A Study on the Thermal Crack Control of Foundation for Large Turbine (대형 터빈 기초 구조물의 온도균열 제어에 관한 연구)

  • Ha, Ju-Hyung;Cho, Yun-Gu;Lee, Kewn-Chu;Lim, Chang-Keun
    • Journal of the Korea Concrete Institute
    • /
    • v.26 no.3
    • /
    • pp.287-297
    • /
    • 2014
  • Heat of hydration of mass concrete is one of the most important factors that significantly affect structural quality and construction period. Therefore, appropriate methods to control heat of hydration are essential technologies for mass concrete construction. In this study, probability of thermal cracking was checked by thermal analysis prior to the construction of a turbine foundation in a domestic power plant. Subsequently, changes of concrete mix proportion and an effective curing method were proposed to control heat of hydration of mass concrete structures. Concrete manufactured by slag cement was proposed instead of concrete produced by ordinary Portland cement, and an automated curing method was proposed to improve the curing method using typical moist curing with blanket. The automated curing method maintains the temperature difference between center and surface of concrete below a setting value by temperature monitoring. Concrete with slag cement was used for actual construction. One of two identical turbine foundations was cured by an insulated curing method, and the other was cured by the automated curing method to compare the curing methods. And then, the effects of control of heat of hydration were evaluated based on temperature/strain monitoring and crack investigations.

Control of Thermal Crack in Mass Concrete Using Automated Curing System (양생자동화 시스템을 이용한 매스 콘크리트 온도균열 제어)

  • Ha, Ju-Hyung;Cho, Yun-Gu;Hyun, Tae-Yang;Lim, Chang-Keun;Seo, Tae-Seok
    • Journal of the Korea Concrete Institute
    • /
    • v.25 no.2
    • /
    • pp.195-200
    • /
    • 2013
  • New thermal crack control system for mass concrete was developed to increase quality and to save construction period and cost. The principle of this system is that the curing water having proper temperature is supplied automatically to the surface of mass concrete member to keep the temperature difference between center and surface of concrete less than generally recommended temperature difference ($20^{\circ}C$). Mock-up test was conducted to investigate the validity of newly developed curing system. As a result, no crack was founded in the specimen using automated curing system developed in this study, while many cracks occurred in another specimen without automated curing system. It was also confirmed that the strength and the durability of the concrete cured by automated curing system were improved.