• Title/Summary/Keyword: 기류속도

Search Result 108, Processing Time 0.027 seconds

The Analysis on the Effect of Supply Air Velocities by Location of Supply Air Damper on the Performance Efficiency of the Smoke Exhaust Systems (공기유입구 위치에 따른 유입공기의 풍속이 배연시스템 성능효율에 미치는 영향 연구)

  • Yeo, Yong-Ju;Lim, Chae-Hyun;Kim, Hak-Jung;Kim, Bum-Gyu;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.24 no.6
    • /
    • pp.20-27
    • /
    • 2010
  • In smoke control systems the amount of air supply is almost the same as that of smoke exhaust. This study analyzed the effect of supply air velocity on the smoke exhaust behavior using FDS tool. The results showed that fire plume can be disheveled by the rapid air velocities developed when the air supply inlet is located near the fire plume. Disheveled smoke caused the rapid descent of smoke layer level and the reduced visibility. To increase the efficiency of smoke exhaust systems supply air inlet should be located sufficiently far from the location of the fire plume.

A Study on the Smoke Movement by the Opening and Heat Generator Position (개구부와 열원의 위치에 따른 연기이동에 관한 연구)

  • 조성우;이재윤
    • Fire Science and Engineering
    • /
    • v.16 no.4
    • /
    • pp.7-14
    • /
    • 2002
  • The diffusion characteristics of the smoke by effect of an ascending air movement in a local part of the room where heat generated was studied. How the smoke move in the limited parts of the room at which heat generated was studied through 3 cases altering locations of inlet and outlet of ventilated air and heat generated by CFD(Computational Fluids Dynamics) method. It was found that 1. Similar distribution of air velocity, air temperature and smoke concentration appeared in the case of upper left inlet and lower right outlet and the case of lower inlet and upper right outlet. 2. Distribution of temperature and smoke concentration was 0∼0.3, 0.06∼0.14 in the case of lower left inlet and upper right outlet. 3. the location of heat generation did not influence on the temperature distribution, but influence on the distribution of smoke concentration.

CTP시장 지각변동 예고

  • Kim, Chang-Ryun
    • 프린팅코리아
    • /
    • s.4
    • /
    • pp.66-69
    • /
    • 2002
  • CTP장비의 국내 보급속도가 제트기류를 탈 전망이다. 지난 KIPES2002(국제인쇄산업전시회)를 전후해 CTP장비 보급업체가 크게 늘어나고 있기 때문이다. 프리프레스장비 공급업체에 따르면 KIPES를 전후해 CTP장비에 대한 상담건수가 날로 증가하고 있을 뿐만 아니라 총 9대를 계약한 것으로 조사돼 앞으로 더욱 늘어날 것으로 기대되고 있다.

  • PDF

Activation Conditions of Sprinkler Head Considering Fire Growth Scenario (화재성장시나리오에 따른 스프링클러 헤드의 작동조건)

  • Kim, Sung-Chan
    • Fire Science and Engineering
    • /
    • v.34 no.4
    • /
    • pp.45-51
    • /
    • 2020
  • The aim of this study is to investigate the gas temperature and velocity during sprinkler activation considering the fire growth scenario based on the thermal response model of the sprinkler. The fire source is assumed to have time square fire growth scenarios with a maximum heat release rate of 3 MW. Eight types of standard and fast-response sprinkler heads with an operating temperature range of 65-105 ℃ and a response time index range of 25-171 m1/2s1/2 were adopted. The temperature difference between the gas stream and the sensing element of the sprinkler head decreased as the fire growth slowed down, and the RTI value decreased. The overall gas temperature and velocity conditions predicted using the FDS model at sprinkler activation were in reasonable agreement with those of standard test conditions of the sprinkler head response. However, the sprinkler head could be activated at lower limits of gas temperature and velocity under the current test conditions for a slowly growing fire scenario.

The Fundamental Study on the Parameter Identification of Station Storm Model (지점 호우 모형의 매개상수 동정의 관한 기초 연구)

  • Lee, Jae Hyoung;Ceon, Ir Kweon;Cho, Dae Hyun
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.12 no.2
    • /
    • pp.123-130
    • /
    • 1992
  • We check up on whether the one-dimensional station precipitation model of Geogakakos and Bras is suitable to the storm model for Chonju station or not. The fundamental variables of the physically based model consists of the pressure at the cloud top, the hight-averaged updraft velocity(HAUV), and the inverse of the average diameter of the hydrometeors(ADH) at cloud base. And they are parameterized by input variables. The parameters are eastimated by the direct search algorithm of Hooke and Jeeves in this paper. The results show that HAUV and ADH are dominant factors to minimize root mean square error between the calculated and the observed rainfall. In this numerical analysis, the deviation between the calculated and the total observed rainfall is small, otherwise the gap for the time distribution is quite big.

