Flow Control of a Centralized Cooling Plant for Energy Saving (중앙식 냉방 플랜트의 유량제어를 통한 에너지 절감에 관한 연구)

  • Lee, Jeong Nam;Kim, Young Il;Chung, Kwang Seop
    • Journal of Energy Engineering
    • /
    • v.24 no.3
    • /
    • pp.48-54
    • /
    • 2015
  • In a centralized cooling plant, precise mechanical design and control strategy are required for peak and partial cooling load management. Otherwise, it will lead to low efficiency of cooling system and energy loss due to low partial load efficiency. The purpose of this paper is to enhance energy performance of the centralized cooling plant by controlling flow system in an industrial building using measured data and energy performance simulation program. The simulation results show that the proposed flow control can cut down annual electric power consumption by about 17% compared with the conventional cooling system.

Characteristic Analysis of Hybrid Desiccant Cooling System for District Heating in Residential Environment (지역난방에 연계된 하이브리드 제습냉방시스템의 주거환경에서의 성능 분석)

  • Ahn, Joon;Kim, Jaeyool;Kang, Byung Ha
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.38 no.7
    • /
    • pp.571-579
    • /
    • 2014
  • A series of field tests on hybrid desiccant cooling systems were conducted in July-August, 2013. The temperature and humidity of the supply and return air, power, and heat consumption were monitored and transferred in real time through the Internet. The performance parameters of the cooling system, namely, cooling capacity and COP (coefficient of performance), were evaluated from the measured data and their variations under outdoor conditions was analyzed. It was found that with increase in the outdoor temperature, the total energy decreases and cooling capacity increases whereas the latter decreases with increase in the outdoor humidity. The COP was also found to increase with the increase in outdoor temperature.

Performance Characteristics of the Electrical Air Conditioning System for the Zero Emission Passenger Vehicle (무공해 승용 자동차의 냉방을 위한 전동식 냉방시스템 성능에 관한 연구)

  • Lee, Moo-Yeon;Cho, Chung-Won;Lee, Ho-Seong;Won, Jong-Phil
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.12 no.12
    • /
    • pp.5430-5437
    • /
    • 2011
  • The objective of this study is to investigate the cooling performances of the electrical air-conditioning system using electric driven scroll compressor for zero emission passenger vehicles. This air conditioner with air source was used R-134a as a refrigerant and installed in a real zero emission passenger vehicle for tests under various driving conditions. The cooling performance of the electrical air conditioner was affected by driving velocities and conditions of the tested vehicle. The condensing rate of the condenser during driving is better than that of the idle condition. The average cool down temperature in the cabin room decreased on average $5.2^{\circ}C$ with the increase of the outdoor temperature from $20.0^{\circ}C$ to $30.0^{\circ}C$. In addition, the cooling performances were sufficient for cooling loads of the tested passenger car under tested conditions.

사무소건물의 에너지절약형 냉방시스템 적용 검토

  • Park, Chang-Bong
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.40 no.9
    • /
    • pp.23-37
    • /
    • 2011
  • 에너지절약형 냉방시스템은 에너지절약효과에 대한 성능자료 부족 및 초기투자비 부담으로 적용이 미흡한 실정이다. 사무소 건물에 적용 검토한 냉방시스템을 소개하고자 한다.

  • PDF

A Study on Cooling Performance and Exergy Analysis of Desiccant Cooling System in Various Regeneration Temperature and Outdoor Air Conditions (재생온도와 외기조건 변화에 따른 제습 냉방시스템의 냉방 성능 및 엑서지 해석에 관한 연구)

  • Lee, Jang Il;Hong, Seok Min;Byun, Jae Ki;Choi, Young Don;Lee, Dae Young
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.38 no.5
    • /
    • pp.413-421
    • /
    • 2014
  • Desiccant cooling system is an air conditioning system that uses evaporative cooler to cool air and it can perform cooling by using heat energy only without electrically charged cooler. Thus, it can solve many problems of present cooling system including the destruction of ozone layer due to the use of CFC[chloro fluoro carbon] affiliated refrigerants and increase of peak power during summer season. In this study, cooling performance and exergy analysis was conducted in order to increase efficiency of desiccant cooling system. Especially, using exergy analysis based on the second law of thermodynamics can resolve the issue related to system efficiency in a more fundamental way by analyzing the cause of exergy destruction both in whole system and each component. The purpose of this study is to evaluate COP[coefficient of performance], cooling capacity and exergy performance of desiccant cooling system incorporating a regenerative evaporative cooler in various regeneration temperature and outdoor air conditions.

