Browse > Article

An Estimation on Indoor Thermal Environment by Pressurized Plenum Under Floor Air Conditioning System in Heating  

Choi, Eun-Hun (Dept. of Architecture & Urban Environmental Engineering Kyungpook National University)
Lee, Yong-Ho (Dept. of Architecture & Urban Environmental Engineering Kyungpook National University)
Kwon, Young-Cheol (Dept. of Architecture & Urban Environmental Engineering Kyungpook National University)
Hwang, Jung-Ha (School of Architecture in Halla University)
Publication Information
Journal of the Korean Solar Energy Society / v.30, no.4, 2010 , pp. 92-99 More about this Journal
Abstract
The purpose of this study is to apply pressurized plenum under floor air conditioning system to office areas to understand characteristics of indoor thermal environment based on forms of diffusers. For doing this, the author conducted experiment of module measurement, and based on the results, analyzed indoor temperature distribution and velocity distribution based on direction of diffusion by using Computational Fluid Dynamics(CFD), and estimated the Predicted Mean Vote(PMV) of residents based on forms of diffusers to present the optimal air conditioning of the pressurized plenum under floor air conditioning system in heating. The results of this study are as follows. First, as for forms of diffusers, distributed diffusers rather than conical and grill diffusers were favorable in maintaining $24^{\circ}C$, the established temperature in heating, were active in velocity flowing, and were wide in a radius of diffusion. Second, as for position of pressurizing, the difference between upper and lower temperature was wider in center, lateral, and dispersed pressurizing (in order). As for velocity distribution, the velocity was more increased in lateral, center, and dispersed pressurizing(in order), indicating that dispersed pressurizing maintained uniform thermal environment. Third, as for diffusion direction, mixed direction showed less difference between upper and lower temperature and the difference in velocity between center and lateral part was 0.01m/1, indicating that it maintained uniform thermal environment. Fourth, as for the PMV of residents based on the forms of diffusers, the dispersed type showed(+) values above (0) when applied variably based on the position of diffuser, presenting thermal feeling of "being comfortable" to residents.
Keywords
Pressurized Plenum Under Floor Air Conditioning System; Predicted Mean Vote; Position of Pressurizing; Diffusion Direction;
Citations & Related Records
연도 인용수 순위
  • Reference
1 신동민, 정차수, 홍민호, 유지용, 이상엽, 조동우, 시뮬레이션을 통한 바닥급기 시스템 설계인자에 대한연구, 대한설비공학회 동계학술발표회논문집, 2004, pp.371-379
2 석호태, 최동호, 김호진, 양정훈, 디퓨져 유형에 따른 CFD 시뮬레이션 방법에 관한 연구, 대한건축학회 학술발표대회 논문집, 2009, pp. 785-788