• 제목/요약/키워드: 리튬브로마이드수용액

검색결과 22건 처리시간 0.017초

수직 흡수전열관의 흡수성능에 미치는 스프링의 영향 (Influence of Spring on The Absorption Performance of a Vertical Absorber Tube)

  • 김정국;조금남
    • 설비공학논문집
    • /
    • 제14권10호
    • /
    • pp.825-832
    • /
    • 2002
  • The present study investigated the enhancement of the absorption performance by the spring wrapped around the outer surface of the vertical falling film absorber tube. Heat and mass transfer enhancements were experimentally investigated, and flow visualization was performed to observe the wettability and flow pattern of the solution. The key experimental parameters were spring diameter (0.5, 1.0 mm) and spring pitch (1, 3, 10 mm), film Reynolds number (50~150), and concentration of LiBr-$H_2O$ solution (55, 60, 65 wt%). As the spring diameter was increased, the absorption mass flux, Sherwood number, Nusselt number, heat flux, and heat transfer coefficient were increased The Nusselt and Sherwood numbers showed the maximum at the spring pitch of 3mm, and the ratio of pitch to diameter of approximately 3 and 6 for the spring diamter of 0.5 mm, respectively.

하수처리수 이용 흡수식 열펌프 사이클의 시뮬레이션 (Simulation of a two-stage absorption heat pump cycle using treated sewage)

  • 이용화;신현준;최국광
    • 설비공학논문집
    • /
    • 제11권3호
    • /
    • pp.422-430
    • /
    • 1999
  • This paper concerns the study of a two-stage absorption heat pump cycle to utilize treated sewage. This two-stage cycle consists of coupling double-effect with parallel or series flow type and single effect cycle so that the first stage absorber and condenser produces hot water to evaporate refrigerant in the evaporator of the second stage. The effects of operating variables such as absorber temperature on the coefficient of performance have been studied for two-stage absorption heat pump cycle. The working fluid is lithium bromide and water solution. The efficiency of the two-stage absorption heat pump cycle has been studied and simulation results show that higher coefficient of performance could be obtained for the first stage with parallel flow type. The optimum ratio of solution distribution can be shown by considering the COP, the crystallization of solution and the generator temperature.

  • PDF

수평관군에서 리튬브로마이드 수용액 막의 수증기 흡수과정에 대한 비흡수가스의 영향 (Effects of non-absorbable gases in the absorption process of water vapor Into the Lithium Bromide-water solution film on horizontal tube bank)

  • 김병주;권기석
    • 설비공학논문집
    • /
    • 제12권2호
    • /
    • pp.218-225
    • /
    • 2000
  • In the present study, the effects of film Reynolds number (60∼200) and volumetric content of non-absorbable gases (0∼10%) in water vapor on the absorption process of aqueous LiBr solution were investigated experimentally. The formation of solution film on the horizontal tubes of six rows were observed to be complete for Re>100. Transition film Reynolds number were found to exist above which the Nusselt number and Schmidt number diminishes with solution flow rate. As the concentration of non-absorbable gases increased, mass transfer rate decreased more seriously than heat transfer rate did. The degradation effects of non-absorbable gases seemed to be significant especially when small amount of non-absorbable gases were introduced to the pure water vapor.

  • PDF

수평 냉각관 외부를 흘러내리는 $LiBr-H_2O$ 수용액의 유동 및 열/물질 전달 특성에 관한 실험적 연구 (An Experimental Study on Flow and Heat / Mass Transfer Characteristics of $LiBr-H_2O$ Solution Flowing over a Cooled Horizontal Tube)

  • 설신수;이상용
    • 대한기계학회논문집B
    • /
    • 제24권8호
    • /
    • pp.1085-1096
    • /
    • 2000
  • An experimental study was performed to examine the heat and mass transfer characteristics of $LiBr-H_2O$ solution flowing over a single horizontal tube with the water vapor absorption. Effects of the flow rate and the temperature of the solution at the top of the tube, the absorber pressure and the drainage pattern were considered. The absorption rate depends highly on the absorber pressure at the low flow rate condition while on the solution inlet temperature at the high flow rate condition. Also, when the flow rate is low, the absorption performance with the sheet flow drainage appeared to be higher than that with the dripping/jet drainage. However, at the high flow rate condition, the case became reversed. The liquid film became wavy with the higher absorption rate. The waves were more probable to form with the lower flow rate and temperature of the solution, and with the higher absorber pressure.