Study on Improvement of Air Conditioning Units for Anti Aircraft Gun Wheeled Vehicle (차륜형 대공포 냉방장치 성능개선 연구)

  • Jeon, Ki-Hyun;Lee, Dong-Hui;Lee, Boo-Hwan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.37 no.12
    • /
    • pp.1099-1103
    • /
    • 2013
  • A combat vehicle needs to have an air-conditioning unit. Accordingly, new combat systems have tended to apply an integrated heating, cooling, and ventilating system. The air conditioning unit used depends on the combat vehicle's purpose of use. In this study, we studied an air-conditioning unit for an armored combat vehicle as a special use and military specification and tried to improve the air-conditioning unit's performance.

Experimental Study on Cooling Performance of Multi-Heat Pump by Indoor-Unit Combination (실내기 조합에 따른 3실형 열펌프의 냉방성능 실험연구)

  • Kwon, Young-Chul;Chun, Chong-Keun;Park, Youn-Chang;Ko, Kok-Won;Seo, Dong-Nam
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.6
    • /
    • pp.1487-1493
    • /
    • 2008
  • In order to investigate the cooling capacity of multi-heat pump applying an inverter compressor, the experiment on the cooling performance characteristics of heat pump with 3 indoor units was performed under the cooling standard and cooling low-temperature conditions. The system data were measured by the psychrometric calorimeter. The operation characteristics and the behavior of the cooling cycle of the heat pump with 3 indoor units were understood from the cooling capacity, COP, and P-h diagram by indoor-unit combination. The operating load and performance of the multi-heat pump depends on the indoor-unit combination. The cooling capacity and COP of the low temperature condition were larger than those of the standard one. Also the cycle was analyzed by using P-h diagram.

Study on Cooling Performance Characteristics of Air Conditioning System Using R744 for a Passenger Vehicle (이산화탄소를 적용한 승용자동차 냉방시스템의 성능특성에 관한 연구)

  • Lee, Ho-Seong;Cho, Chung-Won;Won, Jong-Phil;Lee, Moo-Yeon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.12 no.12
    • /
    • pp.5457-5463
    • /
    • 2011
  • The objective of this study is to investigate cooling performance characteristics of mobile air conditioning system using R744 as an alternative of R-134a. In order to analyze the cooling performance characteristics of the air conditioning system using R744 for a passenger vehicle, the developed air conditioning system using R744 was applied in a real passenger vehicle and tested under various operating conditions with the variation of gas-cooler inlet air conditions, evaporator inlet air temperatures and compressor speeds. As a result, cooling capacity and coefficient of performance (COP) of the tested air conditioning system decreased with the rise of the inlet air temperature of the gas cooler but increased with the rise of the inlet air temperature of the evaporator. In addition, cooling capacity and coefficient of performance (COP) increased by 42.2 % with the rise of the compressor speed from 900 rev/min to 1800 rev/min, but it decreased by 55.4%.

Capacity Modulation of a Ground Source Multi-Heat Pump in the Part Load Condtions (축열형 지열원 냉난방 시스템의 단기 성능 특성 연구)

