• Title/Summary/Keyword: 열감

Search Result 72, Processing Time 0.023 seconds

A Study for Performance Improvement of Fire Detector and Sprinkler Head in Apartment Houses (공동주택 화재감지 및 소화성능개선에 관한 연구)

  • Lee, Chae-Won;Son, Bong-Sei
    • Fire Science and Engineering
    • /
    • v.29 no.1
    • /
    • pp.38-44
    • /
    • 2015
  • This study suggested the problems and their improvement measures for the operation of fire detectors and sprinkler heads installed at apartment houses. According to a census on population and housing in 2010, apartment houses account for 71.6% of the total housing facilities. And by fire statistics data of the National Emergency Management Agency, approximately 25.0% of fire accidents and 46.4% of casualties occur at apartment houses every year. Therefore, this study conducted for identifying the causes and characteristics of fire to establish the fire safety improvement measures for apartment houses. And this study was carried out virtual fire simulation at domestic apartment houses. The scenario of the simulation contains a comparative analysis on the operation time of standard sprinkler heads and residential sprinkler heads, heat detectors and smoke detectors. As a result of simulation, it was found that standard sprinkler heads and heat detectors installed at the existing apartment houses should be replaced with residential sprinkler heads and smoke detectors for rapid fire suppression. In addition, sprinkler systems should be considered to be installed for excluded floor at apartment houses. Especially, it is necessary to construct remote inspect systems like advanced countries for efficiency of apartment houses safety management.

Operating Temperature and Time of Rate of Rise Heat Detector (차동식 열감지기의 작동온도와 작동시간)

  • 류호철;이병곤
    • Journal of the Korean Society of Safety
    • /
    • v.9 no.1
    • /
    • pp.61-67
    • /
    • 1994
  • Rate of rise heat detectors that respond to the heat generated in fire plume and alarm when the temperature reaches a specified point, give a great influences to the loss of life and property according to their reaction sensitivity. In this study, simple equations were derived which can be predicted the response time and temperature of the rate of rise heat detector with the results of hot wind tunnel tests and compartment fire experiments.

  • PDF

A REPORT ON THERMAL LAG OF PAINTED HEAT DETECTORS (도막상태에 따른 열감지기의 감온특성에 관한 시험, 연구)

  • Lee, Bok-Yeong;Yu, In-Ho
    • Fire Protection Technology
    • /
    • s.14
    • /
    • pp.18-33
    • /
    • 1993
  • This report is announced about thermal lag of painted heat detectors. Thermal lag is forecast result from painting the part of heat receiving. It is delayed responsive time to assume fire fighting, escape. Test is simulated that heat detector is painted by synthetic resin emulsion paint according to the circumstance of installation. Painting method, number, thick etc is determined by research worker based on the popular idea.

  • PDF

Prediction of a rectal temperature utilizing a thermal perception index.

  • Kwon, Young G.;Jerry D.Ramsey
    • Proceedings of the Korean Society for Emotion and Sensibility Conference
    • /
    • 1998.04a
    • /
    • pp.159-164
    • /
    • 1998
  • 이 논문은 신체온도를 직접 측정하지 않고서 신체온도를 예상하는 모델을 연구한 것이다. 열감지지수 (TPI)를 개발하여 환경으로부터 느끼는 체감온도와 몸의 내부온도인 직장온도(Tuec)와 몸의 외부온도인 피부온도 (Tskin)를 예측하도록 하였다. Kwon와 Ramsey의 개발모델을 Goldman의 모델과 비교해본 결과 정확도에 통계적으로 유의한 차이가 없었다. 회귀분석과 경험을 토대로 만든 체감온도를 예측할 수 있는 손쉬운 Kwon의 열감지수 (KTPI)도 제시하였다. 대부분의 사람들이 쉽게 예측할 수 있도록 측정 또는 사용가능한 몇 개의 환경변수로부터 몸의 예상 내부온도와 외부온도를 계산할 수 있게 단순화하였다.

  • PDF

Evaluation of the Closed-type Sprinkler Head Activation Time (밀폐형 스프링클러 헤드의 동작시간 평가)

  • Moon-Hak, Jee;Sung-Yull, Hong
    • Fire Science and Engineering
    • /
    • v.18 no.3
    • /
    • pp.1-8
    • /
    • 2004
  • As a predominant active fire suppression method, closed-type sprinkler systems are used for the purpose of fire control and suppression at the nuclear power plants as well as the industrial facilities. It goes without saying that the proper selection of the system guarantees the adequate actuation of the thermal device. Consequently, the appropriate evaluation should be executed for the thermal behavior with the theoretical and empirical approach. For this purpose, the comparison of activation time for the fusible-link type sprinkler head with the simplified fire case and t-square fire growth case was evaluated. At this paper, the comparison output was presented with the tendency of thermal behavior. In addition, we issued some technical comments for the most appropriate equation in case of the estimation of the sprinkler head activation time. We also raised some idea that should be incorporated for the usage of the t-square equation for the realistic application in the field of the performance-base fire protection approach.