헬리컬 흡수기의 흡수 열물질전달 해석 (Analysis of Heat and Mass Transfer on Helical Absorber)

  • 권오경;임종극;윤정인;김선창;윤재호
    • 대한기계학회논문집B
    • /
    • 제24권11호
    • /
    • pp.1428-1436
    • /
    • 2000
  • The absorption of vapor involves simultaneous heat and mass transfer in the vapor/liquid system. In this paper, a numerical study for vapor absorption process into LIBr-H$_2$O solution film flowing over helical absorber has been carried out. Axisymmetric cylindrical coordinate system was adopted to model the helical tube and the transport equations were solved by the finite volume method. The effects of operating conditions, such as the cooling water temperature. the system pressure, the film Reynolds number and the solution inlet concentration have been investigated in view of the absorption mass flux and the total absorption mass flux and the total absorption rate. The results for the temperature and concentration profiles, as well as the local absorption mass flux at the helical absorber are presented. It is shown that solution inlet concentration affected other than operation conditions for a mass flux.

수평단관 상의 유하액막 열전달 (Falling Film Heat Transfer on a Horizontal Single Tube)

  • 김동관;김무환
    • 설비공학논문집
    • /
    • 제12권7호
    • /
    • pp.642-648
    • /
    • 2000
  • Falling film heat transfer analyses with aqueous lithium bromide solution were peformed to investigate the transfer characteristics of the copper tubes. Finned(knurled) tube and a smooth tube were selected as test specimens. Averaged generation fluxes of water and the heat transfer performances(heat flux, heat transfer coefficient) were obtained. The results of this work were compared with the data reported previously. As the film flow rate of the solution increased, the generation fluxes of water decreased for both tubes. The reason is estimated by the fact that the heat transfer resistance with the film thickness increased as the film flow rate increased. The effect of the enlarged surface area at the knurled tube was supposed to be dominant at a small flow rate. The generation fluxes of water increased with the increasing degree of tube wall superheat. Nucleate boiling is supposed to occur at a wall superheat of 20 K for a smooth tube, and at 10 K for a knurled tube. The heat transfer performance of the falling film was superior to pool boiling at a low wall superheat below 10 K for both tubes tested. The knurled tube geometry showed good performance than the smooth tube, and the increased performance was mainly came from the effect of the increased heating surface area.

  • PDF

수직형 흡수기내 열 및 물질 전달 특성 (Heat and mass transfer characteristics in a vertical absorber)

  • 서정훈;조금남;최기봉
    • 설비공학논문집
    • /
    • 제11권6호
    • /
    • pp.835-845
    • /
    • 1999
  • The objective of the present study was to investigate heat and mass transfer characteristics in a vertical falling film type absorber using LiBr-$H_2O$ solution with 6owt%. The experimental apparatus consisted of an absorber with inner diameter of 17.2 mm and length of 1150mm, a generator, an evaporator/condenser, a solution tank, a sampling trap etc. The parameters were solution temperature of 45 and $50^{\circ}C$, coolant temperature of 30 and $35^{\circ}C$, and film Reynolds numbers from 50 to 150. Pressure drop in the absorber increased as solution and coolant temperatures decreased. Pressure drop in the absorber increased up to the film Reynolds number of 90, and then decreased at the further increase of the Reynolds number above 90. The maximum absorption mass flux observed at the film Reynolds number of 90. Absorption mass flukes increased as coolant temperature decreased. Absorption mass fluxes and heat transfer coefficients under subcooled condition were larger than those under superheated condition. Heat transfer coefficients were affected by solution temperature more than coolant temperature. The maximum absorption effectiveness under the subcooled condition was 23% for coolant temperature of $30^{\circ}C$ and 31% for coolant temperature of $35^{\circ}C$ under the present experimental conditions.