  • Kim, Namtae;Cho, Chanyong;Choi, Jong Min
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2010.11a
    • /
    • pp.119-119
    • /
    • 2010
  • 무한 지속 가능한 지열 에너지를 활용한 공조시스템인 지열원 냉난방 시스템은 기존의 공조 시스템보다 열원이 안정적이기 때문에 높은 효율과 우수한 성능을 가지므로, 기후변화협약 대응의 주요수단으로서 기술개발과 보급이 증대되고 있다. 본 연구에서는 대수층 축열 지열원 열펌프 시스템에 대한 실증 연구를 통하여 대수층 축열 지열원 열펌프 시스템의 하절기 냉방 성능을 분석하였다. 대수층 축열 냉난방 시스템은 주입정과 양수정의 2개의 우물공이 설치되어 있으며, 겨울 난방 운전 중에 한 개의 우물공으로부터 지하수를 열펌프로 유입한 후 낮은 온도의 지하수를 타 우물공에 축열하고, 하절기에 겨울에 저온으로 축열된 우물공으로부터 지하수를 열펌프로 유입하여 온도가 증가된 지하수를 타 우물공에 주입한다. 즉, 계절별로 열펌프에서 생성된 냉수와 온수의 대수층 축열을 위하여 계절별로 주입정과 양수정이 바뀌게 된다. 본 연구의 대수층 축열 지열원 열펌프 시스템의 2009년 8월의 주요일자별 시스템 운전 중의 평균 냉방 열펌프 유닛 COP와 냉방 시스템 COP는 각각 4.7과 3.4이상의 우수한 성능을 나타냈다. 또한, 모든 일자에 대하여 외기온도가 $31.6^{\circ}C$$22^{\circ}C$까지 변화가 크게 나타났지만 열펌프 유닛 COP와 시스템 COP의 변화는 미소하였다. 이는 양수정으로부터의 지중 순환수가 운전기간 중에 $17.5^{\circ}C$로 일정하게 유지되었기 때문이다. 양수정과 주입정 사이에 5개의 관측공을 설치하였으며, 양수정 측에 인접한 관측공의 온도는 거의 변화가 없었으며, 단기간이지만 널리 사용되고 있는 수직밀폐형 시스템과 달리 지속적인 냉방운전 중의 양수 온도의 증가는 발생하지 않아 안정적인 성능을 나타냈다. 주입정에 인접한 모니터링 홀의 온도는 심도가 깊은 곳의 온도가 낮은 곳보다 높게 나타났다. 이는 냉방 운전 시 열펌프 유닛의 실외열교환기에서 지중 순환수가 냉매로부터 열을 취득하여 온도가 상승하면서 주입정측에 온열이 축열이 진행되었기 때문으로 분석되며, 하절기의 냉방 운전 시간이 증가할 경우 축열 효과는 더욱 증가할 것으로 예상된다. 양수정과 주입정 중간의 모니터링 홀의 온도는 2009년 8월 가동 중에 온도변화는 없었는데, 이는 양수정과 주입정 사이의 열간섭이 발생하지 않았기 때문으로 분석된다. 일자별로 운전 중의 열펌프 유닛 COP는 차이가 없었지만, 운전 및 정지 시간을 모두 포함한 시스템 소비전력과 냉방용량을 모두 합산하여 산정한 일일 평균 냉방 열펌프 유닛 COP와 냉방 시스템 COP는 일자별로 다소 차이가 발생하였는데, 이는 각 일자별로 열펌프 유닛 가동율의 차이로 인하여 열펌프 유닛 가동 전에 먼저 작동되는 지중순환펌프의 운전 소비전력의 차이와 열펌프의 단속운전 시의 열손실과 추거 소비전력의 차이 때문이다.

  • PDF

Experimental study on cooling performance characteristics of hybrid refrigeration system in a heavy duty vehicle (상용차 하이브리드 냉방시스템 냉방 성능 특성 연구)

  • Lee, Ho-Seong;Jeon, Hanbyeol;Kim, Jung-Il;Lee, Moo-Yeon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.20 no.1
    • /
    • pp.419-425
    • /
    • 2019
  • The objective of this study was to investigate the cooling performance characteristics of a hybrid refrigeration system in a heavy duty vehicle. The tested hybrid refrigeration system had additionally an electric compressor besides the present mechanical compressor for selective use according to the operating conditions. The applied electric compressor was a scroll type and with 18.0 cc displacement. In order to analyze the performance characteristics of the hybrid refrigeration system with respect to the cooling capacity and Coefficient of Performance (COP), other components, including two different types of compressors, were installed and tested under various operating conditions such as compressor speed and air flow rate of the evaporator. When the electric compressor was operated at 4,500 rev/min, the cooling capacity was about 4.0kW and COP was 3.5. When the mechanical compressor was operated, whereas the cooling capacity was higher than the electric controlled compressor, COP was lower due to the larger displacement and higher power consumption. To analyze the hybrid system operating characteristics due to reasonable cooling capacity with electric compressor operation, the mechanical compressor and electric compressor were operated by turns every 10 minutes under certain system operating conditions. Because surge pressure occurred when both compressors were switched on, the operating strategy required some time to balance the system pressure.