• 제목/요약/키워드: 대향류형 냉각탑

검색결과 5건 처리시간 0.035초

NTU법을 이용한 대향류형 냉각탑의 성능해석에 관한 연구 (A study on the counter-flow cooling tower performance analysis using NTU-method)

  • 김영수;서무교;이상경
    • 설비공학논문집
    • /
    • 제11권5호
    • /
    • pp.598-604
    • /
    • 1999
  • The thermal performance of cooling towers is affected by the temperature of inlet water, wet bulb temperature of entering air add water-air flow rate. In this study, the effects of these variables are simulated using NTU-method and experimentally investigated for the counter-flow cooling towers. The simulation program to evaluate these variables which affect the performance of cooling tower was developed. The maximum errors between the results of simulations and experiments were 3.8% under the standard design conditions and 5.4% under the other conditions. The performance was increased up to 46~50% as the water loading was increased from $6.8m^3$/$hr\cdot m^2$ to $15.9m^3$/$hr\cdot m^2$. The range was reduced up to 56~42% when the wet bulb temperature of the entering air was increased from $22^{\circ}C\; to\; 29^{\circ}C.$

  • PDF

대향류형 냉각탑의 탈설계 성능해석 (Off-Design Performance Analysis of a Counterflow-Type Cooling Tower)

  • 신지영;손영석;한동원
    • 설비공학논문집
    • /
    • 제14권3호
    • /
    • pp.191-198
    • /
    • 2002
  • Cooling tower design procedure was set up using conventional Merkel theory, The design data could be different depending on the characteristic curve that the engineer chose. It reveals that the consistent and reasonable criteria are required based on the exact information of the cooling tower Performance. In this study, an off-design performance analysis program for a counterflow-type cooling tower was developed and verified by comparing with experimental data. Also, the off-design performance with various operating conditions was analyzed.

대향류형 냉각탑에 대한 설계 및 성능해석을 위한 수치해석적 연구 (Numerical study for performance analysis and design of a counterflow type cooling tower)

  • 이상윤;이정희;최영기;유홍선
    • 설비공학논문집
    • /
    • 제10권5호
    • /
    • pp.535-549
    • /
    • 1998
  • A numerical study for performance analysis of a counterflow type forced draft tower and natural draft cooling tower has been performed based on the method using the finite volume method with non-orthogonal body fitted and non-staggered grid system. For solving the coupling problem between water and air, air enthalpy balance, moisture fraction balance, water enthalpy balance, and water mass balance equations are solved with Navier-Stoke’s equations simultaneously. For the effect of turbulence, the standard k-$\varepsilon$ turbulent model is implied in this analysis. The predicted result of the present analysis is compared with the experimental data and the commercial software result to validate the present study, The predicted results show good agreement with the experimental data and the commercial software result. To investigate the influence of the cooling tower design parameters such as approach, range and wet bulb temperature, parametric studies are also peformed.

  • PDF

직교.대향류 충진재를 이용한 하이브리드 냉각탑에 대한 실험적 연구 (The Experimental Study of the Hybrid Cooling Tower using Cross and Counter Type Fills)

  • 전철호;이호생;이호출;문춘근;김재돌;김은필;윤정인
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2005년도 후기학술대회논문집
    • /
    • pp.236-237
    • /
    • 2005
  • An experimental study on the Hybrid Cooling Tower has been done having a rated capacity of 3RT. Counter flow type fill, cross flow type fill and hybrid-type fill which is combined with two type fills as previously stated having a height of 0.3m have been used in the 0.8m${\times}$0.4m${\times}$1.9m dimensional tower respectively. The heat exchanger is consisting of 2 or 3 rows. The relevant temperatures and the velocities were selected based on the typical Korean weather for the year round operation of the tower. The cooling capacity of the tower is explained with respect to varying air inlet velocities, wet-bulb temperatures, and air to cooling water volume flow rate ratio (L/G ratio). The capacity of the hybrid-type fill was much superior to other fills, but hybrid-type fill shows higher pressure drop.

  • PDF

충진재(Filler)가 대향류형(Counter Flow Type) 냉각탑 유동에 미치는 영향에 대한 연구 (Effect of Filler on the Flow of Counter Flow Type Cooling Tower)

  • 신정훈;이준경;진철규
    • 한국산업융합학회 논문집
    • /
    • 제25권4_2호
    • /
    • pp.565-572
    • /
    • 2022
  • The white plume from the cooling tower can be generated by mixing between discharging hot and humid air and cold air outside. This causes various problems such as icing, traffic disturbances, and fire factors in the vicinity, moreover it can also damage the image of a company. Various methods can be used to prevent white plume, one of them is to install a heat exchanger at the outlet of the cooling tower so that the heat exchanger transfers as much heat as possible to lower the temperature. Therefore the air flow path in the cooling tower should be optimized. Installation of the filler can be used to make the air flow better, thus we investigate the effect of filler on the air flow using CFD method. The pressure and velocity profile in the cooling tower could be acquired by the calculations. The filler made the velocity of the air entering the heat exchanger uniform this was because high flow resistance of the filler suppresses the generation of eddy in the cooling tower. But the total air pressure drop increased about 2 times with filler because the pressure drop by the filler accounted for about 60% of the total pressure drop.