Analysis of the cause of insulation breakdown in Transmission cable EB-A (지중송전케이블 기중종단접속함 절연파괴 원인분석)

  • Moon, Kyoung-Hee;Kang, Ji-Won;Kim, Jong-Chae
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.511-512
    • /
    • 2011
  • 본 논문에서는 154kV 지중송전선로의 기중종단접속함 (EB-A)에서 발생한 절연파괴 고장을 분석하여 정확한 원인을 규명하고자 한다. 케이블 결함은 제조 공정에서 철저히 걸러내도록 조치하고 케이블 공장 출하시 시험을 통해 점검하고 있어, 고장은 케이블 자체 보다 현장에서 시공하는 접속함에서 발생할 우려가 매우 크다. 따라서 접속함 시공은 케이블의 안정적인 운전을 위해 매우 중요한 공정으로 접속작업 후 성능이 케이블과 동등 이상의 특성을 유지하도록 하여야 한다.

  • PDF

Seismic Performance Evaluation of 500 kV EBA (500 kV 기중종단접속함의 내진성능평가)

  • Jeon, Bub-Gyu;Jung, Chi-Young;Jin, Jung-Woon;Kim, Han-Hwa;Cheung, Jin-Hwan
    • Transactions of the Korean Society for Noise and Vibration Engineering
    • /
    • v.25 no.7
    • /
    • pp.496-502
    • /
    • 2015
  • In this study, seismic performance tests for 500 kV EBA are conducted through the IEEE Std. 693. It is hard to conduct both the static tests and dynamic tests for 500 kV EBA as IEEE Std. 693 because the size of specimen, 9 m in height, is too large to be examined. To do so, it can cause the unnecessary time and cost, and also the damage on the specimen. However, in this study, both static tests and dynamic tests are conducted in the same test field as IEEE Std. 693 to achieve more accurate and reliable test results. From the test results Taihan Electric Wire Co. can win contract for 500 kV extra-high voltage project in the U.S.A., therefore it can be evaluated that the tests are conducted successfully and the capability to estimate large electric power facilities are achieved as IEEE Std. 693.

DC Electric Field Characteristics considering Thermal Effect for HVDC Slip-on Type Outdoor Termination (HVDC 슬립 온형 기중 종단접속함에 대한 열 영향 반영 DC 전계 특성 평가)

  • Kwon, Ik-Soo;Hwang, Jae-Sang;Koo, Jae-Hong;Sakamoto, Kuniaki;Lee, Bang-Wook
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.1 no.1
    • /
    • pp.39-46
    • /
    • 2015
  • A outdoor termination installed at the outdoor substation is required to connect undergroud cables and overhead transmission lines. The joint box for AC transmission system is already developed and widely used to interconnect overhead and undergroud systems. But the development of the joint box for DC transmission system was only introduced from China and Japan, but theire developemnt staus and core technologies were not fully reported. In order to implement HVDC systems connecting ovehead transmission lines and undergroud cables, a outdoor termination should be developed, but the detailed specifications and information of this device were not reported. It is estimated that the development of the joint box for DC environment has some technical obstacles including insulating materials, electric field mitigation, thermal temperature rise, and space charge accumuations. Among this, the most important one is the DC elctrical insualtion design. Therefore, in order to investigate the DC elctrical insualton design of outdoor termination, the design of AC slip-on type outdoor termination is reffered, and DC electric field analysis performed to verify the possiblity of application of AC joint box into DC joint box. Especially for DC electric field analysis, temperature rise of insualting materials of a joint box was considered, because the conductivity of materials could be changed due to temperature rise. Furthermore, DC electric field analysis considering transinet state, and polarity reversal state were also investigated to verify which state is the most severe condition for the DC joint box. From the simualtion resulsts, it was shown that the value and the position of maximum electric field was obtained comparing AC state, DC state without temperaure rise, and DC state with temperaure rise. And it was confimred that severe DC electric field was observed considing temperaure rise. Finally, in order to reduce DC eletric field intensifation, different configuration of the joint box was applied and it was not possible to obtain satisfactory results. It means that the slight change of configuration of AC joint box was not the suitable soluton for DC joint box. It is essential to establish novel DC insulaton design skills and method for DC joint box to commercialze this product in the near future.

Development of 132kV XLPE Cable Composite Bushing EB-A (132kV XLPE Cable용 Composite Bushing 기중종단접속함 개발)

  • Kim, J.H.;Oh, E.J.;Kim, K.Y.;Park, J.K.;Jeoung, Y.W.
    • Proceedings of the KIEE Conference
    • /
    • 2000.11c
    • /
    • pp.547-549
    • /
    • 2000
  • Silicone insulators have many advantages over porcelain insulators. Especially silicone insulators have good characteristics of impact hardness, surface insulation, ease of processing, mass productivity and don't have risk of bombardment and vandalism. Recently insulation part made by silicone are becoming widely used. In this paper we introduce the development of Sealing End for 132kV XLPE cable with silicone composite hollow insulator and the adoption of it to a actual transmission line in abroad. This paper contains of design procedure, structure, electrical performance of it.