출구 온도를 고려한 수평형 지중열교환기의 매설 지침에 관한 연구 (A Study on Burial Guideline of Horizontal Geothermal Heat Exchanger based on Exit Temperature)

  • 조성우;임병찬
    • 설비공학논문집
    • /
    • 제26권12호
    • /
    • pp.553-558
    • /
    • 2014
  • Geothermal energy can be used with a geothermal heat pump or an earth-to-air heat exchange system (EAHES), which is referred to as a "cooling tube" in Korea. In this study, we suggest EAHES burial guidelines in terms of the parameters of buried pipe length and air velocity regarding the exit air temperature of EAHES. The exit air temperature for EAHES in three regions (Changwon, Busan and Seoul) was calculated with variation in buried pipe length and air velocity at ${\Phi}100mm$ and ${\Phi}200mm$. In conclusion, variation in the buried pipe length is more effective than that of air velocity to achieve the required exit air temperature.

수평형 지중열교환기 설계를 위한 토양 열전도도 예측 모델 평가 (Evaluation of Conventional Prediction Models for Soil Thermal Conductivity to Design Horizontal Ground Heat Exchangers)

  • 손병후;위지혜;박상우;임지희;최항석
    • 한국지반공학회논문집
    • /
    • 제29권2호
    • /
    • pp.5-14
    • /
    • 2013
  • 지중 토양의 열 물리적 성질 중 열전도도(thermal conductivity)는 지열 히트펌프 시스템(ground-coupled heat pump systems)의 지중열교환기 설계 과정에서 매우 중요한 변수다. 토양의 열전도도는 3상 구조로 인해 함수비와 건조밀도의 영향을 많이 받는다. 본 논문에서는 수평형 지중열교환기의 트렌치 뒤채움재로 사용되는 9종류의 토양(모래-물혼합물)을 대상으로 열전도도 측정결과와 기존 상관식에 의한 계산결과를 비교하였다. 건조토인 경우, 2상 구조의 열전도도 예측모델인 준이론 모델에 의한 열전도도 계산 결과는 측정 결과와 큰 차이를 보였다. 불포화토인 경우, 기존 모델 중 Cote와 Konrad가 제시한 모델에 의한 계산 결과가 측정 결과와 가장 잘 일치하였다. 또한 토양의 열전도도와 함수비, 종류 등이 수평형 지중열교환기의 설계 길이에 미치는 영향을 고찰하였다. 뒤채움재로 사용되는 토양의 열전도도가 증가할수록 수평형 지중열 교환기의 설계 길이는 감소하였다.