• Title/Summary/Keyword: 습식 바닥난방

Search Result 4, Processing Time 0.016 seconds

공동주택 바닥난방 시스템의 현황과 개선방향

  • 조동우
    • 월간 기계설비
    • /
    • s.43
    • /
    • pp.94-100
    • /
    • 1994
  • 본고에서는 기존 공동주택에 적용되고 있는 습식 바닥난방방식의 현황과 조립식 난방판넬의 현황과 문제점을 살펴보고 앞으로 조립식 난방시스템의 적립식 난방시스템에 적용시 검토사항 및 개선방향에 대하여 기술하였다.

  • PDF

A Study on Comparison of Capacity between Wet.Dry Floor Heating Systems Using Geothermal Heat Pump (지열히트펌프를 이용한 습식.건식 바닥난방 성능평가 연구)

  • Lee, Byoung-Doo;Lee, Se-Jin;Lee, Dae-Woo;Oh, Sung-Hae;Nam, Woo-Dong
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.567-570
    • /
    • 2009
  • The present study conducted comparative evaluation of wet dry floor heating systems using geothermal heat pump. Circulation hot water from geothermal heat pump which is $10{\sim}15^{\circ}C$ lower than that from boiler was used. In order to access indoor temperature ($25^{\circ}C$) it took 74 minutes for dry type and 247 minutes for wet type. Average floor temperature was $23.89^{\circ}C$ for wet type and $32.66^{\circ}C$ for dry type. Energy saving rate gradually increased by 66% after 138 minutes. In the results, for floor heating system using low temperature circulation water, wet type was not enough to meet stable and comfortable radiant floor heating due to low floor temperature and access time to indoor set temperature. While dry type was practicable for stable floor heating due to fast rise of indoor set temperature and comfortable floor temperature.

  • PDF

Comparative Study on Performance of Wet-type and Dry-type Floor Heating Systems Using Geothermal Heat Pump (지열히트펌프를 이용한 습식.건식 바닥난방 성능평가 연구)

  • Lee, Byoung-Doo;Lee, Se-Jin;Lee, Dae-Woo;Oh, Sung-Hae;Nam, Woo-Dong
    • New & Renewable Energy
    • /
    • v.5 no.4
    • /
    • pp.60-65
    • /
    • 2009
  • The present study was conducted for a comparative evaluation of wet and dry floor heating systems using geothermal heat pump. We circulated hot water from geothermal heat pump which is $10{\sim}15^{\circ}C$ lower than that from boiler. In order to access indoor temperature ($25^{\circ}C$) it took 74 minutes for dry type and 247 minutes for wet type. Average floor temperature was $23.9^{\circ}C$ for wet type and $32.7^{\circ}C$ for dry type. Energy saving rate gradually increased by 66% after 138 minutes. As a result, in case of floor heating system using low temperature circulation water, dry type was more practicable for stable floor heating than wet type in terms of floor temperature and access time to indoor set temperature.

  • PDF

A Study on the Development of Rolled Dry Floor Heating System for Improving Workability (현장 시공성 개선을 위한 롤타입 건식바닥난방시스템 개발)

  • Lee, Gyu-Dong;Kim, Jun-Ho;Jeong, Chang-Ho;Kim, Dong-Woo;Ogawa, Keiichiro
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2012.11a
    • /
    • pp.177-180
    • /
    • 2012
  • Korea residential housing generally use wet floor heating system 'Ondol' which consist of insulation cushioning, lightweight foamed concrete, hot water pipe and mortar on top of reinforced concrete slab. Wet floor heating system's installation process is too complicate and difficult to supervise field for continuing assurance quality. Also, this method has a huge impact on the progress of construction because it take a long time to cure finishing mortar and lightweight foamed concrete. Therefore, it is considered a disturbance factor of reduction of construction duration for enhancing competitiveness. In this study, we conducted an experiment about the radiant heat performance and temperature difference on upper panel of rolled dry floor heating systems which is jointly developed by Kolon global and Sumisho Metalex for remodeling housing, studio apartment and the urban-life housing.

  • PDF