• Title/Summary/Keyword: 반환부하법

Search Result 3, Processing Time 0.019 seconds

The Energized Aging Property of Pole Mount Mold transformer by Back-to-back Method (반환부하법에 의한 옥외 주상용 몰드변압기의 과전열화 특정)

  • Hwang, Bo-Guk;Cho, Han-Goo;Lee, Un-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.484-487
    • /
    • 2002
  • The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss. In this paper, the proto type mold transformer of 50kVA class is investigated by routine, type, special test. The outdoor energized aging test is investigated by back-to-back method to verify the long time performance of pole mold transformer. The aging process of transformer is analyzed by various diagnosis method such as DC voltage-current test, $tan{\delta}$, Meggar measurement, winding temperature and etc.

  • PDF

3-D Analysis of Temperature Distribution in Transformers (변압기의 3차원 온도분포 해석)

  • 오연호;송기동;선종호
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.52 no.9
    • /
    • pp.434-441
    • /
    • 2003
  • This paper deals with the temperature characteristics according to the cooling medium and the duct size in model transformers. For the analysis and the temperature-rise tests, two 400kVA model transformers have been manufactured. One has been filled with the alpha oil as the cooling medium and constructed the duct sizes of $3\textrm{mm}$ and $5\textrm{mm}$ in the low-voltage and high-voltage windings respectively. The other has been filled the beta oil and the duct sizes were $4\textrm{mm}$ and $6\textrm{mm}$. The temperature-rise tests have been performed by the back-to-back method and the load factor has been controlled the range of 90%∼130%. The temperature values have been measured by the thermocouple and from the sixteen points in each transformer. A commercial CFD program "FLUENT" has been used for the analysis of temperature distribution. The geometry of transformer has been modeled to 3-dimensional by using the hybrid calculation mesh including the radiator. And also, the natural convection velocity has been measured at the oil top position, and compared with the calculated results.

Aging Test of 20kVA Amorphous Core Transformer by Loading Back Method (부하반환법에 의한 20KVA 비정질 변압기의 경년열화 연구)

  • 민복기;송재성;정영호;임정재
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.43 no.2
    • /
    • pp.278-285
    • /
    • 1994
  • Aging test was done by loading back method for 20kVA amorphous core transformers manufactured by Hyosung Industries Co. and korea Electric Power Corporation. Iron losses, copper losses and insulation oil temperatures of the transfromers was measured for all the testing period. Expected life of amorphous core transformers on the basis of the degradation of the insulators was 46 years at 100% load, and 2.4 years at 130% load. Average temperature rising of transformer oil of amorphous core transformers was higher than that of silicon steel core transformers. Hence lowering the oil temperature by optimized design is needed for improving the expected life of the amorphous transformers.

  • PDF