m/1, indicating that it maintained uniform thermal environment. Fourth, as for the PMV of residents based on the forms of diffusers, the dispersed type showed(+) values above (0) when applied variably based on the position of diffuser, presenting thermal feeling of "being comfortable" to residents.

실내 온열환경 쾌적 제어를 위한 단순 PMV 회귀모델의 적용에 관한 시뮬레이션 연구 (A Study on the Application of Simulation-based Simplified PMV Regression Model for Indoor Thermal Comfort Control)

  • 김상훈;윤성준;정광섭
    • 에너지공학
    • /
    • 제24권1호
    • /
    • pp.69-77
    • /
    • 2015
  • 본 연구에서는 보정된 모델링 건물을 대상으로 PMV 변수에 대한 데이터베이스를 구축하였고, 다중회귀분석을 통하여 PMV 회귀모델을 도출하였다. PMV 회귀모델은 민감도 및 데이터 분석을 통하여 단순화하여 단순 PMV 회귀모델을 제시하였다. 단순 PMV 회귀모델과 Fanger PMV 모델에 대한 MAE 및 RMSE 검증을 통하여 단순 PMV 회귀모델이 Fanger PMV 모델을 대체할 수 있는 것으로 분석되었다. EnergyPlus의 EMS(Energy Management System)를 이용하여 보정된 모델링 건물에 PMV 회귀모델 제어를 적용하였다. 단순 PMV 회귀모델과 Fanger PMV 모델 제어의 온열 쾌적도를 비교한 결과, 두 제어 모두 공조기간 동안 약 90% 이상이 온열쾌적 범위를 만족하였고, 온열 쾌적 제어의 특징인 설정 PMV를 만족하는 설정온도에 의하여 제어되는 것으로 나타났다.

겨울철 가습 및 환기에 따른 교실내 쾌적환경 분석 (Analysis of Comfortable Environment in the Classroom with Humidification and Ventilation in Winter)

  • 정성일;성내리;김두현;이재근;황유진;박종훈;서석장
    • 설비공학논문집
    • /
    • 제21권7호
    • /
    • pp.402-408
    • /
    • 2009
  • In this paper, the effects of ventilation and humidification on thermal comfort and indoor air quality(IAQ) were evaluated in a classroom when a heat pump system was operated in winter. Thermal comfort parameters, such as temperature, relative humidity, globe temperature and air velocity, were measured at 9 points in the classroom. The concentration of $CO_2$ and total suspended particles(TSP) in the classroom were measured in order to analyze IAQ. Temperature distribution in the classroom was decreased by $2{\sim}5^{\circ}C$ when the ventilation system and the humidifier were operated. When the relative humidity was adjusted to 60% by operating the humidifier and the ventilation system, the predicted mean vote(PMV) in the classroom was within the comfortable range of $-0.5{\sim}0.5$. When the ventilation system was operated, the average concentration of $CO_2$ and TSP were decreased by 645 ppm and 0.17 $mg/m^3$, respectively. This paper suggests the humidification and ventilation conditions to maintain the comfortable environment in the school classroom in winter experimentally.

도시근린공원의 열환경 개선을 위한 열쾌적성 평가 (An Evaluation of Thermal Comfort on Urban Neighborhood Park for Improving Thermal Environment)

  • 임은나;이우성;최철현;송봉근;정성관
    • 한국지리정보학회지
    • /
    • 제16권4호
    • /
    • pp.153-170
    • /
    • 2013
  • 본 연구는 도시 근린공원의 열쾌적성을 평가하고 이에 따른 열환경 개선방안을 도출하고자 연구를 진행하였다. 먼저 공원의 주요 열환경 인자의 분포특성 및 공간 유형별 차이를 평가한 결과, 기온, 상대습도, 풍속의 경우 공간적으로 뚜렷한 차이를 보이지 않았다. 그러나 평균복사온도는 공간의 개방정도 및 포장재질에 따라 큰 차이를 나타내는 것으로 확인되었다. 추출된 열환경 인자를 토대로 공간 유형에 따른 열쾌적성을 평가한 결과, 광장의 PMV(Predicted Mean Vote, 예상온열감) 지수가 4.39로 가장 높게 나타났으며, 동선의 경우 2.58, 녹지 1.90 그리고 휴게공간은 0.42로 평가되었다. 이러한 열쾌적성을 결정하는 열환경 요인에 대한 중요도를 평가해보기 위하여 PMV 회귀모형을 구축한 결과, 평균복사온도(1.084), 풍속(-0.280), 기온(0.013), 상대습도(-0.009)의 순으로 PMV에 대한 상대적인 중요도가 높게 나타났다. 열환경적 측면에서 개선이 필요한 지역을 대상으로 시나리오 분석을 실시한 결과, 반사율, 색상, 포장재질의 물리적 특성 변화를 통해 인체가 체감하는 열쾌적성을 향상시킬 수 있으며, 실제 공원에 이를 적용하여 개선안을 마련할 수 있을 것으로 판단된다.