Failure Analysis of the Rate of Rise Spot Type Heat Detector on Artificially Accelerated Aging (인공 가속열화에 따른 차동식 스포트형 열감지기의 고장 원인분석)

  • Kim, Chan-Young
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.48-55
    • /
    • 2011
  • This paper presents the failure analysis of the rate of rise spot type heat detectors on artificially accelerated aging. The failures of heat detector turned out by two reasons. The first one is the separation of binder from plastic moulding, resulting in the leakage of air from heat chamber. The second reason is the crack of plastic. The large cracks were maybe created by these reasons, thermal expansion difference, mechanical stress, or growth of microcrack. In the sound detector, the separation and the crack were not occurred or not developed to the critical size. The glass fibers which increase the mechanical strength were added in the binder of detector 2010G. The densities of binder or plastic of each detector were similar. However, the TGA result shows that the thermal characteristics of 2005A and 2005B were not similar.

A Study of Korea Performance Testing Methodology for Fingerprint Recognition System (국내 지문인식시스템 성능시험방법론 연구)

  • 신대철;심상옥;김재성
    • Proceedings of the Korea Institutes of Information Security and Cryptology Conference
    • /
    • 2002.11a
    • /
    • pp.440-445
    • /
    • 2002
  • 최근 생체인식제품 시장이 활성화됨에 따라 생체인식제품에 대한 객관적인 성능평가가 절실히 요구되고 있는 상황이다. 이미 국외에서는 이러한 추세에 따라 지문, 얼굴, 홍채, 음성 등 각 생체인식제품에 대한 성능평가 기술을 개발하고 있으며, 자국의 생체인식제품에 대한 성능을 개선하는데 도움을 주고 있다. 현재 국내의 경우는 생체인식제품에 대한 객관적인 성능평가 연구기반이 취약한 상태이며, 개발자 자신에 의한 주관적인 평가방법에 따라 자체 시험을 하는데 머물고 있는 실정이다. 이에 따라 본 고에서는 우선적으로 지문인식제품에 대한 국내 적용 가능한 성능평가 항목과 평가방법을 제시하기 위하여 광학식, 반도체식, 열감지식 입력센서별 온도, 습도, 압력, 기만성 측정방법과 인식알고리즘에 대한 성능측정방법을 분석하였다.

  • PDF

A Study on Domestic and Foreign Test Method of Fire Detectors (국내외 화재감지기 시험의 차이점에 관한 연구)

  • Shin, Seung-Chul;Baek, Dong-Hyun;Go, Eun-Ae
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2013.04a
    • /
    • pp.144-145
    • /
    • 2013
  • 국내에서 생산되고 있는 화재감지기는 설치 환경, 위치, 전기적 및 기계적인 요인에 따라 그 성능의 신뢰성이 차이를 나타내고 있다. 본 연구는 국내에서 제조되고 있는 국내 화재감지기 성능 신뢰성 제고를 위한 방안을 제시하고자 열감지기, 연기감지기, 불꽃감지기 등의 성능시험 관한 각 기관별 주요 내용과 차이점을 비교 검토하였다. 이를 위해 국가시험기관의 27종, 방재시험연구원 46종류, 국제 표준화기구 36종류를 대상으로 한바 다양한 환경에서 적응하고 신뢰성 향상에 비중이 많았다. 감지기에서 발생하는 비화재보, 감지지연 및 기타 원인 불명등과 시험기준의 상호관계를 확인하는 연구가 선행되어야 한다.

  • PDF

Sclerotherapy of the varicose veins (정맥류 경화용법)

  • 김부연;김재영;이교준;함석진;김해균
    • Journal of Chest Surgery
    • /
    • v.34 no.3
    • /
    • pp.231-234
    • /
    • 2001
  • 배경: 하지 정맥률의 치료법중의 하나인 압박경화요법의 치료효과를 알아보고자 하였다. 대상 및 방법: 영동세브란스병원에서 1997년 8월부터 1999년 8월까지 복대-대퇴정맥판막 부전이 없는 하지정맥류 환자 중 압박경화용법을 시행 받은 94명을 대상으로 하였다. 병역 및 이화학적 검사결과, 압박경화용법의 치료효과와 합병증 등을 살펴보았다. 결과: 환자의 연령은 20대에서부터 70대까지 있었으며, 평균 43.4세였고 성별은 남자가 28명 여자가 66명 이었다, 정맥의 돌출 이외에 다른 증상은 없는 환자가 87명이었으며, 다리가 무거운 증사, 피로, 통증도 각각 1예, 2예, 2예가 있었다. 대상 환자 중에서는 소복재정맥에 이환된 사람이 83예이었다. 50명환자에서 1회의 시술만으로 만족할 만한 결과를 보였으며, 시술 후의 합병증으로 부분적인 열감, 정맥염, 괴사가 있었다. 결론: 복재-대퇴정맥판막 부전이 없는 하지정맥류의 치료에 있어 경화요법은 미용적으로 우수한 효과적인 치료법으로 생각된다.

  • PDF