  • PDF

이중효용 흡수식 냉온수기 동특성 모델 개발 및 실험결과 비교 (Development of a Dynamic Model for Double-Effect LiBr-$H_2O$ Absorption Chillers and Comparison with Experimental Data.)

  • 신영기;서정아;조현욱;남상철;정진희
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.109-114
    • /
    • 2008
  • A dynamic model has been developed to simulate dynamic operation of a real double-effect absorption chiller. Dynamic behavior of working fluids in main components was modeled in first-order nonlinear differential equations based on heat and mass balances. Mass transport mechanisms among the main components were modeled by valve throttling, 'U' tube overflow and solution sub-cooling. The nonlinear dynamic equations coupled with the subroutines to calculate thermodynamic properties of working fluids were solved by a numerical method. The dynamic performance of the model was compared with the test data of a commercial medium chiller. The model showed a good agreement with the test data except for the first 5,000 seconds during which different flow rates of the weak solution caused some discrepancy. It was found that the chiller dynamics is governed by the inlet temperatures of the cooling water and the chilled water when the heat input to the chiller is relatively constant.

  • PDF

이성분 나노유체($H_2O$/LiBr+나노입자)를 적용한 유하박막 흡수기의 열 및 물질전달 촉진 실험 (An Experimental Study on Falling Film Heat and Mass Transfer for Binary Nanofluids ($H_2O$/LiBr+Nanoparticles))

  • 김현대;김성수;남상철;정진희;강용태
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.130-135
    • /
    • 2008
  • The objectives of this study are to investigate the combined heat and mass transfer enhancement using binary nanofluids as the working fluids in a $H_2O$/LiBr absorber. The result of heat and mass transfer experiment with the additives(Arabicgum, 2E1H) showed that the heat and mass transfer performance of binary nanofluid with 2E1H enhanced significantly in comparison with that without additive. In the case of 0.01wt% $Al_2O_3$ binary nanofluids with 2E1H, the vapor absorption rate increased up to 77% in comparison with that without additive. The heat transfer rate of 0.01wt% $Al_2O_3$ binary nanofluids with 2E1H increased up to 19%. Based on the experimental results, it is recommended that the $Al_2O_3$ binary nanofluid be good with 2E1H to improve the heat and mass transfer performance.

  • PDF

이중효용 흡수식 냉온수기 동특성 모델 개발 및 실험결과 비교 (Development of a Dynamic Model for Double-Effect LiBr-$H_{2}O$ Absorption Chillers and Comparison with Experimental Data)

  • 신영기;서정아;조현욱;남상철;정진희
    • 설비공학논문집
    • /
    • 제20권12호
    • /
    • pp.781-788
    • /
    • 2008
  • A dynamic model has been developed to simulate dynamic operation of a real double-effect absorption chiller. Dynamic behavior of working fluids in main components was modeled in first-order nonlinear differential equations based on heat and mass balances. Mass transport mechanisms among the main components were modeled by valve throttling, 'U' tube overflow and solution sub-cooling. The nonlinear dynamic equations coupled with the subroutines to calculate thermodynamic properties of working fluids were solved by a numerical method. The dynamic performance of the model was compared with the test data of a commercial medium chiller. The model showed a good agreement with the test data except for the first 5,000 seconds during which different flow rates of the weak solution caused some discrepancy. It was found that the chiller dynamics is governed by the inlet temperatures of the cooling water and the chilled water when the heat input to the chiller is relatively constant.