  • PDF

Investigation of amount of the Air Flow through a Natural Ventilator in the Subway System (지하철 자연환기구 공기 이동량 조사)

  • Bae, Sung-Joon;Hwang, Sun-Ho;Shin, Chang-Hun;Kim, Shin-Do;Lee, Kyoung-Bin;Park, Duck-Shin
    • Proceedings of the KSR Conference
    • /
    • 2011.05a
    • /
    • pp.1480-1486
    • /
    • 2011
  • After installation of platform screen door (PSD) in subway stations, particulate matters (PMs), which are originally ventilated through the platform, are accumulated inside the tunnel of the subway system. It deteriorates an air quality inside the tunnel. To ventilate the accumulated PMs inside the tunnel, the natural ventilator which are located inside the tunnel (namely, tunnel ventilation system) are used as only one circulation system. In addition, the installation of PSD can affect to the aerodynamic variations inside the tunnel, since the PSD system was not considered factor when the tunnel ventilation system was designed. However, the researches about the tunnel ventilation system have not been adequate. Therefore, this study is carried out with two objectives: 1) to measure the velocity of air current by the train-induced wind, when the train passes through the tunnel, and 2) to investigate the typical patterns of air current by quantitatively evaluating the characteristics of inflow/outflow of air current which passes through the natural ventilation system. This study can suggest the basic standard to newly design the tunnel of the subway system as well as the ventilation system.

  • PDF

A Study on Estimation of Ventilation Performance in the Underground Parking Lot (지하 주차장의 환기성능평가에 관한 연구)

  • Hwang, Min-Kyu;Kim, Seong-Sik;Kim, Kang-Soo
    • Journal of the Korean Solar Energy Society
    • /
    • v.27 no.3
    • /
    • pp.71-77
    • /
    • 2007
  • In past, parking lot was placed on the ground and for the reason air quality was not in problem. But recently parking lot has been placed under the ground and the air quality becomes problem. So in this study, the ventilation performance on the underground parking lot was estimated by using CFD software and alternative system was suggested. Three case studies are handled in this study. 1st case is just an underground parking lot. 2nd case is about an underground parking lot where has 4 fan rooms on each floor and 3rd case is about an underground parking lot where has 4 fan rooms and 30 guidance fans on each floor.

An experimental study on the evaporation of paraffin family fuel droplet under high temperature and high pressure (고온 고압기류중을 비행하는 파라핀계 연료액적의 증발에 관한 연구)

  • ;川口修
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.15 no.6
    • /
    • pp.2125-2131
    • /
    • 1991
  • Evaporation rate constant, obtained by in this experimental study, of freely falling liquid fuel droplet on the condition of hot and pressurized environment are converted to critical evaporation constant according to Eq. of Ranz and Marshall. Critical evaporation constant, on constant environment pressuire, actively increase almost linearly with environment temperature increasing, but, on constant temperature, increases more or less with pressure increasing. Multycomponent droplet mixed with the fine fuel having a different of boiling point evaporate in order to boiling point, and each evaporation rate constant of mixed fuel equal to each fuel.

Growth and Development of Potato Plug Seedlings as Affected by $CO_2$ Enrichment ($CO_2$ 시용이 감자 플러그묘의 생육에 미치는 효과)

  • 김용현;최유화;이명규
    • Proceedings of the Korean Society for Agricultural Machinery Conference
    • /
    • 2003.07a
    • /
    • pp.402-406
    • /
    • 2003
  • 묘생산 시스템은 크게 개방형과 폐쇄형으로 구분된다. 개방형 묘생산 시스템은 시스템 내부와 외부의 공기ㆍ물ㆍ열 등의 교환이 가능한 시스템을 의미한다. 현재 실생묘, 삽목묘, 접목묘 등은 일사가 투과되는 온실 또는 묘포장에서 생산된다. 그러므로 온실 또는 묘포장을 이용한 묘생산 시스템은 개방형 묘생산 시스템에 해당한다. 개방형 묘생산 시스템에서는 외부기상의 변동에 따라 시스템 내의 기온, 상대습도, 광량, 기류속도, $CO_2$ 농도 등의 물리적 환경요인이 변화하므로 이들 환경 요인을 일정한 수준으로 제어하기가 쉽지 않다. 때문에 균일한 묘소질을 지닌 묘의 계획적 생산이 근본적으로 불가능하다. (중략)

  • PDF

The Study on Indoor Thermal Environment during Convection Heating - Thermal Comfort by Indoor Air Temperature and Velocity - (대류난방시 실내열환경에 관한 연구 - 온도 및 기류속도에 대한 온열쾌적감-)

  • Kim Dong-Gyu;Chung Yong-Hyun
    • Journal of Environmental Science International
    • /
    • v.14 no.2
    • /
    • pp.209-214
    • /
    • 2005
  • Draft is defined as an unwanted local cooling of the human body caused by air movement. It is a serious problem in many ventilated or air conditioned buildings. Often draft complaints occur although measured velocities in the occupied zone maybe lower than prescribed in existing standards. Purpose of this study is to clarify the evaluation of thermal comfort based on temperature and air velocity in winter. Experiments were performed in an environmental chamber in winter. Indoor temperature and air velocity was artificially controlled. The experiments were performed to evaluate temperature conditions and air velocity conditions by physiological and psychological responses of human. According to physiological responses and psychological responses, it was clear that the optimum air velocity is about 0.15 m/s and 0.30 m/s.